  • Hey everyone. Hope you are well. Today Wilson & I test 2 Halon 1301 Systems protecting 2 large magnetic laboratories. The way these systems is in the following steps:
    Upon the first alarm, a bell / strobe will activate to notify of a fire. This bell goes on infinitely.
    Upon the second alarm, the system goes into pre-discharge. The horn strobe next to the bell will begin to sound. This signifies that there is 20 seconds until discharge.
    After 20 Seconds, the discharge light one the panel activates, the solenoids are energized (if connected to the bottle, it would dump the Halon), and the Horn Strobes outside the protected area begin to sound to signify that discharge has begun.
    Any alarms on this system will result in the activation of the building fire alarm.
    Equipment:
    Fenwal 2210 Special Hazard Control Panel
    Fenwal PSD-7130 Photoelectric Smoke Detector
    Fenwal CPD-7129 Ionization Smoke Detector
    Fenwal CPD-7054 Ionization Smoke Detector
    Fenwal CPD-7051 Ionization Smoke Detector
    Fenwal/FCI MS-2H Halon Manual Release Pull Station
    Wheelock MBS-G6-24-WS Bell Strobe
    Wheelock 7002T-24 (Halon Lettering)
    Wheelock NS-24-MCW
    Fenwal Abort Switch (Model Unknow)
    Fenwal Halon 1301 (500 lbs tank)
    Fenwal Halon 1301 (300 lbs tank)
    Fenwal 890181 Electric Solenoid Control Head
  • РазвлеченияРазвлечения

Комментарии • 40

  • @FireAlarmGuy13
    @FireAlarmGuy13 Год назад +4

    Hahaha! So halal!

  • @willbill808
    @willbill808 Год назад +4

    Time to vamoose when the dying duck quacks for Halon.

  • @burnoutteamclubbtcp7283
    @burnoutteamclubbtcp7283 Год назад +3

    Yep, there are some Halon systems that will automatically activate the Main Fire Alarm System.

    • @alexgilbert2
      @alexgilbert2 Год назад

      I heard about that before, it makes sense honestly

  • @EYL8902
    @EYL8902 Год назад +6

    Nice, I love it. Those 7002Ts with the halon wording are rare and cool!

  • @samanthashafer1742
    @samanthashafer1742 Год назад +1

    Without even reading the description I heard the sound of a cold head and I thought, this is either a radiology floor or a magnetic laboratory.
    Been through enough MRIs to know the sound of a chugging helium tank

  • @ElCalamardo69
    @ElCalamardo69 Год назад +2

    Old school Fenwal! I've only seen one such panel but that one had a big Halon ball hanging from the ceiling

    • @a.r.aproductions1569
      @a.r.aproductions1569  Год назад +2

      Wait till you gotta remove a bunch of those old Fenwal Spheres. Pain in the butt man. Spent a whole week doing it back in October.

  • @IndustryAndMusic
    @IndustryAndMusic Год назад +2

    Awesome video. Suppression systems are some of the coolest alarm systems, especially Halon. Is Halon 1301 the only variant of Halon that is still used this day or is Halon 1211 still used?

    • @a.r.aproductions1569
      @a.r.aproductions1569  Год назад +1

      1211 is only used in extinguishers. It has a higher concentration and drops the oxygen content down way lower than 1301 does. The whole point of Halon 1301 was to have a rapid suppression agent with minimal damage to equipment and to people.

    • @IndustryAndMusic
      @IndustryAndMusic Год назад

      @@a.r.aproductions1569 that's what I thought. I have been trying to find more about Halon because there have been so many variations and most of them are dangerous for humans, it's just been hard to find videos like that because Halon is not something that you can just go out and discharge, but now I know a little bit more. Thanks!

  • @GaryBeltz
    @GaryBeltz Год назад +2

    I thought Halon systems had to be replaced with FM200 or some other suppression systems because of risk of suffocation for anyone stuck in the room and other regulations.

    • @GaryBeltz
      @GaryBeltz Год назад

      @MBTA Fan they are generally tied to the buildings fire alarm system but they are meant to protect server rooms, labs and other sensitive areas

    • @a.r.aproductions1569
      @a.r.aproductions1569  Год назад +5

      Halon is non toxic to humans. It was deemed unsafe for the environment because of its effects on global warming. You could be in a room with halon dumping and you will be fine. CO2 on the other hand, it can kill you.

  • @aidanthetoiletelevatorfire7554
    @aidanthetoiletelevatorfire7554 Год назад +1

    I love the system!

  • @alexgilbert2
    @alexgilbert2 Год назад +1

    where do you keep finding halon systems with their own alarms? this is still awesome though!!

    • @a.r.aproductions1569
      @a.r.aproductions1569  Год назад +2

      Im a Halon/ Clean Agent Suppression Technician. These systems are actually in more places than you would think. So I do these more often than fire alarm now. I try to film all these old ones because there isn’t much documentation or many videos of them existing. Im glad you enjoyed!

    • @alexgilbert2
      @alexgilbert2 Год назад

      @@a.r.aproductions1569 thanks a lot man, you really got me interested in halon systems now. hopefully you can show us more, never knew you were a halon technician

    • @a.r.aproductions1569
      @a.r.aproductions1569  Год назад +1

      @@alexgilbert2 I will try and do as many as possible. I’m glad you enjoy them! They really are awesome!

    • @alexgilbert2
      @alexgilbert2 Год назад

      @@a.r.aproductions1569one question, when you mentioned the horns outside do they also have halon lettering or just general fire

    • @a.r.aproductions1569
      @a.r.aproductions1569  Год назад +1

      @@alexgilbert2 when I walk out the door and show the other 7002T, that’s what I am referring to. The one outside the protected area.

  • @JBF-GST-Tanda
    @JBF-GST-Tanda Год назад

    MRI room?

  • @noahfurry4146
    @noahfurry4146 Год назад

    I thought all halon was removed along time ago

  • @user-Calebculwell
    @user-Calebculwell Год назад

    Those are some cool devices

  • @midnightjackolantern1070
    @midnightjackolantern1070 Год назад

    do u have to have A DAEPLOMA TO DO THIS JOB

    • @a.r.aproductions1569
      @a.r.aproductions1569  Год назад

      Yes you need a high school diploma to do this job. However, a college education usually isn’t needed to do this. Most of the skills you learn on the job.

  • @CoolSimasGuy
    @CoolSimasGuy Год назад

    Where’s Fire Suppression #5?

  • @riseandfallchannel2763
    @riseandfallchannel2763 Год назад

    i seen halon alarms like that online, Never in person. Still cool just wondering where this is found
    lemme take a guess… sensitive areas?

    • @a.r.aproductions1569
      @a.r.aproductions1569  Год назад +1

      Usually areas where there is sensitive data or equipment that if damaged, would cost thousands if not millions in losses.

    • @riseandfallchannel2763
      @riseandfallchannel2763 Год назад

      @@a.r.aproductions1569 like a lab?

  • @firealarm2903_
    @firealarm2903_ Год назад

    So cool!!!

  • @firealarm2903_
    @firealarm2903_ Год назад

    Were the MS2s added later on?

    • @a.r.aproductions1569
      @a.r.aproductions1569  Год назад

      Nope. They are original to the system. These are pretty old models from the 80’s.

    • @firealarm2903_
      @firealarm2903_ Год назад

      @@a.r.aproductions1569 dang

  • @vrryan6
    @vrryan6 Год назад

    Very cool. I love suppression systems, they’re so cool!