Troubleshooting a Rooftop Condenser Unit with a Tripped Breaker and Fried Motor
HTML-код
- Опубликовано: 8 фев 2025
- YT301
Called out for the Beer Aisle Front half on RTU 2 reported as not cooling. I found the RTU Not running. One of the 2 breakers for the condenser fan motors tripped. Upon resetting the breaker and pushing the manual HPS, a short popped off from one of the motors and tripped the breaker again. Found that Fan # 3 is fried completely. Windings totally burned. Unwired it, reset the breaker, and started the unit and unit runs. I removed the fan motor page and assembly with the blade and tried to remove the blade, and the set screw for the blade snapped. We will need to order a new motor and a new blade. Until then , the unit should operate and run normally with the 3 fans.
Job Incomplete
PART Numbers HUSSMANN
BLADE - 0251098
MOTOR - 3016977
Beer man gotta make his quota too!
Another day saved 👍👍
Hey man, love the videos. I currently work on kitchen refer. How much more work is doing supermarket stuff? I wanna make the switch and stop working on prep tables and crap but I also wanna see my wife lol
@johnstrh1 it can be alot more at times. Depends on if you work for a major company or not. The big ones can be busy 24/7 so when you're on call it's brutal.