Reinforcement lapping Zone as per IS Code 13920 in Column | Learning Civil Technology

Поделиться
HTML-код
  • Опубликовано: 22 дек 2019
  • ✔In case of any confusion, feel free to message me on Facebook:
    / learningciviltechnology
    ✔New Channel Link: House Construction free Support
    / @cemukeshsah
    JOIN US ON
    ✔Instagram: / learningciviltechnology
    ✔Whatsapp: chat.whatsapp.com/KLl7CHaxTMi...
    ✔Facebook: / learningciviltechnology
    ✔Telegram: t.me/LearningCivilTechnology
    ✔Pinterest: / learningciviltechnology
    ✔Email Id for Business Enquiry - civilengineeringofficial@gmail.com
    ✔Linkedin: / civilengineermukeshsah
    In this video, I will explain,
    1. Reinforcement lapping Zone as per IS Code 13920 in Column
    2. What is the reason behind this?
    3. What is Reinforcement Lapping?
    4. What is the function of Reinforcement lapping?
    5. Bending Moment Diagram of Column
    ⓿My Playlist Link
    ✔HOW TO STUDY DRAWING
    • How To Study Drawing
    ✔CIVIL INTERVIEW
    • Interview
    ✔CHECKLIST OF CIVIL WORKS
    • Checklist of Civil Works
    ✔BBS (BAR BENDING SCHEDULE)
    • BBS (Bar Bending Sched...
    ✔QUANTITY ESTIMATE
    • Quantity Estimate
    ✔CONCRETE VOLUME CALCULATION
    • Concrete Volume
    ✔IS CODE LECTURE
    • IS CODE LECTURE
    ✔DREAM HOUSE CONSTRUCTION SERIES
    • DREAM HOUSE CONSTRUCTI...
    ✔HOUSE CONSTRUCTION
    • House Construction
    ✔HOUSE PLAN
    • House Plan
    ✔CIVIL EXPERIMENTS
    • Experiment
    ✔SURVEYING
    • Surveying
    ✔CIVIL ENGINEERING TALK
    • Civil Engineering Talk
    ****************************************************************
    Official Website in English: www.learningtechnologyofficia...
    Official Website in Hindi: www.civilofficial.com
    ****************************************************************
    #CivilEngineerMukeshSah #ReinforcementLappinginColumn #LapinRCCColumn #LappingZoneinColumn ReinforcementLappingZone #CivilEngineeringVideos #LearningTechnology #L&T-LearningTechnology

Комментарии • 208

  • @LearningCivilTechnology
    @LearningCivilTechnology  4 года назад +14

    Video ko Daba ke Share karo bhailog aur apna pyar dikhau.. Taki hamare sabhi bhahiyo, hamare Juniors aur Engineers tak pahuch sake.

    • @manojsuthar5041
      @manojsuthar5041 4 года назад

      Sir plinth beam top se floor beam bottom hight hi length hoga kya

    • @mdshahanshahalam6262
      @mdshahanshahalam6262 3 года назад

      I like ur videos more than other's videos.....

    • @Mahijavre
      @Mahijavre 2 года назад

      Sir middle zone me to bending moment kam hota he na tabbi ties ki spacing ku kam rkhte he

  • @shivamitvlogsnz2416
    @shivamitvlogsnz2416 4 года назад +6

    Also make video on staircase. As most of the people get confused while calculating treads and risers on actual site. Most important is staircase which is starting from some random floor. Which is not in continuation.

  • @SurajKumar-oc3he
    @SurajKumar-oc3he 2 года назад +1

    Sir aapka video dekhne ke bad pura tarah se satisfied ho jata hu bhagwan aap ko aise aur mind ko clear rakhe 👏

  • @abubakarsiddik5033
    @abubakarsiddik5033 3 года назад +1

    Sir I'm form Bangladesh,You are my very good teacher.Your explanation is very good sir.
    Thank you so much,keep your update your video.

  • @UttamSingh-ee5oj
    @UttamSingh-ee5oj 7 месяцев назад +2

    Sir I am Engineer but I can't explain as you explain. Thanks sir 🙏

  • @ziauddin7948
    @ziauddin7948 Год назад +1

    👍👍# good lap zone in column #

  • @phyohtetkoko929
    @phyohtetkoko929 2 года назад +1

    Thanks For Teaching Sir

  • @ShahabUddin-fu5yq
    @ShahabUddin-fu5yq 4 года назад +4

    Also make video on beam and slab for overlapping

  • @saileshsingh1
    @saileshsingh1 4 года назад +1

    Thank you very much for the practical knowledge on Lapping Zone in column.
    It is increasing our knowledge and confident in real time environment in site.
    I have one question regarding column.
    What could be the solution if the length of the reinforcement from isolate foundation is not enough for Lapping which should be provided for second or next story of building ?
    Thank you and Regards!
    Shailesh Singh.
    Nepal

  • @shashikanth3648
    @shashikanth3648 Год назад +1

    Excellent sir

  • @eguru786
    @eguru786 3 года назад +1

    Beam lap also required .
    Thank you soo much.

  • @AKTV_786
    @AKTV_786 Год назад

    #Beam zone required. Beautifully explained.

  • @VeerBuildhouseEngineering
    @VeerBuildhouseEngineering 4 года назад +2

    knowledgeable video sir 👌👍

  • @vinodjoshi1234
    @vinodjoshi1234 Год назад +1

    Mukesh ji I like you for good teachings

  • @raviyadav5
    @raviyadav5 Год назад

    I have downloaded your IS Code app.You have done a fab job brother.

  • @shadabhussain3695
    @shadabhussain3695 3 года назад +1

    Bro ur teaching is damn good
    👍🏻 Keep it up
    Tnx for clearing my concept

  • @mdshoaibhossain360
    @mdshoaibhossain360 2 года назад +1

    u r so good person! ❣️
    Allah bls you

  • @devcpwd
    @devcpwd 2 года назад +1

    Thank you for your support

  • @RajeshKumar-my2ri
    @RajeshKumar-my2ri 21 день назад +1

    Very good video

  • @ashwinanandh7590
    @ashwinanandh7590 4 года назад +1

    Excellent sir.. 👍👍👍🙏🙏🙏🙏

  • @vinodkarle2630
    @vinodkarle2630 4 года назад +1

    अच्छा.व्हिडीओ.धन्यवाद.सर.

  • @krazyharsh5040
    @krazyharsh5040 3 года назад +1

    your explaination is very good

  • @shibnathbanerjee7821
    @shibnathbanerjee7821 2 года назад +1

    Hats of to you sir...

  • @anildas888
    @anildas888 Год назад +1

    Good and informative video. Thanks!

  • @rahulsingha2227
    @rahulsingha2227 3 года назад +1

    Bahat achhaa!

  • @gudiyaali1357
    @gudiyaali1357 Год назад +1

    Good job 👌

  • @sarthakmohapatra3738
    @sarthakmohapatra3738 4 года назад +1

    Superb video sir.
    #Beam and Slab lap zone

  • @-adnanKhaja
    @-adnanKhaja 3 года назад +1

    Thank a lot sir

  • @amitjoshi1872
    @amitjoshi1872 Месяц назад +1

    Absolutely sir

  • @user-cr2np7hn6o
    @user-cr2np7hn6o 3 месяца назад +1

    Thank u sir

  • @arunkumarkarn1995
    @arunkumarkarn1995 4 года назад +1

    NYC videos about lap zone

  • @jackybosko1362
    @jackybosko1362 4 года назад +3

    Thanks for Ur valuable information. I want to know one information, what is the joggle length and its ratio of the lapping bar as per the code reference.

  • @vivekborse2790
    @vivekborse2790 3 года назад

    nice information , take a example of floor to floor ht 4 m , and give detail of lapping and lap length for footing to coloum , and above

  • @b.m.sudhakar6595
    @b.m.sudhakar6595 Год назад +2

    Your my Guruji

  • @mahadevchinchali2843
    @mahadevchinchali2843 3 года назад +1

    Well explained

  • @YogeshLohar93
    @YogeshLohar93 Год назад +2

    Auto level pe video banao sir....

  • @shahabdulhaqim8900
    @shahabdulhaqim8900 4 года назад +1

    PLEASE MAKE A VIDEO ON LEVEL OF. SLAB. ( SLAB ka level kaise check krte hai before casting)

  • @amarkumar-hx8bk
    @amarkumar-hx8bk 4 года назад +2

    Lap joint in beam as per is13920 2016

  • @kalindrasingh5459
    @kalindrasingh5459 3 года назад

    Thank you sir.....ur valuable information.sir i want to know that about bbs.

  • @haidaralikhorejia8984
    @haidaralikhorejia8984 3 года назад +1

    Excellent sir. Please sir still ki quantity nikalna batao. Kaise still ki quantity ko nikale total slab, beam, coloum etc.

  • @success555
    @success555 4 года назад +2

    Very Good Follower Base. Good Luck. #Success555

  • @vykuvicky7573
    @vykuvicky7573 4 года назад

    Sir I have one doubt about feture extension of building we leave 1 height of steel for feture extension but that is not a lap zone.then what we do for that for over come that problem

  • @ajaz545
    @ajaz545 3 года назад +1

    Bhut gazab sir Plz Do some Thing for compitative exam

  • @mdahmed9336
    @mdahmed9336 3 года назад +1

    Very nice👌👌👌

  • @mukeshmani2003
    @mukeshmani2003 4 года назад

    from the edge of the bottom or the top of the slab into the column, what shall be the minimum distance to provide the ties.

  • @shivamitvlogsnz2416
    @shivamitvlogsnz2416 4 года назад +3

    Kindly make a video on accelerator and retarders, plasticizers and superplasticizers

  • @sgpfamilysgpfamily844
    @sgpfamilysgpfamily844 3 года назад

    Sir , now column height is 2.5m and stirrups spacing is 150mm. This data’s are given as per drawing ..L/6 area it has less spacing .I what spacing should use here (L/6)

  • @engrkhalilnaz9019
    @engrkhalilnaz9019 4 года назад +1

    Very nice sir .make vedio also beam ,slab lapping

  • @ShahabUddin-fu5yq
    @ShahabUddin-fu5yq 4 года назад +1

    Plz make a video on importance of primavera p6

  • @er.deepaktewatiya808
    @er.deepaktewatiya808 4 года назад +2

    #beam pl. Sir bnao, and also explain how to decide L lenght of primary & secondary beam at end of beam.

  • @prajayurkude9821
    @prajayurkude9821 3 года назад

    Its very good vidio. Please make vidio on mivan Constructions steel.

  • @ravikirankadam3306
    @ravikirankadam3306 2 года назад

    Sir while calculating L beam depth should minus or not

  • @jitulkalita6579
    @jitulkalita6579 3 года назад

    Sir me assam se hu . mera building me column ka 6 sariya me 4 ko job join kiya tha usme laping kiya baki bij ka 2 me laping kiya nahi .kiya kharab hoga kiya .abhi me groun floor banaya he .

  • @sahiljharia8850
    @sahiljharia8850 Год назад

    In addition to that minimum clear vertical distance between lapped bars shall be 0.25 times lap length. What is this?

  • @arunkumarkarn1995
    @arunkumarkarn1995 4 года назад +1

    Please make videos on RE wall highway

  • @sharadbarman6491
    @sharadbarman6491 3 года назад

    Sir colomn ki clear length beam bottom se Lena hai ya slab bottom se ? Kyoki beam bottom , slab bottom se down hi hoga

  • @babusjohn
    @babusjohn 4 месяца назад

    Hi mukesh... i have a question. Between both the lapping zone how much should be the spacing? I mean 50% rebars to be lapped below centerline and 50%above centerline. Should there be any gap between these staggered bars?

  • @rahulgarg4335
    @rahulgarg4335 4 года назад

    Mukesh ji only column beam junction mai actually minimum numbers of ring set kitne provide krne chahiye as per which is code

  • @shivamitvlogsnz2416
    @shivamitvlogsnz2416 4 года назад +1

    Also make a video on water proofing of terrace. What are the best materials present for it in the market.

    • @LearningCivilTechnology
      @LearningCivilTechnology  4 года назад +1

      already made a video on waterproofing of terrace..few days back... check my videos

    • @shivamitvlogsnz2416
      @shivamitvlogsnz2416 4 года назад

      @@LearningCivilTechnology yeah sure...Great 🙂

    • @javedkhan-eu2sx
      @javedkhan-eu2sx 4 года назад

      Thank you for this video.pls make a video on beam lap required.👍

  • @tarunpigfarm1629
    @tarunpigfarm1629 2 года назад

    Good sagsion

  • @dimpalrana7183
    @dimpalrana7183 4 года назад +1

    Nice sir

  • @ABHISHEKYADAV-oj6zt
    @ABHISHEKYADAV-oj6zt 6 месяцев назад

    # plz tell about cutting length of steel from foundation so that we can avoid zone A for floor height 3mtr..❤

  • @shankarsinghaniya617
    @shankarsinghaniya617 2 года назад

    Hello sir..
    Yaha lap ham upar se jo joint karenge us steel me dena hai ya niche wala me.

  • @firdous529
    @firdous529 4 года назад

    Sir ; Bridge pier or abutment will be same Lapping zone

  • @jaymadhale5666
    @jaymadhale5666 4 года назад

    Sir clear span for lap in column is from beam bottom or slab bottom please tell me from where we take l/4 length please explain sir

  • @adityaghosalkar431
    @adityaghosalkar431 11 месяцев назад +1

    Mukesh tum yaha ho..Mai Kabse dhund rha tha

  • @MADHAVMULTYPRINTHasmukh
    @MADHAVMULTYPRINTHasmukh 3 года назад +1

    Very nice app

  • @gowrinaidu7656
    @gowrinaidu7656 3 года назад

    waterpoofing mixing details at buildings prepare one video sir.....

  • @mohammadshoaib2073
    @mohammadshoaib2073 Год назад

    Column ki laping beam wale porsen me kr sakte h

  • @altafrikarti
    @altafrikarti 3 года назад

    Sir, our engineer has placed lapping zone in column beam junction, already centering is done , waiting for slab,what shall I do now, engineer says it is ok for 2stor house,sir kindly suggest what should I do

  • @mamasconstructiongroup
    @mamasconstructiongroup Год назад

    Slab beam ke Ander column r/f ka lap de sakte h kya

  • @9549549543
    @9549549543 4 года назад

    Agar zone B me bars ko starting karni padi to kya karenge. How it possible with overlap?

  • @owaisulqamar1617
    @owaisulqamar1617 3 года назад

    Sir plz bta dain stagger kB provide krte hai raft me

  • @sapatesantosh0
    @sapatesantosh0 3 года назад

    Lapping lower dia ya higher dia interview Questions?

  • @mkhurshid2961
    @mkhurshid2961 3 года назад

    What happen if the lapping given by welded ? Kindly make a vedio about why engengeers do not let welding any rebar joint in the building design ? Please let me know ! ?

  • @gudiyaali1357
    @gudiyaali1357 Год назад

    Lapping dete hue and bante hue bhi dikhayen field mai taki samjhna asan ho

  • @sanjayswain9763
    @sanjayswain9763 Год назад

    Sir, I want to know that.... Ki sariya ka dia Or quantity saman hona chahiye ya nanhi..... 1000sq building ka sab Callum ka

  • @adityashekhar852
    @adityashekhar852 2 года назад

    Sir splice mai jo ties provide krte hai uska spacing kitna hota hai ???

  • @shaikhssr7417
    @shaikhssr7417 3 года назад

    16mm bar 45d kar k kat diya hun... isku over lapping dene se koi problem hoga????

  • @husnealam7553
    @husnealam7553 4 года назад +2

    #beam zone required

  • @gayathrijayaraman9800
    @gayathrijayaraman9800 4 года назад

    Pls explain abt shear wall bro

  • @sapatesantosh0
    @sapatesantosh0 3 года назад

    What type of joggle,joggle methologi, IS code standard interview Question?

  • @AshokYadav-ov9uy
    @AshokYadav-ov9uy 3 года назад

    Jab ham clear cover ki baat karte hain to beam ya column dono cases me yah clarify Karen ki langitudinal bar ke outer face se clear cover consider Karen ya stirrups/ ties ke outer face se.Thanks

  • @adityatiwari-lv6yb
    @adityatiwari-lv6yb 4 года назад +1

    Beam ke leye bhi video bana degeye

  • @b.m.sudhakar6595
    @b.m.sudhakar6595 Год назад +1

    Beam lap required Sir ji

  • @lakhandas
    @lakhandas 3 года назад

    Total station operation video banaye sir G

  • @shashikanthsanatanikshatri3907
    @shashikanthsanatanikshatri3907 4 года назад

    #parapet part, column extend wat height we should leave for further construction and lapping on it, tag mee bro when u upload

  • @swarnabhushanbagdi8067
    @swarnabhushanbagdi8067 4 года назад +1

    Sir all about pile foundation plzzzz!

  • @jineshkumaarvklm
    @jineshkumaarvklm 3 года назад

    Sir it’s not available in App Store .. I could not find .. pls help

  • @debasisghosh6697
    @debasisghosh6697 4 года назад +2

    Jab column k vertical bar k dia change hota hai tab humko kakha lapping dalna hai?????
    Matlab 2nd floor k bad mera steel k dia change hone wala hai..tab konsi jaiga par lap dalna hai?????

    • @LearningCivilTechnology
      @LearningCivilTechnology  4 года назад

      lap always zone B

    • @debasisghosh6697
      @debasisghosh6697 4 года назад +1

      I know the lap provides always zone B...But
      How it's possible when my dia of bar change in 2nd floor...!!!so how can i extend the bar B zone in 3rd floor...!!!

    • @9549549543
      @9549549543 4 года назад +1

      @@debasisghosh6697 please clear you Quotation I think for example 3rd floor par dia 20 hone wala hai aur 2nd par 25mm hai. To 25mm ka bar 3rd floor par zone B ke center tak jayega. Aap kehna chahte ho ki me steel 3rd floor par 25mm kyon du.

  • @govindsingh8168
    @govindsingh8168 4 года назад +1

    🙏 🇮🇳 👍 😍 #beamlap required

  • @lovedeepsingh1398
    @lovedeepsingh1398 3 года назад +1

    # beam lap explain please sir

  • @skjha1947
    @skjha1947 3 года назад +1

    Sir Column ko jab overlapping krte hai tab L/4 rule ke liye column ka total height ground se count hoga ya floor to slab? Please

  • @rahulc8086
    @rahulc8086 4 года назад

    Please make a video on Beam and shear wall according to IS 13920:2016. IS-13920:2016 is very jumbled and difficult to understand.

  • @hassanhaider9651
    @hassanhaider9651 3 года назад

    Sir please confirm thi, bar dia 25mm hai, uska lap zyada hai, ab lap ka kuch portion plinth beams me ja rha ha, tou kya ye possible hai ke hum uper jo columns uthayengy unko plinth se lap krkey utha len? Please confirm this sir thankyou so much

  • @chetanrana6427
    @chetanrana6427 3 года назад

    G+2 ke liye column, beam or plinth Ka kya size rkhe

  • @oldephart471
    @oldephart471 2 года назад +1

    Any change in lapping zone if couplers are used?

    • @LearningCivilTechnology
      @LearningCivilTechnology  2 года назад

      No

    • @oldephart471
      @oldephart471 2 года назад

      @@LearningCivilTechnology I can't find Section 7.2.3 (in the copy of the IS code I have) to understand transverse reinforcement as mentioned in Fig 12. Please give me a link to the right version of the IS code.

  • @dibyajyotisen4090
    @dibyajyotisen4090 4 года назад +1

    # Beam lap required sir

  • @arimrankhan4270
    @arimrankhan4270 4 года назад +1

    Good sir , Aapne a kaha tha,according to grade of steel and grade of concrete lapping provide karni hy toh wo bhi bataaiye k kounsa grade of steel & concrete se lap kaisa provide karte hy.

  • @aibansharailyngdoh8608
    @aibansharailyngdoh8608 Год назад

    Bro,in lap zone do we used 45D