• Power factor panel dr... • power factor panel ko ... drawing of power factor panel.@electricworkcenter @ElectricalTechnician @KhanSirPatnaKhanGs
Sab parameters setting kr liya hu but still relay auto mode me on nhi ho rha hai..kya reason hoga sir ?manual mode me sare capacitors check kr lia hu.working fine
Nice
Harmonic filter aur capacitor bank maintenance ka video bnaye sir..❤
Ok sir
Sab parameters setting kr liya hu but still relay auto mode me on nhi ho rha hai..kya reason hoga sir ?manual mode me sare capacitors check kr lia hu.working fine
Kindly check sensing ct wire. Proper connected or not.
Contactor terminal frequently burning plz tell me
Use capacity duty contactor . Terminal screw should be properly tight. Sensitivity and discharge sensitivity min. 60 s.
sir mere pass model no BR 5016 but sir auto me kam to karta hai par auto me pf maintain nahi hota hai kya reason ho skta hai
Check proper connection of sensing ct
Sir mere pass hai damege ho gaya hai to dusra lagana hai
Apko apne panel supplier se baat kar lo wo provide kara dega
Sir mujhe new lagana hai
Apka site address kya hai
Siddharthanagar gorkhpur
Sir apfc relay steps on to karti h lekin kuch der bad sare stap trip ho jate h kya reason ho sakta h me 33kv sub station operator hu sir please btaye
Koi contactor kharab hoga. Manual mode me sare capacitor ko on kijiyega one by one.
Sir mera apfc relay without on any stage show 0.94 what can I do for 0.99
Small step ke capacitor bank install karo.
Ato mod not working sir any problems
Manual mode me sare capacitor bank check Karo. koi contactor ka contact stuck ho gaya hoga
Coi contect no hai aapka