Should I used 0-10VDC and 4-20mA Analog Signals?

Поделиться
HTML-код
  • Опубликовано: 31 июл 2024
  • 0-10VDC and 4-20mA are the the two most popular signals in industrial automation. Why use milliamps instead of voltage? Voltage drop...
    You can find our FREE lesson series including creating a new program, downloading, and going online at twcontrols.com/allen-bradley-...
    Don't forget to like and comment on our videos and subscribe to our channel.
    ruclips.net/user/TimWilbo...
    Support these videos while you advance your skills courses.twcontrols.com/
    Items used in this video:
    PLC Trainer twcontrols.com/plc-trainers
    Analog Simulator plctools.com/analog-simulator...
  • НаукаНаука

Комментарии • 75

  • @lordfizzz
    @lordfizzz Год назад +2

    My mentor has us using your 4-20ma simulator all the time. It reeeeeally helps me get a grasp of things as we use it on heating controls! You're a legend!

  • @75blackviking
    @75blackviking Год назад +2

    Your channel is great. Really solid content.

  • @DimensionMachine
    @DimensionMachine 2 года назад +2

    Very concise and clear explanation. Thanks!

  • @nigelnovak3096
    @nigelnovak3096 3 года назад +3

    Awesome explanation as always Tim :-)

  • @jackpast
    @jackpast 5 лет назад +3

    Nice comparison of both choices and why to use one over the other!

    • @TimWilborne
      @TimWilborne  5 лет назад +1

      Thanks! Let me know if you think of anything special that needs covered in this analog series.

  • @seyedmahdimirhashemi2993
    @seyedmahdimirhashemi2993 4 года назад +1

    Great point, well done.

  • @orhirshfeld
    @orhirshfeld 4 года назад +1

    The video was very helpful, thanks

    • @TimWilborne
      @TimWilborne  4 года назад

      Glad you found it helpful. Let me know if you have any questions about analog come up.

  • @electricaltyler5998
    @electricaltyler5998 Год назад +1

    Thank you once again Tim

  • @raphaelmahumane1648
    @raphaelmahumane1648 Год назад +1

    great video. THANK YOU

  • @craigfishcake2543
    @craigfishcake2543 3 года назад +1

    Excellent - thanks.

  • @saroashliaqat1393
    @saroashliaqat1393 4 года назад +1

    thank you Tim

  • @warptmanbmx
    @warptmanbmx 3 года назад +1

    learned something new today thanks again

  • @spk7054
    @spk7054 6 месяцев назад +1

    thank you

  • @JohnnyJr396
    @JohnnyJr396 2 года назад +1

    Tim maybe you can help me here.
    I’m trying to drive an actuator (0(2)-10vdc or 4-20 ma) with an Arduino.
    Since the Arduino pin can only put out 5 volts I’m using the 4-20 ma input on the actuator.
    I’m using a 250 ohm resistor and can produce a 4-20 ma signal but my stroke on the actuator isn’t no where near fully open.
    Is this because (my guess anyway) that even though the input is a 4-20 ma it has to be based off of at least a 10v source for this actuator?
    Or is 4-20ma in controls 4-20 no matter what?

  • @roberthernandez1985
    @roberthernandez1985 3 года назад +1

    Can you link me that voltage drop calculator Tim that was a nice one always good videos from you

  • @locolopez75
    @locolopez75 4 года назад

    My nigga every.time I have a question you have a video I don't regret buying your plc training at 800 thank you Sensei

  • @inothome
    @inothome Год назад +2

    Great video explaining it. The best part is how does the PLC or meter read that 4-20 signal? By measuring the voltage drop across a precision resistor on the input! I used to know the resistor values off the top of my head for 0-1V, and 0-10V but it's been a long time.

    • @inothome
      @inothome Год назад +1

      Crap, this is a three year old video! But just came up in my feed.

    • @TimWilborne
      @TimWilborne  Год назад +2

      Oldie but goodie, here is one on the resistor values 😁
      ruclips.net/video/DAMW5sKoH6E/видео.html

    • @inothome
      @inothome Год назад +1

      @@TimWilborne Ah yes! 250 Ohm. How could I forget that?

  • @Futbolnews12
    @Futbolnews12 3 года назад +1

    Right on the money!

  • @Full_Circle_Automation
    @Full_Circle_Automation 5 лет назад +3

    Tim where do I buy one of those analog simulators? It looks like a nice tool to have for troubleshooting.

    • @TimWilborne
      @TimWilborne  5 лет назад

      It sure is Jeff. Here is the link to buy one. www.theautomationstore.com/analog-simulator-and-generator-with-lcd-0-10vdc-and-4-20ma/

  • @mnada72
    @mnada72 3 года назад +2

    What is the difference between the range 0-5 v and 0-10 v ? some times we have both on input module types , when to use this or that ?

    • @TimWilborne
      @TimWilborne  3 года назад +1

      Typically you will use 0-10V in industrial applications.

  • @MM-vi9kh
    @MM-vi9kh 4 года назад +1

    Great ❤️❤️

  • @user-yq1pf3gi4y
    @user-yq1pf3gi4y 10 месяцев назад +1

    I have a question. I am trying to install a digital display meter that will be commanded by a 0-10VDC analog signal. Simply extending from control cabinet to outside of control room so truck drivers can watch a readout. Any suggestions on where I can get a LARGE weatherproof analog 0-10VDC readout?

    • @TimWilborne
      @TimWilborne  10 месяцев назад +2

      I have seen them before but never installed one so I'm not sure which brands are good and bad.

    • @user-yq1pf3gi4y
      @user-yq1pf3gi4y 10 месяцев назад +1

      @@TimWilborne thank you

  • @Miguel-wx8ii
    @Miguel-wx8ii 4 года назад +1

    Thanks a lot!!! what could we do with an control loop of the engine governor? what`s the difference in this case?

    • @TimWilborne
      @TimWilborne  4 года назад

      Hi Miguel. You probably could get more precise engine speed control but it would depend on what type of precision you need for your application as to whether it would be helpful.

    • @Miguel-wx8ii
      @Miguel-wx8ii 4 года назад +1

      @@TimWilborne It`s a caterpillar speed governor, it controls the speed and the generator power at the axis output, then i`ve a problem because it`s very unstable at 60hz, and i don`t know if i may to change the type of signal or calibrate the pid controller.

    • @TimWilborne
      @TimWilborne  4 года назад

      @@Miguel-wx8ii I might talk to Caterpillar before making any adjustments. Most Caterpillar generators are good a regulating their frequency. I would lean towards it needing a tuneup first.

  • @jeesonpeter2049
    @jeesonpeter2049 3 года назад +1

    I have a 0-10v output signal from a loadcell amplier to PLC. Can I wire a parallel connection from this to a digital panel meter in order to display it near the loadcell amplifier?

    • @TimWilborne
      @TimWilborne  3 года назад +2

      Typically yes. As long as the electrical load isn't more than the load cell can handle. It will have a minimum load resistance. Compare it to the panel meter and PLC consumption.

    • @jeesonpeter2049
      @jeesonpeter2049 3 года назад +1

      @@TimWilborne thankyou so much for the reply. The minimum load resistance is 200 ohm on loadcell amplifier, and input impedance on panel meter is 433kohm, and on plc is 200 kohm.

    • @TimWilborne
      @TimWilborne  3 года назад +1

      @@jeesonpeter2049 You should be fine then.

    • @jeesonpeter2049
      @jeesonpeter2049 3 года назад

      @@TimWilborne thank you for the support and information❤️

  • @somnathpaul6620
    @somnathpaul6620 3 года назад +1

    100 mv signals can be transmitted by wire long?

    • @TimWilborne
      @TimWilborne  3 года назад +1

      No, as we explained in this video, voltage drop will become an issue.

  • @nikariff18
    @nikariff18 2 года назад +1

    Ok im pretty new to this kind of stuff, how do u generate 4-20mA from a PLC instead of voltage output?

    • @TimWilborne
      @TimWilborne  2 года назад +1

      You must have a 4-20mA analog output.

    • @nikariff18
      @nikariff18 2 года назад

      @@TimWilborne do u have a video abt generating 4-20ma from a plc?

  • @alexisvillalobos3560
    @alexisvillalobos3560 Год назад +1

    Hi I have watched some of your videos and they are very well done. I am not an engeneer but I am trying to make a device that is feed by:
    1. In 110V 2. Out: 0-60V - 0-35mA. (with a knob to control the voltage and if is possible the mA as well. I want to use it as a intophoresis device. Can you help me out with the project? If there is a price for it, please let me know. Thanks.

    • @inothome
      @inothome Год назад

      Buy an off the shelf bench top power supply. Normally you can only control one value at a time either the current or the voltage. Since depending on the load the ratio of Volts to Amps will change one of the values to obtain the constant of the value you want. Say to maintain a 35mA output, depending on the load the voltage can be 1 Volt or 100V. If is you wanted a steady 60V, depending on the load your current will have to change to keep the Voltage constant. So in order to have a precise voltage AND current the load would have to be configured to achieve those constants.

  • @johnbrinkley1440
    @johnbrinkley1440 3 месяца назад +1

    How do you program a 4-20mA input using CCW .

    • @TimWilborne
      @TimWilborne  3 месяца назад +1

      Check out the analog section in this course.
      courses.twcontrols.com/courses/allen-bradley-micro800-plc-training

    • @johnbrinkley1440
      @johnbrinkley1440 3 месяца назад +1

      @@TimWilborne Thanks . I am a monthly subscriber to the TW Controls lesson series ! I learned more from you then I did in my previous classes for the community college I attended . Started on SLC 500 and Micrologix, love these micro 800s , they do a lot and inexpensive. I also have the 4-20mA simulator and the IP config tool you sell they help a lot in troubleshooting. You been a big help to me and I appreciate the lessons!

    • @TimWilborne
      @TimWilborne  3 месяца назад +1

      That is great to hear!

  • @tbrd69
    @tbrd69 5 лет назад +1

    Are you going to cover PID loops?

    • @TimWilborne
      @TimWilborne  5 лет назад +2

      Hi Robert. Yes. After we go through analog, we'll do math instructions, then PID loops.

    • @MM-vi9kh
      @MM-vi9kh 4 года назад

      @@TimWilborne I'm waiting for math instructions 😍😍

  • @steffankaizer
    @steffankaizer 5 лет назад +2

    0-10VDC isnt 0-10v its usually 2-10VDC to detect disconnects but yes they both have pros and cons

    • @aussiegruber86
      @aussiegruber86 2 года назад +1

      no, that's why you would use 4-20mA

  • @clems6989
    @clems6989 2 года назад +2

    Who would run awg22 wire 100 feet ?

    • @TimWilborne
      @TimWilborne  2 года назад +1

      The answer is in one of those missing web links you keep complaining about 🙄

    • @clems6989
      @clems6989 2 года назад +1

      @@TimWilborne "Keep complaining about" Wow,
      Adios to this channel...

    • @TimWilborne
      @TimWilborne  2 года назад

      Try @SolisPLC, he is probably more thorough...

  • @kasinbb207
    @kasinbb207 4 месяца назад +1

    why dont use 1 to 10VDC to avoid 0V

    • @TimWilborne
      @TimWilborne  4 месяца назад +1

      Overall, 4-20mA is more reliable if you are concerned about the 0V signal vs failure.