Redundancy of Valves- It is impossible to identify voting of the valves without checking Fail Action
HTML-код
- Опубликовано: 27 авг 2024
- Redundancy of Valves- It is impossible to identify voting of the valves without checking Fail Action
The same configuration may become 1oo2 or 2oo2 depending on Failure Action of the Valve.
There can be different Configurations:
A. Fail Close and Normally Open Valves:
a) 1oo2: Better Safety
b) 2oo2: Better Availability
Combination of these two configuration provides both better Safety and Better Availability.
B. Fail Open and Normally Close Valves:
a) 1oo2: Better Availability
b) 2oo2: Better Safety
Combination of these two configuration provides both better Safety and Better Availability.
Choose your preferred option based on process condition.
Get Certified as Functional Safety Engineer by opting for this course: www.udemy.com/course/functional-safety-certified-expert-iec-61508-iec-61511/?referralCode=26A69A14ACE514D8D550