Main System Eco HE boiler pressure too high

Поделиться
HTML-код
  • Опубликовано: 22 мар 2012
  • Boiler pressure is too high on stand by.. but when the boiler is woring pressure indicator decreases to Green! Do you know why...( Give you a clue.. Pressure goes low when the pump is on)

Комментарии • 11

  • @repairs4pcrepairs4pc67
    @repairs4pcrepairs4pc67 8 лет назад +1

    Correct Dan, according to the manual online from main, it says 0.5 bar. When I removed the expansion vessel in my main combi eco 25, it says 0.8 bar on the label attached to it, which is roughly around 11.60 psi. I had the same issue where upon turning off the boiler, it will reach 4 bar and I had to top up every 2 or 3 days. Took out the expansion vessel, emptied it completely, then recharge using a compressor up to roughly 0.8 bar. Put everything back and boiler works fine now. Thanks Dan for sharing your knowledge.

  • @k956upg
    @k956upg 10 лет назад +6

    The expansion vessel on most main Eco / elite boilers is low from production.
    I have fitted about 150 of them & they usually need to be empty of water then empty the expansion vessel then refil with foot pump to about 1-1.2 bar
    It's all u need to do.
    The mistake people do is
    Lowering the pressure by bleeding a rad will bring it down but when u run it the air particles in the water will expand with heat & up the pressure will go.
    Then it will contract to a low pressure when cold.meaning unstable pressure.
    The only other thing is if you have lots of radiators you may exceed the expansion vessels capacity.but that's only in very big houses.

  • @stitcheruk1150
    @stitcheruk1150 6 лет назад +1

    One suggestion for the pressure issue is to check the filling loop. If it is still fully connected, as mine was, it may well be that it is still letting a small amount of water in to the system. Excess water escaped through the pressure valve but also leaked through the thermostat valves on the radiators. I just had to slightly back off the filling tap and my pressure was sorted - a fault in the tap on the filling loop.. However, as the high pressure had been happening for some time I also had to replace the expansion vessel which had started to leak - possibly due to continual high pressure.

  • @ndukaanalogbei1043
    @ndukaanalogbei1043 6 месяцев назад

    Is it safe to bath when the boiler bar is at 3.5, would it have any effect on the boiler?

  • @Waynetywh4526
    @Waynetywh4526 10 лет назад +3

    Has this problem always been present on the boiler?

  • @Memories4lifemedia
    @Memories4lifemedia 6 лет назад

    its the same with all main eco elite boilers installed hundreds of them

  • @sharonfrost4323
    @sharonfrost4323 2 года назад

    God ours is forever doing this

  • @tonywit55
    @tonywit55 10 лет назад

    Connections reversed on pressure guage

  • @chalker1100
    @chalker1100 5 лет назад

    Reset "....WHERE