Ventilation does a modern gas engineer need to know it.

Поделиться
HTML-код
  • Опубликовано: 24 янв 2025

Комментарии • 16

  • @ScottyDog345
    @ScottyDog345 Месяц назад

    Love the videos.Its taking me ages to do my portfolio.However one tging i have noticed on this video,which needs pointing out.When you have gone from gross to net you have stated the figure 27.02 then minus the 7 ....20.02
    Then 20.02 x5 you have stated 100.13.
    So when doing these calculations DO NO ROUND YOUR CALCULATOR DOWN SO
    30 /1.11 =27.027
    27.027 -7=20.027
    20.027 ×5 =100.13
    Just letting people doing their ACS out there like myself.
    To be wary
    LOVE THE VIDEOS FANTASTIC.
    Dont want to come across as pedantic.Just staing a fact.
    Good luck everyone.

  • @scottlouis4076
    @scottlouis4076 Год назад +5

    Why am I watching a ventilation video on my day off Derek? 😂

    • @tomkatgastraining
      @tomkatgastraining  Год назад +4

      Because you need your tomkat fix 😂

    • @Viewer765
      @Viewer765 3 месяца назад

      Why can’t you show what is allowed

  • @johnward5006
    @johnward5006 Год назад +3

    Because installers don't install appliances that require any kind of ventilation (Intergas are an exception in certain installations for cooling putposes) they almost disregard the ventilation requirements of appliances they encounter.
    I hope all installers will be reminded to assess the vents they come across to avoid potential risks.
    It maybe old tech.,but there are loads of appliances still out there waiting to bite the unwary or complacent!

  • @space48725
    @space48725 11 месяцев назад

    Derek is master .He simply explain all thing so is easy to understand .Thank you Derek .I will watch you as long as you going to be in youtube.

  • @RajindersinghGallon
    @RajindersinghGallon 8 месяцев назад

    Very helpful

  • @kukiechag99
    @kukiechag99 10 месяцев назад

    @tomkatgastraining what is the ventilation requirement for a flueless gas fire with a catalytic converter?

    • @tomkatgastraining
      @tomkatgastraining  10 месяцев назад +1

      100cm2 up to 2.7kw then 55cm2 per kw over 2.7kw in a room

    • @kukiechag99
      @kukiechag99 10 месяцев назад

      @@tomkatgastraining if it doesn't mention how many kw the fire has what do i put?

    • @tomkatgastraining
      @tomkatgastraining  10 месяцев назад +2

      @@kukiechag99 the fire should have a data badge with the heat input in kw. If you don’t have one and you don’t have the instructions you will need to speak to the manufacturer.

  • @accesszero4803
    @accesszero4803 Год назад

    Am sorry mate,ive not long sat in the classroom with u doin this again and cant sit through it again 😂

  • @idriselmi4101
    @idriselmi4101 Год назад

  • @paul_my_plumbs_uk
    @paul_my_plumbs_uk Год назад

    Flueless is clueless 😂😂😂

  • @davebayliss3142
    @davebayliss3142 6 месяцев назад

    Complete waste of time , it’s only there to generate money from the engineers