Insulation Resistance Test of Transformer

Поделиться
HTML-код
  • Опубликовано: 28 дек 2024

Комментарии • 48

  • @humanbeing4097
    @humanbeing4097 9 месяцев назад +2

    Superb detailed videos,that every videos should have.

  • @akhtarhussainshah7435
    @akhtarhussainshah7435 2 года назад +4

    It is the ratio of reading taking after 15 or 30 seconds to reading taking after 60 seconds with same coonection as your video. Both readings are taken in one step. The purpose of this test is to ensure integrity of the winding insulation.

  • @nkvaishnav6395
    @nkvaishnav6395 3 года назад +4

    Nice Explanation point to point...Will wait for next video.. Quality video..

  • @shashanksahu2326
    @shashanksahu2326 2 года назад +4

    It is really a very helpful video. It has cleared all my doubts. Thank u sir.

  • @kiwidevo1
    @kiwidevo1 3 года назад +5

    What voltage are you setting the megger to for each test H-XG X-HG and HX-G ?

    • @theengineeringpower4213
      @theengineeringpower4213  3 года назад +2

      For a High voltage i.e. 220kV or 500kV transformer, the megger testing set rating must be 5 kV. For medium voltage i.e. 11kV, megger set of 1kV rating is OK.

  • @judebarnes7595
    @judebarnes7595 3 года назад +4

    Nice work - thank you for posting this video. In the calculations you compensate based on room temperature. Should you instead be compensating for transformer oil temperature.

    • @theengineeringpower4213
      @theengineeringpower4213  3 года назад +1

      You are right. In this video, for simplification ambient temperature is used. However for accurate calculation, the transformer oil temperature must be used, Thanks for your valuable comment.

  • @smartengineeringeee4990
    @smartengineeringeee4990 11 месяцев назад

    Please give the reference informations in detail that where did you get it.

  • @esauogutu1702
    @esauogutu1702 7 дней назад

    What is the need of shorting the hv yet it is delta ?

  • @benjaminotettey6315
    @benjaminotettey6315 Год назад +1

    I love the explanation

  • @erisherm.8451
    @erisherm.8451 2 года назад +2

    Very informative indeed 👍

  • @erwinreyes5888
    @erwinreyes5888 5 месяцев назад +1

    thank you so much for your helpful videos

  • @earnmoney2505
    @earnmoney2505 2 года назад +2

    Thank you sir🙂 ,this is very helpful .

  • @jaydoctor7824
    @jaydoctor7824 2 года назад +2

    Thank you sir for your educational video.

    • @theengineeringpower4213
      @theengineeringpower4213  2 года назад

      You are welcome. Keep in touch for more educational videos related to practical Electrical Engineering.

  • @goodman12310
    @goodman12310 4 месяца назад

    is the 20 ' c the temperature of winding of the ambient temperature ,
    another thing would this work with dry transformers ?
    thanks

  • @ziaullhaqzahid3458
    @ziaullhaqzahid3458 Месяц назад +1

    Helpful

  • @chandanjana6964
    @chandanjana6964 Год назад

    Informative, Thnx sir.

  • @kdmq
    @kdmq Год назад +1

    It's OK to say that any transformer is safe to operate at 20 Celsius, but what if the manufacturing company knows that the transformer is going to be subjected to ambient temperatures much hotter than 20 Celsius? Isn't it better to apply the IR test for the maximum operating temperature. For example, if the transformer is being used in hot summer climates where the temperature regularly reaches 35 Celsius, shouldn't we apply the test for 35 Celsius to make sure there will be no arcing at all times of the year?

  • @Kishore_.035
    @Kishore_.035 2 года назад +1

    What is the resistance value at a temperature of 40 degree celcius

  • @JhonTesfahun
    @JhonTesfahun 2 года назад +1

    nice work.

  • @cedarelectric7763
    @cedarelectric7763 5 месяцев назад

    How dovi test for the temperature of the transformer oil

  • @cedarelectric7763
    @cedarelectric7763 5 месяцев назад

    How do we adjust the temperature of the oil of the transformer

  • @rangerrojo5047
    @rangerrojo5047 3 года назад +2

    Nice work. What books do you suggest about this topic?

    • @theengineeringpower4213
      @theengineeringpower4213  3 года назад +1

      Thanks. As someone practically associated with sub-stations and T/Lines, I would suggest to study updated articles from the internet as the testing sets are evolving with time.

  • @dengakairup
    @dengakairup 3 месяца назад +1

    You are right 👍

  • @TwoFaced2
    @TwoFaced2 Год назад +1

    Can you please make videos on testing of power cables

  • @natural6086
    @natural6086 2 года назад +1

    why did not you use guard terminal.

    • @theengineeringpower4213
      @theengineeringpower4213  2 года назад +1

      It's used practically in most cases. Not shown here to avoid any confusion for new learners. Guard terminal is a way to minimize the interference from unwanted circuits. So e.g. if we are measuring insulation resistance between primary and ground, we will have to guard the secondary terminal of transformer.

    • @hariharroy
      @hariharroy Год назад

      ​@@theengineeringpower4213Could you please explain in more detail? What do you mean by 'to minimise interference from unwanted circuits'?

  • @86karna
    @86karna Год назад

    How the input supply is injected for testing of transformer?. Input source

    • @theengineeringpower4213
      @theengineeringpower4213  Год назад

      Input source is the megger testing set which has built-in battery (in case of electronic set). While in case of old hand operated manual megger testing set, voltage is produced by rotation of crank.

  • @324amit77
    @324amit77 Год назад

    3:04 isn't it 500kOhm ?

  • @Wolf.88
    @Wolf.88 Год назад +1

    Thanks!

  • @sunildevariya7965
    @sunildevariya7965 2 года назад +1

    Tnx

  • @akhtarhussainshah7435
    @akhtarhussainshah7435 2 года назад

    if DAR less the 1 it is dangerous need for maintenance if ration greater then 1 and less then 1.3 the check oil BDV mositure contents and C & DF test of winding if the ratio greater then 1.3 it is good

  • @akhtarhussainshah7435
    @akhtarhussainshah7435 2 года назад

    Dielectric Absorption Ratio (DAR) Test insulation test ruther then IR test

  • @akhtarhussainshah7435
    @akhtarhussainshah7435 2 года назад

    DAR b/w HV to LV, LV to G , HV to G

  • @tyd3407
    @tyd3407 2 года назад +1

    Major Farts 🤣

  • @jasonchristopheraguillon4988
    @jasonchristopheraguillon4988 Год назад

    Insulation Reating of Einding must be not lower Than 10Giga ohms not in mega

    • @theengineeringpower4213
      @theengineeringpower4213  Год назад

      As per insulation resistance minimum requirements for a transformer, for each kV atleast we must have 2 Mega Ohm resistance. so based on this, you can calculate minimum insulation resistance requirements for any rating transformer. that will turn out to be in Mega ohms in most cases

    • @esauogutu1702
      @esauogutu1702 Год назад

      ​@@theengineeringpower4213for each KVA or KV?