# 164 Condenser Water Flow Rate l Condenser GPM Calculation l
HTML-код
- Опубликовано: 4 окт 2024
- This video will explain to you about water-cooled condenser water flow rate calculation.
Chiller water flow rate calculation
• # 163 Chilled Water F...
For HVAC books and other products visit our Amazon Store using the following link
www.amazon.in/...
#girishshinde #airconditioning #hvac
1. Condenser has to reject more heat than that of chiller. This heat includes evaporator refrigeration effect (heat absorbed by the refrigerant in the evaporator) and heat generated due to power input to the compressor for compressing refrigerant (work done by compressor).
2. Total Heat Rejection.
3. 1 TR = 3.517 KW. Divide Total KW by 3.517.
4. Difference between condenser water outlet and inlet.
5. Condenser water flow, GPM = (THR in TR X 24)/Delta T in deg.f
Nice.
Sirji it was a great video . I have a 50 ton ice plant u had visited once with ur students . It was a great experience as i cud also learn few things from u & ur students it wid b a great honour if u wish to visit again. N practically explain karna ho aapke students ko.
Sure Sir I remember that, Your plant is at Taloja Right
@@girishshinde yes taloja
Sir ager hum ny Kisi pump ka flow rate maloom kerna ho to pher bhi yahi farmola lagain gy ??
Informative
1. Condenser hit removiced of total hit produced in evaporater & chiller . this cuse condenser water flow rate is bigger than evapoter water flow rate
2.THR full form is -Total hit rejection
3. TR to KW Rules is- kw/3.516
4.
How to calculate total length of pipe required for an evaporative condenser
Mast
Nice Sir
Sir pump aliment kar video banaye
Nice
Make full course of HVAC and plzz arrange 100 important question for HVAC interview
Ok
Thank you
Good
Thanks
Sir pump alignment par video banao plz with formula plz plz
Girish shinde Sir What if Condenser inlet temperature is greater than atm ambient temp...??
Is condenser and chiller gpm formula is same?
Is 24 is constant for all temperatures
no for delta T 10 degree F
Sabse pahale ye batao bhai 24 kya hai isko bhi batao plz
check full video on condenser and chiller water flow rate
Dr Mr.Girish .
Looking forward for acknowledgement.
Please let me know why the chiller temperature are taken 12-7 or 13 -6 why not the chilled water system is deisshn on bit higher temperatures ... similarities why the condenser water temp condition are.take 32-37 c ...or 33-38 c why such conditions are applied please give an elborative answer. I shall be grateful .
Regards
Saif
Please sir aap ke number do