Mitsubishi VRF | How to fault finding error code 5105

Поделиться
HTML-код
  • Опубликовано: 27 авг 2024
  • Brand : Mitsubishi City Multi
    model : PUHY-P350YHM
    error code : 5105
    Accumulator inlet pipe temperature sensor
    (TH5)fault (outdoor)
    Cause : Thermistor failure
    Check method and remedy: Check Thermistor resistance.
    TH 5 reading around 5K ohm (ambient temperature around 30°c)
    Correction,
    From 4.26 to 4.36 i marking TH4.(wrong marking)
    actually is TH 5.
    sorry for the inconvenience.
    #bonmj #vrf #starmex