Troubleshooting a Rooftop Condenser Unit with a Tripped Breaker and Fried Motor

Поделиться
HTML-код
  • Опубликовано: 8 фев 2025
  • YT301
    Called out for the Beer Aisle Front half on RTU 2 reported as not cooling. I found the RTU Not running. One of the 2 breakers for the condenser fan motors tripped. Upon resetting the breaker and pushing the manual HPS, a short popped off from one of the motors and tripped the breaker again. Found that Fan # 3 is fried completely. Windings totally burned. Unwired it, reset the breaker, and started the unit and unit runs. I removed the fan motor page and assembly with the blade and tried to remove the blade, and the set screw for the blade snapped. We will need to order a new motor and a new blade. Until then , the unit should operate and run normally with the 3 fans.
    Job Incomplete
    PART Numbers HUSSMANN
    BLADE - 0251098
    MOTOR - 3016977