Looks a good panel, and well labeled, just two or three points. 1) No spare capacity, should have a bit of space left for expansion. 2) Looks like the control voltage is missing an earth, ie its SELV, when it should be PELV. 3) The bank of terminals on the left at the bottom, the last one needs a cover on it.
Looks a good panel, and well labeled, just two or three points.
1) No spare capacity, should have a bit of space left for expansion.
2) Looks like the control voltage is missing an earth, ie its SELV, when it should be PELV.
3) The bank of terminals on the left at the bottom, the last one needs a cover on it.