What Input Devices are used in BMS? | Building Management System Training

Поделиться
HTML-код
  • Опубликовано: 25 дек 2024

Комментарии • 87

  • @TechSystems
    @TechSystems  Год назад +1

    *Transform Your BMS Skills!* 🌟 Enjoying my videos? Dive deeper with my BMS Fundamentals course on Udemy. For a limited time, it's available for only $12.99! Don't miss out - click the link below to enroll now.
    www.udemy.com/course/bms_fundamentals/?couponCode=DFAB481D2B13D4E247A9

  • @toqeerahmad7378
    @toqeerahmad7378 4 года назад +5

    Feeling lucky...
    To find your channel
    As was preparing for an interview DDC/BMS technician

    • @TechSystems
      @TechSystems  4 года назад +1

      Best of luck for your interview❤️

    • @ajmedia559
      @ajmedia559 3 года назад +2

      I’m 19 just got a job for bms company loving it think I’m one of the youngest in the industry 😂

    • @TechSystems
      @TechSystems  3 года назад

      Best of luck for your career in BMS.

    • @playbeat9503
      @playbeat9503 3 года назад

      @@ajmedia559 which institute you studied

    • @jollyscaria1922
      @jollyscaria1922 2 года назад

      Not high prshher gonot good no sight no rigjt lfted explain but high minde filpass some is playing for h ,,,,,,,,r m telling mind not bai un lucky bad mind this good way no playin home ok but no grouped making how can go pin and pin must bee treing any eng ,,is bad some i van pin bad ming bai some inter ved right lfeted bad mood bai right no tell builging mange ment systome is vrey good but for play bad repayed bad good cal y feid ok good reson not helping not any playon tope somesomanny compaining making bad havited long wor mind cut offed some over loder chillar systomes chillar pump not watt is effed bai ex pames not any one pleas school not stey jumping some one plaes stoped some gues best but play boy stoping prefeated comeing not vreshion somanney thing jobes vrey veassey no bai sight woris vrey im pronted bai thina some markimg good shering vrey importants gues goo some point good workes not not harres not my supres in formes sir sorrey breathers not any workies not harries plaesok ddc bms vrey good ahu dvddc 24v builg manged ment systom ddc conroled any probels comeing conrolled systomes pannel bord testing power and filer alreom reson defantiley checking sy stome cles and one by checking need sefty dives systomesv vfd ster Delta conneshion bms ddc mico pannel bored ex, direat dmand controled

  • @sathyasview4892
    @sathyasview4892 3 года назад +3

    You're the best clear explanation I appreciate you and iam looking for more videos about HVAC including job opportunities all over the world

    • @TechSystems
      @TechSystems  3 года назад +1

      Thank you for your valuable feedback. 👍

  • @SarangRani24
    @SarangRani24 4 года назад +3

    Thank You sir for sharing your knowledge..
    May God bless you

    • @TechSystems
      @TechSystems  4 года назад

      Glad to hear you are learning from this channel.

  • @salimyousuf8848
    @salimyousuf8848 4 года назад +2

    Thanks for sharingyour knowledge
    How to calculate dps pressures setpoint in ahu for filter
    Where to fix dps for vfd control

    • @TechSystems
      @TechSystems  4 года назад +1

      To set filter DPS setpoint, AHU catalogue shall be consulted where differential pressure value for dirty status of filter is mentioned. For VFD control a static pressure sensor shall be installed on 2/3 length of the supply duct. Hope I answered your question.

    • @salimyousuf8848
      @salimyousuf8848 4 года назад

      @@TechSystems thanks what about dpt to control pump vfd

    • @TechSystems
      @TechSystems  4 года назад +1

      A DPT is installed between main supply pipe and main return pipe of chilled water system. Water balancing team shall provide the Differential Pressure (DP) setpoint at this location. Pump VFD speed is then controlled to achieve this setpoint. Location of DPT installation can be inside pump room or on the farthest pipe line inside the system.

  • @mohammedattoun9696
    @mohammedattoun9696 4 года назад +1

    Perfect explanation
    Thank you

  • @EnochIS_REAL
    @EnochIS_REAL 4 года назад +1

    You have just gained a sub!! 🤙🏾🤙🏾

  • @aknotes3897
    @aknotes3897 3 года назад +1

    Very helpful Channel thank you so much

    • @TechSystems
      @TechSystems  3 года назад

      Glad to hear that. Thank you for your valuable feedback 🙂

  • @toqeerahmad7378
    @toqeerahmad7378 Год назад +1

    Great Job...

  • @vikasmore164
    @vikasmore164 3 года назад +1

    Thanks lot also upload the video for sequence of operation of OAHU and and Mix aira AHU

  • @sayyadafrid5101
    @sayyadafrid5101 4 года назад +4

    Excellent job brother. Expecting more vedios on building management system and HVAC

    • @TechSystems
      @TechSystems  4 года назад

      Sure 👍

    • @TechSystems
      @TechSystems  8 месяцев назад

      You can use this link to purchase the course.
      www.udemy.com/course/bms_fundamentals/?couponCode=F905CD0D3155B2B165FD

    • @tauhidalam3425
      @tauhidalam3425 8 месяцев назад

      @@TechSystems please share your WhatsApp no

    • @TechSystems
      @TechSystems  8 месяцев назад +1

      Share your whatsapp no. I will contact you.

  • @beinganexpat
    @beinganexpat 2 года назад +1

    Fantastic

  • @BBMshort52
    @BBMshort52 Год назад +1

    Nice work 💐👍 BMS good evening sir
    I'm abubker siddiqui I'm working in kuwait BMS systems controller oil and gas fields work and hospital 🏥 work 10year

  • @gatewayasabirschannel409
    @gatewayasabirschannel409 2 года назад +1

    Thank you sir

  • @muhammadhussain8608
    @muhammadhussain8608 4 года назад +1

    Superb

  • @ashokchakravarthi6023
    @ashokchakravarthi6023 3 года назад +1

    Its very usefull bro

  • @kamamn4264
    @kamamn4264 3 года назад

    Great Explanation.....

  • @kamamn4264
    @kamamn4264 4 года назад +1

    👍👍👍

  • @geehvacsensor7344
    @geehvacsensor7344 3 года назад +1

    Nice video

  • @shyamdamodaran4160
    @shyamdamodaran4160 3 года назад

    Great Video!

  • @michaelfendi3402
    @michaelfendi3402 3 года назад +1

    So in case if anyone of these sensor malfunction or found to be faulty? Will it affect the over energy consumption of that building? How will affect the overall operation and energy consumption?

    • @TechSystems
      @TechSystems  3 года назад +1

      It depends on which sensor we are talking about for example if supply air temp sensor of FAHU is faulty and giving wrong reading, it will disturb the control logic and will result in poor temperature control which can have effect on energy consumption... Similar will be the case of static duct pressure sensor controlling the speed of AHU fans and so on

    • @michaelfendi3402
      @michaelfendi3402 3 года назад +1

      @@TechSystems @11:04 the fan which you mentioned "to control the speed of fan in VAV system" are you talking about the supply fan and exhaust fan in VAV system?

    • @TechSystems
      @TechSystems  3 года назад +2

      Yes

    • @michaelfendi3402
      @michaelfendi3402 3 года назад

      @@TechSystems can you kindly give me some advice, Why do you think there is a need to install water leak detector sensor or water detector sensor inside of the AHU and PAU?

  • @Obsidian-ri2yz
    @Obsidian-ri2yz 2 года назад +1

    I have a question, is differential pressure the same as total pressure or are they different?

    • @ToothyGus
      @ToothyGus Год назад

      Differential pressure value or deltaP is measured by subtracting one value of static pressure sensor from another static pressure sensor. Example, in pumps a dP sensor may be installed between a suction strainer, when the dP is very high that means the strainer is dirty and needs cleaned. In AHU a dP sensor can detect when the air filter is dirty and need cleaned.

  • @sambedel8999
    @sambedel8999 4 года назад +1

    Pls help me,
    i have an issue with my VFD, it cant start on Auto Mode always show ( Relay Output 2 ) making noise and cant start on Auto Mode.
    Thanks

    • @TechSystems
      @TechSystems  4 года назад +1

      I couldn't get your problem completey. Did you check the digital command signal from the BMS? Try making jumper on the VFD command terminals. Is it fine in Manual mode without this issue?

    • @sambedel8999
      @sambedel8999 4 года назад +1

      @@TechSystems Yes in manual Mode it work fine only when I press Auto mode it will stop working.

    • @TechSystems
      @TechSystems  4 года назад +1

      Did you check the command signal from BMS? Is it OK? Trying making a cable jumper on the command terminals of VFD.

    • @sambedel8999
      @sambedel8999 4 года назад +1

      @@TechSystems were can I get the instructions on vfd to making the jumper,
      My VFD type is ACH580
      Thanks

    • @TechSystems
      @TechSystems  4 года назад +1

      You will find the manual from internet. To give start command give jumper from terminal 10 to terminal 13. Also make sure that terminal 10 to 16 is already jumped as it is safety interlock and it must be closed to allow VFD to run. As your VFD is running in Manual so I think this will be fine.. Try jump from 10 to 13 while VFD is in Auto.

  • @shswkatkhan99khan13
    @shswkatkhan99khan13 3 года назад +1

    Your excellent

  • @shabeebrahman3985
    @shabeebrahman3985 3 года назад

    Hello sir
    Which is the best certificate in BMS

  • @imrankhan-ns3bi
    @imrankhan-ns3bi 3 года назад +2

    What is the difference between flow meter and flow switch?

    • @TechSystems
      @TechSystems  3 года назад

      A flow switch only gives indication of flow by closing the contact when flow is present while flow meter gives actual value of the flow at a moment.

  • @AbdulRahman-rh8zn
    @AbdulRahman-rh8zn 3 года назад +1

    Subscribed to your channel

  • @chethuharireddy3156
    @chethuharireddy3156 3 года назад +1

    Sir thermistor can able to connect BMS?
    If yes how?

    • @TechSystems
      @TechSystems  3 года назад

      Thermistor is connected to an analog input point and type of thermistor is selected in the DDC controller during programming.

    • @chethuharireddy3156
      @chethuharireddy3156 3 года назад

      @@TechSystems sir pls explain ddc controller programing.
      iam waiting for these type videos.

  • @suhailalvi3545
    @suhailalvi3545 2 года назад

    Dear Sir if you have PDF files for all the videos?
    You may charge for this.

  • @vishalkarekar7954
    @vishalkarekar7954 3 года назад

    what is the scope of bms?

  • @syedasim3680
    @syedasim3680 Год назад

    Sir Plizz make practical video

  • @mohammedabdullahkhan4264
    @mohammedabdullahkhan4264 4 года назад +1

    Run status, trip status pump ka kaise lete hai tohda details mai banaye

    • @TechSystems
      @TechSystems  4 года назад +1

      Run and Trip status signals are taken from the MCC panel. Run status signal is provided by auxiliary contacts of contactor, when contactor is latched we get the run status. While trip status is provided by the overload relay. Hope you get the answer.

  • @sathyasview4892
    @sathyasview4892 3 года назад +1

    I have one request that where r u working currently ?? If you're working in western countries like Canada or USA please make a video about the job opportunities there and HVAC trade courses how to get the job etc.... please do my dear brother

    • @TechSystems
      @TechSystems  3 года назад +1

      Hello Sathya,
      I am working in KSA.

  • @saidabdelmalek8766
    @saidabdelmalek8766 3 года назад

    I Have a problem, I can't understand how the Emergency of switch for industrial steam system works with BMS :
    the customer asked to Emergency of switch To be situated adjacent the boiler room with warning horn, and is to be integrated in the boiler control system and BMS. including all necessary cabling.
    if you can help me, I don't understand how the emergency switch for industrial steam system works:
    1- if you press the emergency switch, it will stop the boiler and it is the boiler that communicates with the BMS.
    2- if the emergency switch is pressed, it will communicate with the BMS and it is the BMS which stops the boiler.
    3- if you press the emergency switch, it stops the boiler and the emergency switch sends its status to the BMS.
    pls send me a reference of the emergency switch to buy it

  • @g...sarwar4231
    @g...sarwar4231 2 года назад

    Sir plz hindi

  • @mtq.KA32
    @mtq.KA32 2 года назад

    sir Hindi Mai bolo English 0/0