Westinghouse WGen20000 Powering ENTIRE HOUSE with (5 TON Central A/C) Generator Review.

Поделиться
HTML-код
  • Опубликовано: 25 июн 2022
  • Westinghouse WGen20000 powering my 5 ton A/C
    Amazon Link amzn.to/3buNnvo
  • НаукаНаука

Комментарии • 221

  • @tommysteele615
    @tommysteele615 10 месяцев назад +30

    Just note. In order to get all 20000watts, you have to use both of the 50A outlets. That has to feed 2- double 50A breakers in a sub panel via 6awg wire. Then from sub panel you feed your main panel to a 100amp breaker via 2awg. This gets you all of the 20000 watts. Using 1- 50A outlet only gets you 12500 watts.

    • @kevinanglin678
      @kevinanglin678 8 месяцев назад

      Is this how you have yours wired up?

    • @danduv1
      @danduv1 6 месяцев назад +1

      If my generator has a 50A and 30A, could I do this with the corresponding 50A/30A breakers in subpanel and 80A in main?

    • @joshsinglefooter
      @joshsinglefooter Месяц назад

      So what you're saying is the 12,500 powered his house. Basically, it did it with one hand behind its back. That what you're saying?

    • @lawjilei
      @lawjilei 12 дней назад

      Finally someone presents a solution

  • @SuperRobkar
    @SuperRobkar 2 года назад +5

    That generator is a beast. When you install that soft starter it won’t even blink.

  • @israelgriffin585
    @israelgriffin585 Год назад +13

    Make sure you treat the fuel and turn the fuel switch off to let the generator shut down on its own. That will clear the fuel in the carburetor. Then turn off the power switch. Be blessed and a blessing Amen.

    • @0409jd
      @0409jd Месяц назад +1

      Also a good idea to let it run at idle for 10 min or so after being on a load to let it cool down, then turn off the fuel to bleed the carb.

  • @heimdallblows179
    @heimdallblows179 Год назад +4

    Looking forward to your more in-depth on this beast. I am pretty much sold on the Genmax GM9000iED but this thing is really making me think. I have planned on gettin 2 Genmax and running them in parallel. That would get me by with not much extra. But the WGen20000 would power my house and I have another 50 amp line to help others out. Thank you for all you do!

    • @donelias1981
      @donelias1981 Год назад

      I’m battling the same dilemma, I am worried about my electronics as I just had to replace a 75in TV that was only a few years old. I’m unsure if it was just a normal failure or caused by the few times we lost power and had back up for an extended period of time. Was just about sold on the GENMAX 9k which matches the Westinghouse I have now but been thinking of upgrading to a larger unit.

  • @utubetjc
    @utubetjc 2 года назад +2

    Thanks Gavin. Very impressive review as expected!

  • @rockystelone21
    @rockystelone21 2 года назад +4

    That's a beast of a portable generator.

  • @yonathanevan3334
    @yonathanevan3334 11 месяцев назад

    Perfect design snd and power for large camper.

  • @garden-queen2393
    @garden-queen2393 2 года назад +2

    Amazing 👍. Great job thanks.

  • @Tom-In-Ga
    @Tom-In-Ga 2 года назад +8

    I'll never need something like that but that was a great demo! Very entertaining.

  • @defjamsgreen
    @defjamsgreen 2 года назад +5

    YOU HAVE A SUPER GENERATOR AND AT 28000 WATTS , IT IS A BEAST . AWSOME VIDEO .👍👍🤗

  • @patrickcoleman5867
    @patrickcoleman5867 Год назад +8

    What about part 2 show more of this monster. I sold my Generac 17500 and ordered this generator. Less then 5% THD is a game changer.

  • @christophersustayta5974
    @christophersustayta5974 Год назад

    Excellent excersize !

  • @jamesprice34120
    @jamesprice34120 Год назад +2

    I have this generator on order. My house is fully electric and uses a lot of power. The 83 amp circuit breaker is the main breaker.

  • @DIYRAYMOND
    @DIYRAYMOND 11 месяцев назад +6

    I just ran my 5 ton 14seer AC unit with my predator 8750 ran it with no problem. I turned off all the other breakers while we ran the AC. Then when we were satisfied with the temperature we turned it off and ran the other breakers.

  • @shanew7361
    @shanew7361 2 года назад +3

    Great video 🇺🇸🙏💪

  • @jeffreypinder9398
    @jeffreypinder9398 Год назад

    You have solar as well, you are def covered for power for the worst of weather. Great job, Gavin.

  • @jamesappling1212
    @jamesappling1212 Год назад +1

    Big Dog for the Big Jobs, add a little Puppy on the side for the light work. (Small fuel saver generator or Solar for light duty situations).

  • @sshvulnerability
    @sshvulnerability 5 месяцев назад +1

    You can put a soft start kit on the hvac compressor so it doesn't pull that much power on start up.

  • @jonlee5642
    @jonlee5642 2 года назад +1

    Gotta do a whole house test with the duromax trifuel! Has a less then 5% tbd

  • @CycleST1300
    @CycleST1300 2 года назад +7

    What a beast! I don't believe I'd want to feed it though, uses about 1 1/2 gallons per hour at 50%.

    • @shanew7361
      @shanew7361 2 года назад +12

      I agree especially with Biden gas prices.

    • @lifeenglightment7977
      @lifeenglightment7977 Год назад +5

      You will wish to have when the time comes. You’re not buying it due to the gas price; you obtain it because it ensures you the peace of mind for the rest of your family. You can not stop the natural disaster, but you can work really smart to minimize the impact.

    • @SouthPawEd
      @SouthPawEd Год назад +4

      It's something like 11hrs on 17gal @ 50% load. However, 50% constant load is *a lot* for this generator. I got this unit a little more than a year ago and had to run it one night. Ran it for about 9hrs on just under a half tank of fuel. It ran a few lights, a tv, and my 2, 2.5 ton hvac units. For about 7hrs of that 9hrs, we were sleeping, so only the hvacs ran.

  • @clintondoner1133
    @clintondoner1133 4 месяца назад +1

    THE BEAST!!! My 4,400 name starts with a B and it is not beast!!! Great Show!!!

  • @SouthPawEd
    @SouthPawEd 2 года назад +6

    I just got this generator delivered on Friday. I have it setup with 2, 50amp inlets--1 for each of my 2 panels. We have 2, 2.5 ton units. I don't know if I'll be trying to run both at the same time though. That 5 ton pulled her right down. Definitely a stout unit.

    • @busterhyman6633
      @busterhyman6633 Год назад

      can you back feed two panels simultaneously

    • @SouthPawEd
      @SouthPawEd Год назад

      @Buster Hyman Yes. I was able to power both panels and run both a/c units plus lights/ceiling fan/tv. I want to get some meters to see how much power we're using, but for all intents and purposes, it "powered my house."

    • @brucewillis7135
      @brucewillis7135 5 месяцев назад

      ​@@SouthPawEdcan you use two separate generators two power those panels

    • @SouthPawEd
      @SouthPawEd 5 месяцев назад

      @@brucewillis7135 This is the only portable generator that I have seen that puts out more than 50 amps, and that's only because it has 2, 50 amp outlets that put out 50 amps each. I haven't seen any portable generators that provide more than 50 amps from a single outlet, nor have I seen power cables that could handle more than 50 amps, so I don't think that I could fully-power each panel, even with 2 generators. These panels are each 100 amps, and as it is, I feed them 50 amps each. This more than powers anything that we need, short of running the washer, dryer, dishwasher, and heating systems simultaneously.

    • @SouthPawEd
      @SouthPawEd 18 дней назад

      ​@brucewillis7135 I suppose if nothing on those panels overlapped, you could use 2 generators. On mine, the downstairs condensing unit is on panel A and the downstairs air handler unit is on panel B. The upstairs system is divided similarly. I was advised by my electrician to power both panels with my one generator.

  • @westinghouse
    @westinghouse 2 года назад +1

    Thanks for sharing!

    • @GeneratorReviews
      @GeneratorReviews  2 года назад +1

      Thanks for watching
      Looking forward to future collaboration with you.

    • @joeriddell1
      @joeriddell1 Год назад

      @Westinghouse can you explain how (and if) you can run two cords out of the 50 amp outlets into 1 200 amp house panel? Thanks!

  • @tonyd3266
    @tonyd3266 Год назад +1

    Property 1: FL: The more I watch these videos, the more I like the idea of a generator under $800 and a $200 walmart window AC unit that runs on 110v. (im in FL so not concerned with the high KW for heating). not having natural gas on property is a huge limit locally. Property 2: I have free "dirty" natural gas - in a rural area with mining and frequent power outages for 6h-3d, at least 3 times a year. there we do have freeze warnings. Anyone else running a dirty nat. gas line off a wellhead into one of these ? what, if anything, do you put inline to filter water/etc and regulate pressure?

  • @OptimalTraining
    @OptimalTraining 2 года назад +21

    With that generator you could power two houses

    • @leoschneider3570
      @leoschneider3570 Год назад +5

      I purchased one, and one time for an extended power outage I ran one of the 50 amps to my neighbor’s house

    • @tw9433
      @tw9433 10 месяцев назад +1

      I’m guessing it’s crazy loud though? I want an inverter for the quietness but love the idea of having that much power with this big boy

    • @user-ui4iv8dz3w
      @user-ui4iv8dz3w 10 месяцев назад

      2 you mean 4.

    • @OptimalTraining
      @OptimalTraining 10 месяцев назад

      @@user-ui4iv8dz3w , True I guess you could power four houses. 😃

  • @JM-fm7dy
    @JM-fm7dy 2 года назад +6

    Hey Gavin, I have this gen hooked up to are house with two 50amp rv cords to run are 5ton geothermal no softstart, well pump for the geo and the frigerator. Only this i dont like about this generator is it only has an 83 amp main breaker for its distribution panel. Which is only good for 19920watts @ 240v. Each 50amp cord is only good for 12000. We can almost kill the gen out if the well and the geo turn on at the same time.

    • @GeneratorReviews
      @GeneratorReviews  2 года назад +3

      Wow!!! you pull some serious power my friend I like that you hooked up each leg with its own 50amp plug

    • @raybees72
      @raybees72 2 года назад +2

      My God, What's your Power bill run monthly?

    • @JM-fm7dy
      @JM-fm7dy 2 года назад +2

      @@raybees72 its like $240 a month on average for really bad insulated 1900 square ft, 1960 built house and everthing in are house is Electric.

  • @athenanimbuss6826
    @athenanimbuss6826 2 года назад +7

    We need something like this as a backup tothehouse. It is about the same price as a whole house generator but save you about $10 - $15k on the install 👍❤️🙏

    • @GeneratorReviews
      @GeneratorReviews  2 года назад +4

      Plus you need to get a permit and neighborhood association approval for those you’re talking about this one when you move you could take it with you or sell it
      Thanks for watching thanks for subscribing👍🏾😊💯

    • @athenanimbuss6826
      @athenanimbuss6826 2 года назад

      @@GeneratorReviews Good info!👍❤️🙏

    • @athenanimbuss6826
      @athenanimbuss6826 2 года назад

      @@johnjohnssouthernexposure5421 Nice 👍❤️🙏

    • @robertduncan2742
      @robertduncan2742 2 года назад +5

      When the powers out all the things needed won't be needed such as permits or neighbors approval or HMO fees everyone will be asking you to hook theres into your for power. That's why I'll never live in those areas. The gen looks great and a great review

    • @SouthPawEd
      @SouthPawEd Год назад +2

      That's why I bought this one over a true back-up generator. For $2,500, I had both of my panels wired up, so that's the only cost I'd leave at my house if/when we ever moved since the gen can come with us. Compared to sinking all that cost in a stand-by unit that would probably be left with the house during a move.

  • @brandonmurphy4657
    @brandonmurphy4657 10 месяцев назад

    I run everything in my home on a 7000/10.5 geni . Including two mini split units

  • @jonlee5642
    @jonlee5642 2 года назад

    Check out the microair softstart

  • @carlwheeler3403
    @carlwheeler3403 Год назад +3

    The max output in that configuration is going to be 12kw (50amp * 240volts = 12kw)

  • @billdee814
    @billdee814 Год назад

    This big generator maintains 60Hz.. perfectly during loads. My 12000 Druamax on propane fluctuates between 58 and 60 while running my 120volt microwave.

    • @theMister07
      @theMister07 Год назад

      Time to level up or switch to a brand like Champion that can handle the pressure

  • @peterfrancis3865
    @peterfrancis3865 11 месяцев назад

    Thanx nice✅

  • @anthonyb1426
    @anthonyb1426 Год назад +1

    Question for you, I am also considering getting this generator but with that 50 amp Inlet isn’t that only capable of moving roughly 12,000W? So do you have some sort of special set up that you’re utilizing the rest of that generator power?

    • @GeneratorReviews
      @GeneratorReviews  Год назад +2

      12500W on the 50amp inlet box, you can still use the plugs on the generator or wire each leg to its own 50amp plug or two inlet box

  • @richardmccoy8628
    @richardmccoy8628 Год назад +1

    That was awesome. What all do I need to run the house? I have a 50 amp plug. Already coming out of my box with a 200 amp.

    • @GeneratorReviews
      @GeneratorReviews  Год назад

      The very first thing you need to do is install a soft start on your compressor then you’re gonna need a 9000 W generator

  • @mdunbar04
    @mdunbar04 2 года назад +4

    Make sure u do a video of the soft start installation

  • @Kyle5371
    @Kyle5371 Год назад +1

    I just ordered one of these generators. I would like to have an auto transfer switch.
    My question is what parts do I need to have this fully installed. A full parts list would be very helpful.
    Any advice on parts or brands is helpful.
    Thank you for you time and knowledge.

    • @GeneratorReviews
      @GeneratorReviews  Год назад

      Hey Kyle
      Get your Inlet box kit plus lock out kit your 50 amp power cable I would say around 25 feet you’ll be all set.

    • @Kyle5371
      @Kyle5371 Год назад +1

      Would I get two so I can run the full 100 amps?

  • @mkvinsley3848
    @mkvinsley3848 Год назад

    This was a great video! Learned a lot. Could I install 2 inlet boxes and wire each to a single 200 amp breaker box with each going to a 50 amp generator breakers to utilize the full 20k capability?

    • @GeneratorReviews
      @GeneratorReviews  Год назад

      That’s a good idea. You probably have to talk to your electrician see if that’s possible.

    • @user-ui4iv8dz3w
      @user-ui4iv8dz3w 10 месяцев назад

      Or run a line to your neighbor so y’all can share the cost of a 3k generator.

  • @ericneidig2792
    @ericneidig2792 Год назад

    But isn't the AC on a 60 amp breaker? Just cause it'll run it doesn't mean it won't damage motor long term. Also 50 amp cord has max wattage of 12.5 kw. I have similar set up.

  • @mikemurray8423
    @mikemurray8423 2 года назад +1

    I want to see the 9000 w gen power the ac with the soft start, or do you need two in parallel, and what about that 23% vs 5% harmonic?

    • @GeneratorReviews
      @GeneratorReviews  2 года назад

      Definitely less than 5% is acceptable anything more I don’t run it. I think the 9000 will power with the soft start no problem. The thing you have to consider is you never know when the AC is going to kick on, so you might be running the microwave or washer and dryer and then the AC decides to kick on and over load the generator.
      Thanks for watching thanks for subscribing

    • @modemer
      @modemer 2 года назад

      If you are referring to my post about the 23% harmonics, I found my mistake when I looked it up. THD is 5%.

  • @user-wm5bu5ey2k
    @user-wm5bu5ey2k Год назад +1

    I'm new to this generator stuff but have questions.
    With the Westinghouse 20kw... 1 - 50amp plug is limited to 12000 watts (correct? )
    Could you connect both 50 amp from the generator to the gome panel to achieve the full potential of the generator? Would that be considered parallel like with the inverter type generators?

    • @GeneratorReviews
      @GeneratorReviews  Год назад +1

      It would not be paralleling, but that is something you can do

    • @user-wm5bu5ey2k
      @user-wm5bu5ey2k Год назад

      @@GeneratorReviews I appreciate the info. Thanks

  • @MrPatdeeee
    @MrPatdeeee Год назад +1

    I agree with you kind Sir @ time 2:43; where you said, "You don't have to do this". Which is break all the circuits \ in the panel. And it really has never been that; with the larger Generators these days.
    And even it does not need, or IF you are NO using/or turned off those users; in the large amp users. Which I feel is the best way to transfer in small Generators.
    So, for with this BIG Generator; NOTHING will happen in 99.9% of the times when you leave the circuits on. And think about this. How many times has lightning killed the power and then it comes back on. So there is NO difference. For most ALL big users; of amps; have electronic protectors; for fast on and off power.
    This is: in most ALL thermostats and/or the A/C's for many years; to protect A/C's, freezer's, Icebox's and etc! For what it's worth.

  • @Noneofyourdambusssiness
    @Noneofyourdambusssiness 5 месяцев назад

    Gavin, I have truly learned a lot by watching your videos. This was the first time I've seen anyone with solar PV shut off RSD before running this type of test. In other videos, you dont show yourself doing so. Is your PV system grid tied and without batteries?
    I have a 19.5 system with no batteries. Im considering doing exactly what you have done with interlock, inlet box, and generator for longer outtagr backup. I will use DPU for shorter. Is there any danger of genrator getting back fed if you dont shut off the RSD? Just trying to ID all possible issues. Thank you and keep up the great work.

  • @seymourscagnetti1413
    @seymourscagnetti1413 Год назад

    This is one serious machine. It sounds like a municipal power sub-station coming online. Quick question Gavin, do you know if anyone manufactures a "V-TWIN" powered inverter generator? Thanks.

    • @GeneratorReviews
      @GeneratorReviews  Год назад

      It does sound like that but it’s an awesome generator, that’s a great question I don’t know any V twin inverter generator🤔

  • @patrickcoleman5867
    @patrickcoleman5867 Год назад +1

    Omg this has a pure sine wave and a THD of 5 do the still make this I can’t find it anywhere I would sell my Generac 17,000 and get this

  • @Randy-vk7pj
    @Randy-vk7pj Год назад

    Gavin, would a Westinghouse 15kw dual fuel generator be powerful enough to run a house with a 3.5 ton and 2 ton split ac units? Not interested in a stand-by generator because I want the ability to move the generator to different location if the need arises. The 27 kw you tested is out of stock but the smaller duel fuel 15 kw is available. I like the ideal of powering my entire house if that need ever arises.
    Thanks, Randy

    • @GeneratorReviews
      @GeneratorReviews  Год назад

      I would recommend you make sure it puts out a pure sine wave before powering the central A/C

  • @drdexter33
    @drdexter33 Год назад

    Nice demo!. Just wondering if there's a duel-fuel (propane) version of this model.

    • @GeneratorReviews
      @GeneratorReviews  Год назад +1

      Thanks! I’m sure there will be a kit for it soon to convert to tri fuel

  • @StrongManMattt
    @StrongManMattt 2 года назад +2

    you do any videos with any of the Echo generators yet?

    • @GeneratorReviews
      @GeneratorReviews  2 года назад +2

      Not yet but I will get one soon thanks for recommending it

  • @HappyHands.
    @HappyHands. 2 года назад +1

    Sorry if you said and i missed it... But what was the total wattage and average amperage use when you had everything on?

    • @GeneratorReviews
      @GeneratorReviews  2 года назад +1

      Sorry but I didn’t focus this test on the watts used I will add the meter on the next one.

  • @Randy-vk7pj
    @Randy-vk7pj Год назад

    Do you have to worry about the generator damaging sensitive appliances because it is not a inverter style power source?

    • @GeneratorReviews
      @GeneratorReviews  Год назад +3

      This model actually has less than 5% THD it’s not like the other construction style which has over 25% THD
      So it actually puts out pretty clean power and it’s pure sine wave

  • @crazygravy437
    @crazygravy437 2 года назад +1

    Nice Video. I just purchased this generator and awaiting shipment. I’m looking for a power inlet box but all the highest related wattage I can find is around 12,500 watts. Is your inlet box rated for 28kw or will it be ok to use one rated 12.5kw with this generator?

  • @dadsworld5084
    @dadsworld5084 Год назад

    When you are at full load, are you using just the 50 amp cord, just wondering how so much can run off it, I currently run a small one then yours and thinking of upgrading currently at 13k but runs the whole house minus AC at once, I can run AC but need to turn off some things dues to surge

    • @GeneratorReviews
      @GeneratorReviews  Год назад

      That was only a quarter of its output. This generator is so powerful

    • @dadsworld5084
      @dadsworld5084 Год назад

      @@GeneratorReviews so you can run all that off one 50 amp cord wow

  • @Ben275353
    @Ben275353 Год назад +1

    Can you parallel the 2 50 amps to 1 100 amp for a home?

  • @blakeloke6997
    @blakeloke6997 12 дней назад

    Thank you for the video Gavin. I just ordered the same machine through Amazon (it hasn't arrived yet). When reading the details more thoroughly, I found that the frequency output is 50Hz instead of 60Hz. Your meter shows 60Hz on the unit connected to the house. Did you have to adjust the run speed and frequency settings to get 60Hz?

    • @GeneratorReviews
      @GeneratorReviews  11 дней назад +1

      It’s 60 Hz don’t worry that was a typo on Amazon

    • @blakeloke6997
      @blakeloke6997 11 дней назад

      Thank you. I was worried as Amazon wouldn’t cancel. Then more research and found the Operating Manual online. It says 60Hz

  • @TheSnakeman3
    @TheSnakeman3 2 года назад

    Looking forward to the Easy Start on the AC and a test with a smaller Gen.
    When running a house, does it have to be an inverter Gen? I got a 8750 watt that’s not an inverter Gen.

    • @GeneratorReviews
      @GeneratorReviews  2 года назад +2

      Hey Robert
      I would be very hesitant to run a non-pure sine wave inverter on my house with all of your electronics and computer systems

    • @TheSnakeman3
      @TheSnakeman3 2 года назад

      @@GeneratorReviews is there any way to turn it into a sine wave output?

    • @GeneratorReviews
      @GeneratorReviews  2 года назад +1

      @@TheSnakeman3 it’s a sine wave power already

    • @GeneratorReviews
      @GeneratorReviews  2 года назад

      @Justin Time you are absolutely right but 90% of modified sine wave power is dirty and will eventually cause more problems than its worth

  • @donelias1981
    @donelias1981 Год назад

    How is the power coming from this generator compared to an inverter such as the 9000 watt inverters out there? I want to protect my electronics with clean power but would also like to run my AC.

    • @GeneratorReviews
      @GeneratorReviews  Год назад +1

      This is a pure sine wave generator but it’s not as quiet as the inverter 9000w because of eco mode

    • @donelias1981
      @donelias1981 Год назад

      @@GeneratorReviews so the low idle switch is not the same as ECO mode? Or does the sound just because the open air vs enclosed generator? Would you recommend the GENMAX over this for a residential backup generator? A 9000 GENMAX matches the Westinghouse WH7500E in power output that I have now just want cleaner safer power to my TVs and such.

  • @carlcapello9956
    @carlcapello9956 2 года назад +1

    This is the first 20000 watt generator I have seen and it's by Westinghouse that is awesome power for your entire house. If you don't mind me asking, what is the financial damage to your wallet? Did you have this running on gasoline or propane?

    • @GeneratorReviews
      @GeneratorReviews  2 года назад

      When I bought this one I paid around 3k now it’s doubled in price it’s a gas only Gen

    • @carlcapello9956
      @carlcapello9956 2 года назад

      @@GeneratorReviews That is a good price and I just found out they have a sale on models they want to get out the door sometimes.

  • @cobbetlprogrammer1344
    @cobbetlprogrammer1344 Месяц назад

    Wow! Totally Awesome: Does this run on propane too? How much does one of these Bad Boys go for? Thanks Much!

  • @davidwho8215
    @davidwho8215 Год назад +1

    You probably need two generator inputs to your house, as pushing 20Kw through a single NEMA 14-50 is over it’s rated limit. I noticed the generator had two NEMA 14-50 plugs, probably for that reason.

    • @GeneratorReviews
      @GeneratorReviews  Год назад

      Yes you’re right.

    • @joeriddell1
      @joeriddell1 Год назад +1

      @@GeneratorReviews Awesome video! Thanks for posting! can you explain how (and if) you can run two cords out of the 50 amp outlets into 1 200 amp house panel? Thanks!

  • @mr.boniato6402
    @mr.boniato6402 11 месяцев назад +1

    Have you thought of using a soft start or smart start? I hesitate to buy due to bad Amazon reviews.

    • @GeneratorReviews
      @GeneratorReviews  11 месяцев назад

      I do have a soft start installed.
      ruclips.net/video/KjGc7fz3D8c/видео.htmlsi=rxU82xXPkD4KT7WE

  • @shanedeal2356
    @shanedeal2356 Год назад

    Turn on stove and oven also

  • @davidyummus6259
    @davidyummus6259 2 года назад +6

    Aussie Dave in PA here Gavin,... What Soft Start unit would you recommend ?

    • @GeneratorReviews
      @GeneratorReviews  2 года назад +4

      I’ll be installing the micro air easy start

    • @alejandrocarrillo373
      @alejandrocarrillo373 2 года назад +1

      @@GeneratorReviews with the soft start installed, will you be be doing the test with one 9000? Genmax or Predator?

    • @GeneratorReviews
      @GeneratorReviews  2 года назад +3

      @@alejandrocarrillo373 yessir I will definitely be doing that👍🏾

    • @davidyummus6259
      @davidyummus6259 2 года назад +2

      @@GeneratorReviews
      Thanks 😏

  • @alnett22
    @alnett22 7 месяцев назад

    What's the specifications for the fuel needed for the generator? Will I do fine on 87 octane 10 percent ethanol

    • @GeneratorReviews
      @GeneratorReviews  7 месяцев назад +1

      Yes, you can run 87 octane 10% ethanol with some fuel treatment added especially if you’re going to store it that way but I recommend you to drain the complete tank and carburetor before storing.

  • @wow1022
    @wow1022 2 года назад +2

    damn, you'd need 2 50A inlets to fully utilize the power out of this generator

  • @enriquesosa3270
    @enriquesosa3270 Год назад

    What amp breaker did you use in your panel for the generator?

  • @tonyaguilar0626
    @tonyaguilar0626 Год назад

    Buying this!! What size 50 amp cord do I get? On Amazon all the 50 amp generator cords say max 12500 watts but this is a lot more. Thanks

    • @GeneratorReviews
      @GeneratorReviews  Год назад

      It has two 50 amp plug

    • @SouthPawEd
      @SouthPawEd 18 дней назад

      I bought 2, 6 gauge cords from Generac. I wouldn't go cheap on the cables

  • @AndTodaysProjectIs
    @AndTodaysProjectIs Месяц назад

    Any idea how many gallons per hour that thing is drinking at anywhere around half load? I may be in a situation where I will not be able to install a whole home permanent generator I found a solution So I might need to rig something like this up to power a rather large home with two air conditioners. One problem we have during hurricanes is typically gas supply. Wondering how many gallons per hour of the same drinks

    • @GeneratorReviews
      @GeneratorReviews  Месяц назад

      This generator uses an estimated 1.56 GPH (gallon per hour) at a 50% load

  • @alejandrocarrillo373
    @alejandrocarrillo373 Год назад +1

    What was the total watts, when everything was on in the house?

    • @GeneratorReviews
      @GeneratorReviews  Год назад +1

      I only pulled 7000 W not even close to what this generator can handle I could’ve hooked up another house

  • @rcprod9631
    @rcprod9631 Год назад

    You mention a "soft start" at the beginning of the video. (I may have spelled it wrong) Would you mind explaining what that would be for? Thanks.

    • @GeneratorReviews
      @GeneratorReviews  Год назад +1

      The soft start helps to run the central A/C using a generator by lowering the power needed to start the compressor
      ruclips.net/video/KjGc7fz3D8c/видео.html

    • @rcprod9631
      @rcprod9631 Год назад

      @@GeneratorReviews Thanks for the helpful link. Just subscribed.

    • @GeneratorReviews
      @GeneratorReviews  Год назад +1

      @@rcprod9631 Thanks for the Subscribe and you’re welcome glad to help 👍🏾😊

  • @lowriderssux
    @lowriderssux 11 месяцев назад

    Hey Gavin, how did the sine wave output look on this generator?

    • @GeneratorReviews
      @GeneratorReviews  11 месяцев назад

      The sine wave looked OK as long as the generator was not in the low idle mode

  • @Tobinator76
    @Tobinator76 7 месяцев назад

    Have you changed the oil yet? What oil filter did you buy?
    I can't find the oem filter anywhere

    • @GeneratorReviews
      @GeneratorReviews  7 месяцев назад

      You don’t have to use the oem filter just take it to your auto parts store and find a replacement it’s just an oil filter.

    • @SouthPawEd
      @SouthPawEd 18 дней назад

      ​@GeneratorReviews Came here to ask the same question. Westinghouse's part number 329908 doesn't help anything. The oem filter has no numbers on it. Just spent 30min at the store with the tech looking around. There's a forum that had a comment where the Fram PH4967 and the WIX 51394XP both fit. The Fram is stubby compared to the oem. Going to look for the WIX next.

  • @markbennett7826
    @markbennett7826 2 месяца назад

    What is 20000 gen fuel usage vs 12500 Westinghouse gen; or know; need extra output?

  • @lordnetsplits3192
    @lordnetsplits3192 Год назад +1

    Could you do a THD test on this generator.

  • @lesruth2756
    @lesruth2756 2 года назад

    Question. How come the 50 amp breaker didn’t trip with the 59 amp start up power draw?

    • @wow1022
      @wow1022 2 года назад

      household breakers operate on a time overcurrent curve which is an inverse curve, as current increases above the pickup the trip time decreases

    • @lesruth2756
      @lesruth2756 2 года назад

      @@wow1022 Reason I asked is because I plan to purchase a 15,000/12,500 Generator to run everything possible in my 3,000 sqft home. I also have a 5 ton AC unit but I’ve been told it won’t work because both the AC & handler are both 50 amp breakers and the 50amp generator will not power both??

    • @GeneratorReviews
      @GeneratorReviews  2 года назад

      It didn’t trip because a 59 amp at 240v is only 29.5 amp on each leg.

    • @wow1022
      @wow1022 2 года назад

      @@lesruth2756 a 12000/15000 probably won't get the AC started on the 5 ton unit without a soft starter, remember that the breaker protects the circuit and not the load, just because it is 50A circuit doesn't mean it's a 50A load, you need get a clamp meter to see how much current draw your AC and water heater pull, usually they size the AC circuit significantly above the actual load because of start up current and circuit length, my 3 ton unit pulls 12A on a 30A circuit

    • @lesruth2756
      @lesruth2756 2 года назад

      @@wow1022 So what about the air handler blower do you think the two can be powered together on this particular generator?

  • @tommyb2616
    @tommyb2616 Год назад

    What meters are those that you put on each leg in the diy box?

    • @GeneratorReviews
      @GeneratorReviews  Год назад

      This is the video I showed how I made it and if you look into the description you’ll find all the links to everything you need on Amazon

    • @tommyb2616
      @tommyb2616 Год назад

      @@GeneratorReviews you forgot to post the link😎

  • @Redtale1106
    @Redtale1106 Год назад

    How big is the tank and how long can it run on gasoline?

    • @GeneratorReviews
      @GeneratorReviews  Год назад

      This generator has 17 gallons tank with a fuel capacity of 17.17 gallons, the WGen20000 may run for around 11hours at 50% load with a full tank (fuel consumption around 1.56 GPH).

  • @Randy-vk7pj
    @Randy-vk7pj Год назад

    Why do these large generators don't offer tri- fuel options?

  • @Durango214
    @Durango214 2 месяца назад +1

    I just hook up the inlet box. But once I turn the breaker on. No power is transferred. Yes the main is off

    • @GeneratorReviews
      @GeneratorReviews  2 месяца назад

      Make sure all your circuit breakers on this generator are on.

    • @Durango214
      @Durango214 2 месяца назад

      @GeneratorReviews when I flip the circuit on .the volt reader on generator goes blank . And when I flip off it comes back on

  • @evisin77
    @evisin77 Год назад

    I like this machine but at the price why not just get a ganarac stand by?

    • @GeneratorReviews
      @GeneratorReviews  Год назад +1

      After installation and permits, I’m pretty sure you would triple the cost of this one

  • @scottmanino7239
    @scottmanino7239 2 года назад +1

    if you use one receptacle does that mean you can only get 12,000 watts?

    • @GeneratorReviews
      @GeneratorReviews  2 года назад +2

      Yes but it can be wired for two

    • @joeriddell1
      @joeriddell1 Год назад +1

      @@GeneratorReviews Awesome video! Thanks for posting! can you explain how (and if) you can run two cords out of the 50 amp outlets into 1 200 amp house panel? Thanks!

    • @joeriddell1
      @joeriddell1 Год назад

      @@GeneratorReviews Awesome video! Thanks for posting! can you explain how (and if) you can run two cords out of the 50 amp outlets into 1 200 amp house panel? Thanks!

    • @Ben275353
      @Ben275353 Год назад

      @@joeriddell1 I would like to know that answer also.

  • @miiitchhh225
    @miiitchhh225 15 дней назад

    Look at all those tandem breakers, my lord is that up to code

  • @alexgenereux4704
    @alexgenereux4704 2 года назад

    What 50 amp power cord is this?

  • @ryanyoshimura4652
    @ryanyoshimura4652 Год назад

    Is your ac compressor a single stage?

  • @mrtjcoleman
    @mrtjcoleman 8 месяцев назад

    Is your 5ton a heat pump or straight cool

  • @DjCorona080910
    @DjCorona080910 16 дней назад

    Do you know how much natural gas it uses per day?

  • @pstoneking3418
    @pstoneking3418 3 месяца назад

    If a 20,000 watt generator doesn't handle all loads turned on, you have a huge problem with the generator. Just start your generator and turn on the generator breaker after you've let the generator warm up.

  • @donaldjeansonne8667
    @donaldjeansonne8667 Год назад

    Do you think a West 12000/15000w generator run a 5 ton A/C unit?

    • @GeneratorReviews
      @GeneratorReviews  Год назад

      Yes it might start it but with a higher THD things will run hotter My computers refrigerators and even the compressor

    • @donaldjeansonne8667
      @donaldjeansonne8667 Год назад

      @@GeneratorReviews Thanks I just concerned about the extra cost for the 20000w unit.

    • @busterhyman6633
      @busterhyman6633 Год назад

      @@donaldjeansonne8667 The 12000/15000 is also 5% THD add that soft start kit and you will be good to go.

  • @fredyenrike198
    @fredyenrike198 16 дней назад

    What's running watts means?

    • @GeneratorReviews
      @GeneratorReviews  8 дней назад

      Running watts means what the generator can handle

  • @michaelfillinger1488
    @michaelfillinger1488 Год назад

    How many gorillas does it take to move it it's got to be heavy

  • @jimmie7520
    @jimmie7520 Год назад

    Just looked At this generator…
    You have two 50 amp outlets
    At 240 volts u only produce 83.33 amps continuous.
    Different AC and heat pump systems require different amperage…having two 50 amp outlets does not give you a 100 amps continuous..
    With one transfer switch and one house breaker panel ..the most continuous amps u can feed that panel is 50 amps. So extra 50 amp plug really not much good unless u run a heavy extension cord into house to plug some 220 volt appliance in to that requires less than 33.3 amps…
    The Westinghouse 15,0000/12,000 DFc Is a way more cost effective Generator..initial cost ,option run propane , and operating cost in gas run time.
    Now if they wound make this wgen20000 with one plug that you could get 83.3 amps out off be a lot more useful and practical .

    • @GeneratorReviews
      @GeneratorReviews  Год назад

      This generator is perfect for what it was intended for, which is construction site, you have electric concrete cutting cement, mixers, chopsaw everything connected to the generator at the same time.

    • @jimmie7520
      @jimmie7520 Год назад +1

      @@GeneratorReviews …now that might be true …but caption says whole house generator kinda implies that it would easily take place of a home standby generator…giving you the full amperage of a 20kw unit home unit.

  • @braut34
    @braut34 Год назад

    You didnt turn any appliances with the AC. A 9500 watts can do that.

    • @GeneratorReviews
      @GeneratorReviews  Год назад

      With 28,000 W starting I didn’t think I would have to. I could’ve ran my whole house and my RV at the same time.😅

  • @spencerw.5195
    @spencerw.5195 Год назад +1

    That generator is super overkill for your house if you can power everything off of a single 50A plug. If you have strip heaters in your air handler as a supplement during cold weather and they kick on, it'll trip that breaker and you'll be powering nothing. You can literally do everything you did here with a 9kw continuous, 12kw peak generator.

  • @jvazquez53
    @jvazquez53 Год назад +1

    If I run my whole house with 7000 watts you can run yours and you neighbors!🤣🤣🤣. Only a difference, mine run at low RPMS, therefore fuel efficiency is better...

  • @Casca-su3ty
    @Casca-su3ty 11 месяцев назад +1

    I couldn't have stuff like this am the most worthless guy with mechanical things Too confusing for me.

  • @wolverinewarlord
    @wolverinewarlord Год назад

    No longer anywhere

  • @snozcocram
    @snozcocram Год назад

    No longer on Amazon

    • @rockystelone21
      @rockystelone21 Год назад

      Electric Direct Generator has them on sale for $3100

  • @zcar2043
    @zcar2043 11 месяцев назад

    I don't recommend thus generator. I bought and after the first time I had to use it, the generator shuts dn randomly. It took more than a month a lot of emails ,phone calls to get a new generator. The customer service is very poor. I don't recommend to buy this generator. Buy something else.

    • @GeneratorReviews
      @GeneratorReviews  11 месяцев назад +1

      Sounds like you got a bad one. Someone like me who sells hundreds of every generator brand I see a lemon every once in a while.
      Sorry you had to go through that. I hope they took care of you.

  • @congsan3528
    @congsan3528 3 дня назад

    Is safe to run sensitive electronic like tv, computer, washer & dryer?

    • @GeneratorReviews
      @GeneratorReviews  2 дня назад

      Inverters generators are a lot better for sensitive electronics