Parameterization of the 3RW55 Soft-Starter | Pumping system

Поделиться
HTML-код
  • Опубликовано: 31 июл 2024
  • ▸ Welcome to a new video from The EP Specialists, this week we bring you a complete guide on how to parameterize our 3RW55 Soft Starter for a Pumping System.
    Do not forget to leave your doubts or suggestions in the comments!
    ▸ In this video:
    1. Today we present: 00:07 - 00:25
    2. Automatic Parameterization: 00:26 - 02:31
    3. Extended Parameters: 02:32 - 04:15
    4. OJO - Non-Automatic Parameterization: 04:16 - 06:00
    5. Application Assistants: 06:01 - 08:56
    6. Farewell: 08:57 - 09:12
    ----- ✅ WE GROW TOGETHER ✅ -----
    We want to give you quick answers to your technical questions. LIKE AND SUBSCRIBE!
    #Siemens #SoftStarter #Arrancador_Suave #3RW55 #Ecuador #Industry #sub #youtubechannel #vlog #Mexico #Siemens_Mexico #contentcreator #subscribe
    #Argentina #youtubeecuador #Peru #youtubecolombia #youtubeperu #Colombia
    #Siemens_Peru #Peru #Smart_Infrastructure #Electrical #Products #Siemens_AR #Siemens_Products
  • НаукаНаука

Комментарии • 34

  • @edilbertoescandonalvarez594
    @edilbertoescandonalvarez594 29 дней назад +1

    @losespecialistasdeep Hola saludos desde Colombia. Gracias por los videos tutoriales los cuales me parecen interesantes y bien explicativos. Aprovecho para consultarte ¿cómo puedo integrar dos bombas a un solo arrancador suave 3RW55 Siemens por medio de contactores?, aclaro que una bomba va a estar en servicio permanente (bomba principal) y la otra bomba va estar en stand by como respaldo (bomba auxiliar) por si la bomba principal falla; ya que el recurso económico es escaso para adquirir los dos arrancadores suaves. ¡Muchas gracias por tu atención! Dios te bendiga.

    • @nikx9532
      @nikx9532 15 дней назад

      Tendria que utilizar el modo bypass externo utilizas dos contactores los cuales van conectados a las bombas, 1 contactor por bomba, y utilizas dos muletillas de 2 posiciones y ahi lo que tendrias que hacer es un pequeño control con las muletillas para que cuando este funcionando la primera de ninguna manera pueda entrar la 2 y viceversa, pues de esta forma yo lo haria y supongo que habra otra forma.

    • @nikx9532
      @nikx9532 15 дней назад

      o puedes utilizar una muletilla de 3 posiciones, posicion central e izquierda y derecha, pero tener en cuenta que estos arrancadores no se pueden activar con mucha frecuencia osea apagar y prender digamos en 1 minuto por que tengo entendido que se pueden dañar y lo recomendable es despues de los 12 minutos volver a utilizar el arrancador

  • @CarvajalWilliam
    @CarvajalWilliam Год назад +2

    Buenas tardes amigo, el video me ha sido de bastante ayuda pero tengo un inconveniente, instale el arrancador en una bomba hidraulica de 110Hp con parametrización automatica, el cual estuvo funcionando sin presentar novedades x algunas horas, la novedad presentada es que en el SCADA se presenta una señal de bloqueo de bomba (solo señal xq la bomba sigue funcionando sin problemas) el cual se desbloquea desde el mismo sitio, mi consulta es si la señal de los bornes 95 y 98 no son constantes?? o que cree que puede estar pasando en el arrancador, ojo en arranque directo no presenta esta señal de bloqueo, ademas ya se reviso todos los elementos que intervienen en el control y no existe inconveniente. Muchas gracias por tu respuesta, saludos desde Ecuador.

    • @gustavo.barnuevo
      @gustavo.barnuevo Год назад

      Gracias por comentar, nuestro arrancador 3RW55 tiene la salida; 95, 96 y 98 para señalización de errores y normalmente se usan para conectar balizas, que le permite al operador observar a distancia si el equipo presenta algún fallo como; elevación de corriente, desbalance de fase, entre otros. Todo depende de como se tenga configurado el equipo frente a una falla, por ejemplo, si se trata de asimetría entre fases, puede configurar el porcentaje límite para que se muestre una advertencia (''warning'') y si ese porcentaje sigue aumentando se mostrará ''error'', en cambio si el porcentaje cae por debajo del umbral de ajuste de ''warning'', se resetea la falla y las salidas reales regresarán a su posición original. El equipo se puede configurar para que se resetee solo (no recomendable) o resteo localmente (recomendable) esto quiere decir con la intervención de un operador.
      En tal caso, puede ser que el umbral de sobrecorriente máx/mín no sea el adecuado, habría que revisar que fallo se presenta continuamente, esto lo puede observar en el registro de fallos de manual del arrancador que adjunto a continuación.
      cache.industry.siemens.com/dl/files/752/109753752/att_953971/v1/manual_softstarter_3RW55_and_3RW55_Failsafe_en-US.pdf

  • @koffiagbekossi7353
    @koffiagbekossi7353 2 года назад +2

    Nous voulons une traduction en français

  • @pachitorock9822
    @pachitorock9822 Год назад +1

    Hola , muy buen video, es de gran ayuda, tengo una consulta, en el menú de datos del motor te pide PAR del motor, como agregar o calcular ese parámetro, saludos

    • @losespecialistasdeep
      @losespecialistasdeep  Год назад +2

      Gracias por comentar, esta variable se la calcula manualmente con los datos de placa del motor y su fórmula es la siguiente:
      Par asignado (Nm) = potencia (kW) * (9550 / velocidad asignada (1/min))
      Quedamos atentos a cualquier inquietud.

    • @pachitorock9822
      @pachitorock9822 Год назад

      @@losespecialistasdeep muchísimas gracias estimados amigos, me gustaria profundizar más sobre estos equipos, brindan capacitación online? Estoy muy interezado, saludos

  • @williamwalterespinozamayta6166
    @williamwalterespinozamayta6166 2 года назад +1

    Buen día . La consulta es si quiero guardar todos mis parámetros en un micro USB como cargado y descargo en otro equipo 3rw55

    • @gustavo.barnuevo
      @gustavo.barnuevo Год назад

      Gracias por su comentario, para realizar transferencia de datos existen dos métodos; la función ''Sustitución del aparato'' que es por medio de una tarjeta micro SD insertada al 3RW5 High-Feature HMI, y la otra opción es usar SIRIUS Soft Starter ES (TIA Portal).
      El primer lugar se deben guardar los datos del arrancador a sustituir, a continuación se detalla como realizarlo:
      - Menu: Tarjeta micro SD > Cargar parametrización en tarjeta SD
      Luego, en el nuevo arrancador seguir los siguientes pasos:
      1- Insertar la tarjeta micro SD en la pantalla High Feature HMI de su arrancador.
      2- Transfiera los datos al/los dispostivo/s.
      Menu: Tarjeta micro SD > Sustitución del aparato
      3- Verifique los datos transferidos.
      Lo invito a ver el siguiente video de nuestro canal, para tenga como referencia:
      ruclips.net/video/IHAejV0k4tw/видео.html

  • @migsilk27
    @migsilk27 Год назад +1

    hola, tengo un arrancador 3RW5548 DAÑADO, veo en la Pagina de siemens que el modulo de control es el mismo deL 3RW5526 HAGO le intercambio pero el arrancador en la potencia del 3rw5548 mas sin embargo no me deja cambiar la potencia, ustedes podrian ayudarme a saber como se hace el reemplazo de esta pieza?

    • @jorgeluisortega7889
      @jorgeluisortega7889 Год назад

      Gracias por su comentario. La tarjeta de control es la misma para nuestros arrancadores 3RW55 desde el tamaño 1 a 4, pero en el caso que necesite reemplazarla de un equipo al otro, los arrancadores deben ser el mismo modelo; por lo cual no va a funcionar si cambia la tarjeta de control de un 3RW5526 a un 3RW5548, esto se debe a que la unidad de control viene preconfigurada para su modelo de arrancador en específico. Entonces, la solución sería pedir una nueva unidad de control y configurarla en base al arrancador deseado.

  • @danielhabib1425
    @danielhabib1425 2 года назад +1

    Hello, I have a proplem when I save the new parameters for the motor and cut off the electric the softstarters get the old parameters why so ?

    • @losespecialistasdeep
      @losespecialistasdeep  2 года назад

      When you have the automatic parameterization mode enabled in the soft starter, the parameters that will be loaded will be those that the device has calculated at startup. To keep the parameters loaded manually you must disable the automatic parameterization. Another cause could be if you have a network card installed in the soft starter, the equipment will give preference to the parameters that it sends over the network and will overwrite those that you have parameterized locally.

  • @noeramirezgomez6742
    @noeramirezgomez6742 2 года назад +1

    Buen día espero me pueda ayudar con mi pregunta para un motor de 300 HP de una trituradora de piedra también lo puedo configurar en parametrización automática?

    • @losespecialistasdeep
      @losespecialistasdeep  2 года назад

      Gracias por comentar, efectivamente el 3RW55 en su modo parametrización automática tiene un algoritmo para la aplicación "Trituradora"; sin embargo todo debe partir de una correcta selección y dimensionamiento del equipo para la aplicación, nuestro software STS nos ayuda con esta selección, incluso para poder ver la curva del carga de una trituradora y su momento de inercia inicial dependiendo si arranca con carga o sin carga, o que niveles de corriente necesitaria para poder mover su carga. Otra opción si ud conoce su aplicación puede hacer uso del modo experto donde incluso puede usar un voltaje de impulso inicial para vencer la inercia en caso la maquina este cargada o trabada en el arranque. Video Parametrización modo experto próximamente en el canal

  • @guillermogonzalesvalladare647
    @guillermogonzalesvalladare647 2 года назад +1

    Hola buenas noches, tengo un arrancador 3RW5547 lo cual le doy arranque pero a los pocos minutos de que trabaja el motor me sale el diagnóstico de falta consumidor. Como puedo arreglar eso. Porque reseteo y vuelvo a prender y sucede lo mismo.

    • @gustavo.barnuevo
      @gustavo.barnuevo Год назад

      Gracias por su comentario, nuestro arrancador 3RW55 cuando no detecta el flujo de corriente después de energizarse el motor, manda a fallo al arrancador mostrando el mensaje ''falta consumidor''. Esto generalmente ocurre, por lo siguiente,
      • Circuito principal interrumpido (fusible, disyuntor).
      • Contactor de motor o contactor de control defectuoso.
      • En el instante en que se utilizan motores de capacidad menor al 10 % de la capacidad nominal.
      • Sin carga.

  • @assemelamirelmasri8739
    @assemelamirelmasri8739 Год назад

    Buen video, solo tengo una pregunta, si necesito la biblioteca del bloque de función que podría controlar el SOFTSTART usando TIA PORTAL, ¿puedo encontrar esta biblioteca con usted, que podría ayudarme a comunicarme con el programa a través de la conexión de telegrama y puedo use PROFINET para ver el consumo actual, código de error, fallas, etc.

    • @losespecialistasdeep
      @losespecialistasdeep  11 месяцев назад

      Gracias por comentar, el paquete de software para la puesta en marcha, operación y diagnóstico de nuestros arrancadores suaves en TIA PORTAL se llama SIRIUS Soft Starter ES, mismo que está sujeto a un costo dependiendo el tipo de licencia, no obstante, es posible utilizar una licencia de prueba por 21 días. Para la comunicación es necesaria la tarjeta de red, y la puede adquirir en los diferentes protocolos de comunicación: Profinet, Profibus, Modbus TCP, entre otros. A continuación, adjunto más información del paquete, sus licencias y link de descarga.
      support.industry.siemens.com/cs/document/109811681/sirius-soft-starter-es-v18-(tia-portal)?dti=0&lc=en-AR

  • @macarenaparisi6410
    @macarenaparisi6410 2 года назад +1

    hola, una consulta como se prende el arrancador?? gracias

    • @losespecialistasdeep
      @losespecialistasdeep  2 года назад

      Gracias por escribirnos, nuestro arrancador suave 3RW55 debe ser alimentado en los bornes de control A1 y A2 en el rango de voltaje de 110 a 250 V AC, o de requerir lo puedes pedir para voltaje de 24V AC/DC. Cualquier otra inquietud no dudes en consultarnos

  • @jcamilo.sierra
    @jcamilo.sierra Год назад

    Buenas noches tengo unos arrancadores que los quiero aplicar a una corriente pequeña de 15A per el arrancador tiene un limite bajo de 34A

    • @losespecialistasdeep
      @losespecialistasdeep  Год назад

      Gracias por comentar, nuestros arrancadores generalmente al detectar corrientes muy bajas por debajo de su umbral límite en amperios, mandan a fallo al equipo por ''falta de consumidor''. Sin embargo, me gustaría conocer, específicamente cual es el modelo del arrancador suave que está utilizando?

    • @jcamilo.sierra
      @jcamilo.sierra 9 месяцев назад

      @@losespecialistasdeep buenas noches las referencias que manejamos son sirius 3RW5246 , 3RW5536 Y 3RW5546

    • @jcamilo.sierra
      @jcamilo.sierra 9 месяцев назад

      tengo una consulta con un punto de falla que están presentando todos los de la linea 3RW5536 Y 3RW5546 favor dejar correo para hacer llegar la novedad o me puedan brindar la orientación

  • @user-ki6cz8jr4z
    @user-ki6cz8jr4z Год назад

    Y cuándo muestras las alarma de falla, es que dice fallo en común

    • @losespecialistasdeep
      @losespecialistasdeep  Год назад

      Gracias por comentar, estamos trabajando en un video para mostrar las fallas de alarma de nuestro arrancador 3RW55, quede atento a nuestras redes.

  • @josueruiz3556
    @josueruiz3556 2 года назад

    Sino quiero ni la parametrización automática, ni la de asistente de aplicación; Cómo hago para que se utilice directamente con los datos del motor?

    • @losespecialistasdeep
      @losespecialistasdeep  2 года назад

      Gracias por comentar, efectivamente como se pudo observar en el vídeo solo tratamos la parametrización automática y el uso del asistente; sin embargo podemos ingresar mas datos y hacer uso de mas funciones cuando el usuario conoce bien su aplicación y quiere sacar el máximo provecho a las funciones del equipo usando los parámetros ampliados.. Ese vídeo es la segunda parte de este vídeo, estamos pendientes de realizarlo . "Modo experto" muy pronto en el canal.

  • @naimayoub7412
    @naimayoub7412 2 года назад

    ¿Tienen idea como controlar un Arrancador 3RW55 mediante PROFINET con TiaPortal? Nadie puede ayudarme

    • @losespecialistasdeep
      @losespecialistasdeep  2 года назад +1

      Hola Gracias por escribirnos, en el siguiente link hacemos al final del video un arranque con TIA PORTAL, haciendo uso de una tarjeta PROFINET
      ruclips.net/video/qqk3qS2jzZQ/видео.html

    • @naimayoub7412
      @naimayoub7412 2 года назад

      @@losespecialistasdeep Excelente video. Avancé mucho. El inconveniente que tengo ahora es con la comunicación con el PLC para que este pueda controlar el Arrancador Suave a través de PROFINET de forma automática. Para variadores de velocidad utilicé la librería SINASPEED, pero no encuentro un análogo para Arrancadores Suaves. El ejemplo de la página de Siemens no me dió resultado. Ojalá me puedan ayudar