Trane Commercial Package Unit ….8.5 Ton THC102 Not Cooling

Поделиться
HTML-код
  • Опубликовано: 25 окт 2024

Комментарии • 24

  • @Freeagent-z7l
    @Freeagent-z7l Год назад +2

    I worked on Trane equipment for 24yrs in Trinidad and Tobago with our local dealer comfort engineering ltd.. learnt alot whilst there

    • @subcoolHVAC
      @subcoolHVAC  Год назад +1

      Good stuff, Thanks for watching!

  • @MariosACandRefrigeration
    @MariosACandRefrigeration Год назад +2

    condenser motor sounds rough,thanks for sharing,nice fix.

    • @subcoolHVAC
      @subcoolHVAC  Год назад

      Thanks, that unit has seen better days for sure.

  • @zekenzy6486
    @zekenzy6486 6 месяцев назад

    Nice Work and Good Job. Thank you for sharing

  • @jessemayra
    @jessemayra Год назад +2

    Good work

  • @stevencarrillo3615
    @stevencarrillo3615 Год назад +2

    Learned something thanks

    • @subcoolHVAC
      @subcoolHVAC  Год назад

      Thanks for watching, always learning myself

  • @danielarteaga3913
    @danielarteaga3913 Год назад +2

    Good video

  • @JP-sd2cw
    @JP-sd2cw Год назад +2

    Can you explain the back feeding terminology? your missing a phase, yet to ground they are all the same 118v to ground….so in order for you to go to ground still and miss a phase, basically on of those legs is powering a load i guess that feeds back to the other leg ? Im so confused

    • @subcoolHVAC
      @subcoolHVAC  Год назад +1

      That’s exactly what is going on , the other legs on line side are feeding through loads giving the 118 v reading. Had I disconnected the line wires from the contactor the missing leg would show to ground. Checking across fuses confirmed .

  • @Shutyourjibbs
    @Shutyourjibbs Год назад +3

    Did you end up having to add some refrigerant? I saw the R-22 jug hooked up to your gauges at the end of the video.

    • @subcoolHVAC
      @subcoolHVAC  Год назад +3

      Good catch, ckt 1 had a minor hose leak on high side. By the time I caught I wasn’t sure how long it had been loose. Added some vapor but Superheat was within a degree of ckt 2 so I don’t much was lost.

  • @eramirez5763
    @eramirez5763 Год назад +2

    That coil should’ve been split and chemically cleaned

    • @subcoolHVAC
      @subcoolHVAC  Год назад +1

      Scheduled at later date, had to move on. Thanks for watching!

  • @gabrielchiu2650
    @gabrielchiu2650 Год назад +2

    that poor trane seems to been neglected

    • @subcoolHVAC
      @subcoolHVAC  Год назад +1

      Unfortunately it only gets attention when it stops cooling.

  • @CSXRailfan6588
    @CSXRailfan6588 Год назад +4

    Why is the condenser coil red

    • @subcoolHVAC
      @subcoolHVAC  Год назад +2

      Good question, It was treated with a corrosion resistant coating when it was new.

  • @RJ-ix4co
    @RJ-ix4co 4 месяца назад

    Can’t believe you didn’t check those filter dryers. I bet they are getting clogged up from someone using some mo99 or 438a. Just from looking at those pressure and since someone had cut the high pressure safeties off. Those contractors looked bad too.

    • @subcoolHVAC
      @subcoolHVAC  4 месяца назад

      The Fixed metering manifold was clogging, A/C Renew added and ended up correcting the restrictions . Condensing coil is also fouled, and that design has a tendency to recirculate condenser discharge air into condenser. It’s shoved in the corner of a building. HP switches also replaced…. Only R22 used… thanks for watching!