HOW TO INSTALL TESLA WALL CHARGER GEN 3 Wall Connector

Поделиться
HTML-код
  • Опубликовано: 1 окт 2024

Комментарии • 65

  • @KevinPon.
    @KevinPon.  4 месяца назад

    #ad USA: Gen 2
    amzn.to/491rdJd
    amzn.to/3IM2CgE
    CANADA: Gen 2
    amzn.to/3PqXLoQ
    Gen 3
    amzn.to/3TJC6dd
    *WIRE*
    6/3 Cable 100ft and less amzn.to/3WWKaul
    200ft cut and less
    RED 6 Gauge Wire: amzn.to/3wLJkWs
    BLACK 6 Gauge Wire: amzn.to/3yv6wc0
    GREEN 6 Gauge Wire: amzn.to/3VaIqwc

  • @jialedai8858
    @jialedai8858 4 месяца назад +2

    Hi! Which wire are you using in the video? 6 AWG wires?

    • @KevinPon.
      @KevinPon.  4 месяца назад

      Hello, yes 6 AWG 🍻

  • @NickWindham
    @NickWindham 5 месяцев назад +3

    Where are all the ranting electricians??
    Good job man!

    • @KevinPon.
      @KevinPon.  5 месяцев назад +1

      Thanks man!!! 🍻🍻

    • @cory8837
      @cory8837 4 месяца назад +1

      Ranting electrician here. That was a beautiful job. The bushing, the extreme care when removing the jacket with a knife, the cardboard to protect the wire when fishing 🤌. You must be an electrician. Just curious why you didn't just use THHN conductors especially since you didn't use the ground in that cable?

    • @KevinPon.
      @KevinPon.  4 месяца назад +2

      @cory8837 thank you very much! I had some extra wire laying around that I'll never use and this was the perfect time 😂

  • @Lucky83...
    @Lucky83... 3 месяца назад +1

    Hi , i like your video . If i have the tesla motel 3 base , is only take 32amp maximum. Is still ok to do the same like you 60 breaker and wire size #6 or is there any problem? Or i have to do with 40 breaker and wire size #8 ? Thank you !

    • @KevinPon.
      @KevinPon.  3 месяца назад

      Yes, it is safe to install 60A breaker with #6. The Tesla will just cap you at 32amp automatically 🍻

    • @Lucky83...
      @Lucky83... 3 месяца назад +1

      @@KevinPon. thank you so much for information

  • @Drucio1
    @Drucio1 3 месяца назад +1

    Whats the purpose of the box? So my panel is in the basement but can run it going straight up and out to the side of the house and that same wall down 20 ft is the garage where im putting the charger inside. The corners going into the house do i put a box?

    • @KevinPon.
      @KevinPon.  3 месяца назад +1

      The purpose of the box is for a 90 degree run through a wall. The junction box makes it the best and easiest option to do so 🍻

  • @tifo-pr5ux
    @tifo-pr5ux 3 месяца назад +1

    Congrats on your fine install. I'm using it as my guide. I can't find a source for that optional bushing and you didn't include one in your parts list.

    • @KevinPon.
      @KevinPon.  3 месяца назад

      Thank you! You can try Home Depot or Lowes. Amazon amzn.to/3X6wKfg

  • @giantinside
    @giantinside Месяц назад

    Does anyone use a torque driver when installing the Gen 3 Tesla wall connector?

  • @neilmartinez143
    @neilmartinez143 Месяц назад

    Thanks. Mine is getting 48A already with 50A breaker and 6awg wiring. Thoughts?

    • @KevinPon.
      @KevinPon.  Месяц назад

      I asked a friend of mine. He has a 50A breaker installed from another person and he's also able to charge at 48A amp but he doesn't and charges at 40A instead. He says the settings can be changed on the app. I assume the charger cannot tell if you have instead a 60A or a 50A breaker. I can't remember correctly but I think the charger is able to detect a 40A breaker and under 🍻

  • @richardhuck8
    @richardhuck8 3 месяца назад

    The wire per code needs to be #6 THHN for a 60 amp 90 deg c continuous load

    • @KevinPon.
      @KevinPon.  3 месяца назад

      In Canada, it is acceptable.

  • @Mangop7q
    @Mangop7q 3 месяца назад +1

    I just installed Tesla wall charger, gen3, and i was able to cjarge my model 3 with 48A, but then, like 15 mins later, my circuit breaker went down, and charging stopped. I turned it on, and it charged again with 48A, but then i lowered it 32A because i just looked at the circuit breaker, and it says 40A.
    Now i have no idea what to do. Please give some advice to me to be able to charge mine with 48A

    • @KevinPon.
      @KevinPon.  3 месяца назад

      @user-gt4qh3dl4n hello there, I do see the problem you're having. First, we want to do this correctly and safely by code. In order to have 48A that requires: all #6 gauge wires and a 60 amp breaker to meet the requirements. If you do not have those two requirements. You will need to upgrade both of them 🍻

    • @Mangop7q
      @Mangop7q 3 месяца назад

      @@KevinPon. no! I made it!!!

    • @Mangop7q
      @Mangop7q 3 месяца назад +1

      @KevinPu0 on. I was able to contact the builder of my unit and confirmed that my unit can handle upto 50A circuit breaker since it has #6 Guage wires installed and he told me that I don't need to follow 80% rule so It's ok to use 48A for my tesla model 3 with 50A circuit breaker and he said the worst scenario would be the circuit breaker will be just tripped.
      As he recommended, I installed siemens gfci 50A circuit breaker, and it cost $139+tax 😲
      Do you really think that I can charge 48A on 50A circuit breaker?

    • @KevinPon.
      @KevinPon.  3 месяца назад

      @user-gt4qh3dl4n this is what I highly recommend you should do. This is what the Tesla manual says to do as well. Install a regular 60A, you will not need a gfci since it has one built in. 60A breaker is very cheap under $40. You will need to double check the wires to make sure they are #6. Do not believe what "she say or he say".
      No I will tell you what will happen if you installed a 50A breaker:
      What are the risks?
      Overheating: The breaker and wiring may overheat, leading to a fire hazard.
      Electrical faults: The breaker may not trip quickly enough to prevent electrical faults, which can cause damage to equipment or even start a fire.
      Reduced breaker lifespan: Running the breaker at or near its maximum capacity can reduce its lifespan and increase the risk of failure.

    • @KevinPon.
      @KevinPon.  3 месяца назад

      @@Mangop7q 80% rule or 125% in USA is electrical code! Safety first. I bet your builder is not an electrician 🍻

  • @1LOVEABRAHAM
    @1LOVEABRAHAM 4 месяца назад

    What size wire did you use, and breaker did you use?

    • @KevinPon.
      @KevinPon.  4 месяца назад

      Did you not watch the video man?
      6 Gauge wire with 60 amp breaker

  • @paulibarra5449
    @paulibarra5449 6 месяцев назад +2

    Nice. But I don't like EV it's danger. To expensive and at the end garbage stuff.
    But it's nice stuff

    • @NickWindham
      @NickWindham 5 месяцев назад +4

      Tesla Model Y Long Range is the favorite I’ve ever had and I’ve had several nice cars. To each their own.

  • @Drunk_in_a_foreign_land
    @Drunk_in_a_foreign_land Месяц назад +1

    This is the cleanest job I have ever seen done by a DIYer. I have a question, I saw some installers run the wires inside the drywall. After installation, there was only the charger outside, and there was no PVC tube underneath. Is it because the wiring needs to pass through the insulation inside the drywall, which increases the difficulty? Or are you worried that the inspection will not be passed? Thanks!

    • @KevinPon.
      @KevinPon.  Месяц назад +1

      @Drunk_in_a_foreign_land thank you very much! There should never be wires expose and should be protected from physical damage. That will fail if it had an inspection. My guess they are not an electrician. If I've done that job I would put a junction box outside and then there will be PVC conduit underneath connecting to the junction box. 🍻🍻

    • @Drunk_in_a_foreign_land
      @Drunk_in_a_foreign_land Месяц назад

      @@KevinPon. Thanks for your reply! My basement main electrical box is directly opposite the garage. Instead of drilling holes to pass the wires through the garage drywall , can I run the wires from the basement to the garage wall first, but without drilling holes, run them up a few feet and then drill holes to get to the charger? In this way, there will be no wires on the garage wall.

    • @KevinPon.
      @KevinPon.  Месяц назад +1

      @@Drunk_in_a_foreign_land I'm trying to picture what you're saying. Is the panel and the garage sharing the same wall?

    • @Drunk_in_a_foreign_land
      @Drunk_in_a_foreign_land Месяц назад +1

      @@KevinPon. It's not the same wall. The difference from your video is that the charger in my house will be installed right above the opening where the wires enter the garage from the basement. So I'm considering if I can run the wires up behind the drywall (garage) then connect to the charger, so that there will be no wire and the pvc pipe outside.

    • @KevinPon.
      @KevinPon.  Месяц назад +1

      @Drunk_in_a_foreign_land oh I see. Yes, you can do that. You'll be able to use an entry point at the back of the Tesla junction box coming in 🍻