Bad ABB ACH550 VFD switch to ACH580
Was doing bearing replacement on supply fan motor. Guess the VFD did not like being off too long decided to end itself before I could start up the motor. Being a prepared tech I already had back up VFD for this unit as I have three of these Older Mcquay units. This ABB also took forever to get at the time when I ordered it last year sometime. Very expensive compared to Dan foss.
#hvac
#abb
#daikin
#vfd
Просмотров: 46

Видео

TEKTON Wrenches!! 🤘🏻
Просмотров 400Год назад
Ordered some new wrenches, tekton is what I’m going with. There having some deals on there website check it out!! www.tekton.com
KAIWEETS WIRE STRIPPERS | REVIEW
Просмотров 170Год назад
These are two Wire strippers from the company Kaiweets. Multi function strippers for electrical use. These can be purchased from these websites. KWS-302 KWS-112 Kaiweets.com amazon links a.co/d/7NZowXW a.co/d/iaOvOzt Aliexpress.com Ebay.com #kaiweets #hvac #hvactechnician #tools #electrical
Carrier RTU EcoBlue Fan Motor Replacement
Просмотров 6 тыс.Год назад
Carrier RTU EcoBlue Fan Motor Replacement
Tech Tip don’t be this guy
Просмотров 176Год назад
Tech Tip don’t be this guy
Copper ain’t like it used to be. Smiley crack on T fitting.
Просмотров 1032 года назад
Copper ain’t like it used to be. Smiley crack on T fitting.
(NAVAC NRDC4M) - RECOVERY MACHINE
Просмотров 1,9 тыс.2 года назад
(NAVAC NRDC4M) - RECOVERY MACHINE
COOLING TOWER DOWN | PUMP MOTOR DISMEMBER
Просмотров 6642 года назад
COOLING TOWER DOWN | PUMP MOTOR DISMEMBER
MILWAUKEE 18V PRO PRESS TOOL IN ACTION
Просмотров 7 тыс.2 года назад
MILWAUKEE 18V PRO PRESS TOOL IN ACTION
VETO PRO PAC (TP-LC) - HVAC REVIEW
Просмотров 19 тыс.2 года назад
VETO PRO PAC (TP-LC) - HVAC REVIEW
AAON RTU-- LEAK REAIR/VACUUM PROCEDURE
Просмотров 3812 года назад
AAON RTU LEAK REAIR/VACUUM PROCEDURE
VETO Pro Pac CT-LC (HVAC REVIEW)
Просмотров 1,7 тыс.2 года назад
VETO Pro Pac CT-LC (HVAC REVIEW)
YASKAWA Z1000 (VFD) FAULT AND OVERVIEW
Просмотров 2,7 тыс.2 года назад
YASKAWA Z1000 (VFD) FAULT AND OVERVIEW
Fieldpiece Vacuum pump Tech Tip
Просмотров 3,9 тыс.2 года назад
Fieldpiece Vacuum pump Tech Tip
COOLING TOWER MAINTENANCE (EVAPCO)
Просмотров 13 тыс.2 года назад
COOLING TOWER MAINTENANCE (EVAPCO)
KLEIN TOOLS 7 IN 1 IMPACT FLIP SOCKET (HVAC FIELD REVIEW)
Просмотров 1,5 тыс.2 года назад
KLEIN TOOLS 7 IN 1 IMPACT FLIP SOCKET (HVAC FIELD REVIEW)
BALDOR MOTOR BEARING CURSE
Просмотров 1,4 тыс.2 года назад
BALDOR MOTOR BEARING CURSE
LOCHINVAR BOILER NOT FIRING UP MULTI ISSUES
Просмотров 7 тыс.2 года назад
LOCHINVAR BOILER NOT FIRING UP MULTI ISSUES
COOLING TOWER WOBBLE OF DEATH
Просмотров 1602 года назад
COOLING TOWER WOBBLE OF DEATH
FIELDPIECE VPX7 OVERVIEW (PT 2)
Просмотров 9 тыс.3 года назад
FIELDPIECE VPX7 OVERVIEW (PT 2)
CARRIER COMPRESSOR REPLACEMENT (MINI SPLIT)
Просмотров 7283 года назад
CARRIER COMPRESSOR REPLACEMENT (MINI SPLIT)
ASPEN Maxi Orange mini Condensate Pump Install
Просмотров 17 тыс.3 года назад
ASPEN Maxi Orange mini Condensate Pump Install
Armstrong Series-4280 Pump Seal Repair
Просмотров 7 тыс.3 года назад
Armstrong Series-4280 Pump Seal Repair
BOILER MAINTENANCE
Просмотров 2,5 тыс.3 года назад
BOILER MAINTENANCE
Building Automation Sensor Install (C02 & RH%)
Просмотров 3033 года назад
Building Automation Sensor Install (C02 & RH%)
Blank Tstat! Too easy of a call & Mass Grave Of Transformers Plus More!
Просмотров 603 года назад
Blank Tstat! Too easy of a call & Mass Grave Of Transformers Plus More!
FIELDPIECE VPX7 VACUUM PUMP OVERLOOK!
Просмотров 4,8 тыс.3 года назад
FIELDPIECE VPX7 VACUUM PUMP OVERLOOK!
Japanese Hand Tools!
Просмотров 3 тыс.3 года назад
Japanese Hand Tools!
THE MEG! ( Fluke 1507) insulation meter in the field use and review HVAC
Просмотров 29 тыс.3 года назад
THE MEG! ( Fluke 1507) insulation meter in the field use and review HVAC
Compressor Contactors Getting Crustified
Просмотров 1203 года назад
Compressor Contactors Getting Crustified

Комментарии

  • @jasonjohnsonHVAC
    @jasonjohnsonHVAC День назад

    580's are nice. No more dipswitches for voltage or current. Easy to read display. Also doing a motor ID check is a great feature. The drive will "tune" itself to the motor installed

    • @hvacslayer2929
      @hvacslayer2929 День назад

      @@jasonjohnsonHVAC right first thing I looked for them dips that will definitely put you in a ghost chase if you forget those or jumpers on certain spots. This same building for the boiler we did another abb ach over to 580 with eclipse bypass and we got stuck for a moment, our controls guy was arguing with Abb tech support over a parameter and a fault 😂 fun times. You’re up early dude 🤙🏻

  • @TheJimmy5454
    @TheJimmy5454 Месяц назад

    What HP is that motor?

  • @Itsjustciah
    @Itsjustciah Месяц назад

    So In my case the plug burned up somehow and I was thinking about bypassing getting a new motor and just wire but the wiring together. Can I do that or no?

    • @hvacslayer2929
      @hvacslayer2929 Месяц назад

      @@Itsjustciah that will work just make sure you wire correctly. Since you’re going to cut the plugs off I would cut back a bit on the plug coming from the line/controls. That way when you get a new motor you can reuse the plug.

    • @hvacslayer2929
      @hvacslayer2929 Месяц назад

      @@Itsjustciah the plugs are just fancy/expensive wire splice. 😂

    • @Itsjustciah
      @Itsjustciah Месяц назад

      @ somebody told me if I do that it can burn the board up. Is that true?

    • @Itsjustciah
      @Itsjustciah Месяц назад

      @@hvacslayer2929 well i think the motor is fine I hadn’t confirmed why the plug burned up but I was attempting to save money by just eliminating the plug and just wiring the wires together

    • @hvacslayer2929
      @hvacslayer2929 Месяц назад

      @@Itsjustciah probably lose connection inside the plug on the high voltage side. The plug connection is just that it’s completing the wires together. The board sends signal to the motor to control speed.

  • @char0507
    @char0507 Месяц назад

    Really good video

  • @jasonjohnsonHVAC
    @jasonjohnsonHVAC Месяц назад

    Great vacuum

  • @xraybravo7180
    @xraybravo7180 2 месяца назад

    What about klien et600 goes for 180$

  • @salvadorgutierrez4474
    @salvadorgutierrez4474 3 месяца назад

    SNOOP wasn't invited to the party? Its my go to for micro leaks.

    • @hvacslayer2929
      @hvacslayer2929 3 месяца назад

      @@salvadorgutierrez4474 I’ve shown snoop in some of my other vids! Yeah I don’t know why I didn’t have snoop involved crap.

  • @zackdepalma6184
    @zackdepalma6184 3 месяца назад

    Belt driven is way better with blower

    • @hvacslayer2929
      @hvacslayer2929 3 месяца назад

      @@zackdepalma6184 agreed 👍🏻

    • @musicnerd72
      @musicnerd72 25 дней назад

      ​@@hvacslayer2929 I agree as well. These sound louder and seem to break down more often.

  • @marcoantonioochoa5332
    @marcoantonioochoa5332 3 месяца назад

    Thanks

  • @mariodiaz6438
    @mariodiaz6438 3 месяца назад

    When vacuum a new recovery tank the ballast valve should be open or close

    • @hvacslayer2929
      @hvacslayer2929 3 месяца назад

      @@mariodiaz6438 have it closed unless the tank has been exposed to moisture which it shouldn’t.

  • @kevinpearce3281
    @kevinpearce3281 3 месяца назад

    Can I just leave the gas ballast closed

    • @hvacslayer2929
      @hvacslayer2929 3 месяца назад

      @@kevinpearce3281 yes but the gas ballast will help on initial start up of moisture removal. I run it open until about 5k then close it.

  • @1_Dantheman_1
    @1_Dantheman_1 4 месяца назад

    Those A2L compatible?? Awesome btw!

    • @hvacslayer2929
      @hvacslayer2929 3 месяца назад

      @@1_Dantheman_1 Yes they are A2L comp. Thanks for watching 🤘🏻

  • @TheCherokeeKidd
    @TheCherokeeKidd 4 месяца назад

    You’re right we all carry about the same tools in the same tool bags/boxes 😂. Great video 👍🏼

  • @dolwhinhooks8059
    @dolwhinhooks8059 4 месяца назад

    Where can I get this gear from?!

    • @hvacslayer2929
      @hvacslayer2929 4 месяца назад

      @@dolwhinhooks8059 from there website. They have an merch category on the site.

  • @WhereDaToofpaste
    @WhereDaToofpaste 5 месяцев назад

    AccuTrak is great for certain conditions but isn’t considered a replacement for electronic leak detector because of how it interacts with fluorescent lights and MRI machines and many other devices that cause high frequency interference (including some VFD’s). There is a similar device made by Amprobe with enhanced sensitivity ranges that supposedly filter out high frequency disturbances but I’ve never known anyone who has used one to hear first hand how well it works in the field like I have the former. H10 pro maintenance tune up kit is over $500 from United Refrigeration (my area cost) and the battery which goes bad after a few years is over $150. That’s nearly the cost of the whole unit. Factoring in how long it takes to dial in and the fact you are tethered to a short pen which prevents you from getting back into tight spaces I’d steer anyone I can away from buying one without at least considering those things first. Having said that I found leaks with mine that weren’t possible with anything else that was around at the time that I was aware of and had access to. Just bought the Infinicon D Tek Stratus and the extra few hundred dollars was well worth the money so far. Its pinpointing capabilities are better than the H10 Pro and ease of use is far less finicky in my opinion. My two cents. Hope this helps.

    • @hvacslayer2929
      @hvacslayer2929 5 месяцев назад

      I’ll have to look into that amprobe instrument. Yeah i try telling people who never used an ultrasonic that you need to have it completely silenced with no electrical noise going on or your gonna hard time. lol just ordered a new sensor for my H10. My battery has been bad for awhile I have to leave it plugged in. I see mixed reviews on the stratus. Hvac guy on RUclips had issues with it. NorCal Dave doesn’t like it as well. I mean everybody will have different opinions of course, but hvac guys unit wouldn’t work and kept having issues with his.

    • @Talentman18
      @Talentman18 3 месяца назад

      Accutrak or DTek which one is better

  • @KarenBeisler-g5k
    @KarenBeisler-g5k 5 месяцев назад

    Does anybody know how to set the heating and cooling setpoints on these units? Our main room is freezing and I cannot figure out why.

    • @hvacslayer2929
      @hvacslayer2929 5 месяцев назад

      You’d have to give bit more info. But you should be able to adjust the set points through the hand held tool if you do not have prizm software

    • @KarenBeisler-g5k
      @KarenBeisler-g5k 5 месяцев назад

      @@hvacslayer2929 we have an AAON Unit RN-011-08-0-EA09-3FB 11T Roof top unit. The reset source is space temperature and the cooling mode enable setpoint is 74, the heating setpoint is 71. sat coolingSAT COOLING high reset source is 80, low reset source is 70, cooling staging window is 5, mod cooling window is 10,SAT SETPOINT OR LOW SAT LIMIT FOR RESET IS 50, SAT High Reset limit is 60, mechanical cooling oat lockout is 35, low cut off temp is 40 SAT HEATING - high reset source is 80, low reset source is 60, heat staging window is 5, mod heating window is 10, Low SAT Limit reset is 90 heating OAT lockout is 90, high temp cutoff is 150. The room that uses this unit has a 25foot ceiling and 80 feet long. Yesterday the temperature of that room was 68 degrees. i tried to use the control unit to increase the temp, but no luck - room would not increase temp. It was showing that the heat was on. It was 80degrees outside but I didnt think the outside temperature made a difference since the reset source is space temp. I am happy to send you pictures of all the settings. this is driving me nuts!

  • @RafaelRodriguez-wc6zi
    @RafaelRodriguez-wc6zi 5 месяцев назад

    Just got the same ones still trying them out they seem okay

    • @hvacslayer2929
      @hvacslayer2929 5 месяцев назад

      These ones got stolen. I ended up getting another set. So far I like them. 👍🏻

    • @RafaelRodriguez-wc6zi
      @RafaelRodriguez-wc6zi 5 месяцев назад

      @@hvacslayer2929 ooh. Noooo let me guess u left them at the job site?

    • @hvacslayer2929
      @hvacslayer2929 5 месяцев назад

      @@RafaelRodriguez-wc6zi worse my van got broken into they got my backpack that had my gauges and hoses in.

    • @JCN2000
      @JCN2000 4 месяца назад

      For me they give me false readings. Says my head is way lower than it really is. Not sure why

    • @hvacslayer2929
      @hvacslayer2929 4 месяца назад

      @@JCN2000 weird. But your suction is fine?

  • @tarpontime7562
    @tarpontime7562 5 месяцев назад

    You can just put an 1/4 adapter on that 3/8 inlet.

  • @kratosdgo
    @kratosdgo 5 месяцев назад

    Thank you so much

  • @UnHinged_Pools-N-Stuff
    @UnHinged_Pools-N-Stuff 5 месяцев назад

    Me likey regular channel locks dont have thet comfort feeling🎉🎉

  • @houston4380
    @houston4380 5 месяцев назад

    No way! You turned something! Im blown away dude!

  • @edlauren9434
    @edlauren9434 6 месяцев назад

    I am replacing one of these motors tomorrow . It’s ICP 6 ton gas package. Looks 100% the save. That motor lasted 7 weeks ONLY! It’s under warranty, however that motor s ~$1200 (!!!!!) at United Refrigeration! So, I am not sure if I want to install these units for my customers in a future.

    • @hvacslayer2929
      @hvacslayer2929 6 месяцев назад

      I’m constantly seeing/hearing these motors going down. One of the things to look for is static pressure I believe these are very picky on static pressure.

    • @edlauren9434
      @edlauren9434 6 месяцев назад

      Well, this particular RTU just got the entire ducts re-done. It was VERY deficient air ducts set up. It was ~800 CFM on the return side…. For a 6 ton unit!!!!! That Sudway restaurant was always sweating. So, I’ve got the entire system done correctly with ~3000 CFM on the return and ~2500 CFM for the supplies. It started to cool… ran happy for 2 days and… that damn motor just quit!

    • @hvacslayer2929
      @hvacslayer2929 6 месяцев назад

      @@edlauren9434 right so now it’s running correctly and set to correct static for the motor. I also read issues with the high temp limit on the indoor section believe that was a recall on select years. And an issue regarding voltage with the plug.

    • @hvacslayer2929
      @hvacslayer2929 6 месяцев назад

      Wswrefrigeration mentioned it in the comments on this video below.

  • @22832gib
    @22832gib 6 месяцев назад

    where did you get the bearing?

    • @hvacslayer2929
      @hvacslayer2929 6 месяцев назад

      Any motor/pump shop would carry them. Just give them the bearing numbers.

  • @ALLANAVILAESCRITOR
    @ALLANAVILAESCRITOR 6 месяцев назад

    Hello i have a problem with my heater, he makes the process , but drops a failure: lockout gas valve fail 1. I change the valve but continuos the failure.

    • @hvacslayer2929
      @hvacslayer2929 6 месяцев назад

      Are you getting the correct gas pressure to valve? How’s the system determine flame prove? Flame rod or HSI? You’ll need to check micro amps. If you are getting flame and high micro amp reading than it sounds like loose wiring issue ignition module/board issue. If there’s a peep hole look though it upon lighting to see if your getting a flame.

  • @dankoohns6582
    @dankoohns6582 6 месяцев назад

    Good taste in music. Hailz!

  • @CaityBlue
    @CaityBlue 7 месяцев назад

    Thank you I genuinely would have never found this thing if not for this video

  • @strivinghigher7005
    @strivinghigher7005 7 месяцев назад

    Thanks for the demonstration, I've got to replace one of these later this week

    • @hvacslayer2929
      @hvacslayer2929 7 месяцев назад

      Glad to help 🤘🏻

    • @edlauren9434
      @edlauren9434 6 месяцев назад

      Was that motor on a pretty new RTU? I am replacing one today. The unit is 1.5 months old.

    • @strivinghigher7005
      @strivinghigher7005 6 месяцев назад

      @@edlauren9434 I think it was 5 years old

  • @luckystrike240
    @luckystrike240 8 месяцев назад

    Good video & 👍 linking tom lech

  • @mope72ful
    @mope72ful 8 месяцев назад

    ruclips.net/video/tNRWkz0NHXA/видео.htmlsi=j7D1Mc5lQFAxx-Ev

  • @mope72ful
    @mope72ful 8 месяцев назад

    ruclips.net/video/HL1iEcOEcns/видео.htmlfeature=shared

  • @yorkrojas1452
    @yorkrojas1452 8 месяцев назад

    Somg and band name

    • @hvacslayer2929
      @hvacslayer2929 8 месяцев назад

      Band is Himsa Song- nights like these that keep us alive

  • @garypoplin4599
    @garypoplin4599 8 месяцев назад

    Please make another video with your microphone inside the head set! I was glad to find this video reviewing the Accutrak Ultrasonic Leak Detector; but, it turned out to be a complete disappointment. I was hoping to actually hear what a leak sounds like with this tool and not just a verbal description of the sound. All I ever hear from this device is the radio squealing you describe here no mater where in the room it is positioned (even near a known leak!) Thanks for getting my hopes up. I returned this tool to the supplier because I thought it was defective. The one they sent to replace it sounds exactly the same way. I paid a lot of money for this unit so I look forward to learning what I’m supposed to be hearing in your next video about this tool. Thanks for the effort.

    • @hvacslayer2929
      @hvacslayer2929 8 месяцев назад

      If you are hearing squealing than you have the sensitivity set to high. I don’t wear a mic, I use a go pro or my iPhone and whateve those pick up it that’s what it gets. I don’t have time to get into detail on editing and using a mic I just go and film. The video was more a comparison from the other leak detection methods. I mentioned these are so sensitive if you are near high voltage it will pick it up or any of radio interference. To get a true idea of a leak make a tiny hole on a Schrader cap and have it on a refer tank valve, slightly open it and use the ultra to go near it listening you’ll definitely hear what it’s suppose to sound like. Then spray some soap on it so you hear what it sounds like wet. There is other videos on RUclips that demonstrate the noise from these tools. I know Shannon knight has one hooked up to a speaker so you can hear it. Hope this puts gives you some confidence in learning how to use it. Also key is using good pair of isolation headphones if you are using the crappy Walkman style ones that came with it well you already lost the battle. I use skullcandy crusher headphones with extra cushion ear pads.

  • @jasonjohnsonHVAC
    @jasonjohnsonHVAC 8 месяцев назад

    That's called a mechanical seal. Great video

  • @boywhohadatiger
    @boywhohadatiger 8 месяцев назад

    Do different headphones make it work better ? I have hard time finding leaks with mine tbh uncles they are very obvious

    • @hvacslayer2929
      @hvacslayer2929 8 месяцев назад

      Well it’s all about listening and the feedback being sent back to the headphones. The original headphones were terrible like some Walkman headphones. I had a spare pare or skull candy crushers that I use they Isolate noise somewhat but the sound is Crystal clear. If you get the higher accutrak model it comes with better headphones they look noise canceling.

    • @luckystrike240
      @luckystrike240 8 месяцев назад

      I've heard misting the area with water will give better feedback to help pinpoint the leak but I have not done it.

  • @beefing313
    @beefing313 8 месяцев назад

    😂

  • @davidperry4013
    @davidperry4013 9 месяцев назад

    The Ecoblue blowers are pretty cool but, I prefer the direct-drive squirrel cage with a Fasco or Marathon ECM motor.

    • @hvacslayer2929
      @hvacslayer2929 9 месяцев назад

      I agree with you Mate!

    • @edlauren9434
      @edlauren9434 6 месяцев назад

      100% with you! I love to be able to repair my equipment without ordering these OEM only very special and crazy expensive parts. One my customer is running the restaurant with no A/C (1.5 month old RTU) and that damn blower motor has to be shipped from the factory.. So, no A/C at that restaurant for 4-5 days…. At Memphis… with 97F outside….

  • @bikechannel4931
    @bikechannel4931 9 месяцев назад

    Swearing is necessary?

  • @williamgreenwood2009
    @williamgreenwood2009 9 месяцев назад

    How do I purchase the program?

    • @hvacslayer2929
      @hvacslayer2929 9 месяцев назад

      I’ve seen them on eBay actually. Or online supply house. I obtained mine through aaon rep in my area.

  • @joejunion6934
    @joejunion6934 10 месяцев назад

    Is the motor on a VFD (Variable Frequency Drive)? I feel the bearing problem is most likely a result of shaft voltage. The approach is to cut the bearing apart and look for shaft voltage and possible fluting. You could start with popping the old bearing shields and looking at the grease inside. If it is discolored that is the first sign of micro arcing caused by the shaft voltage. The voltage on the shaft sparks across the grease film inside the bearing. There are many grounding brush solutions available to prevent bearing damage from shaft voltage. Another additional protection measure would be to install ceramic ball bearings which insulate and break the electrical path through the bearings. I am a Reliability Specialist for the largest Midwest Electric Motor Repair Shop Company, I fix problems like this daily.

    • @hvacslayer2929
      @hvacslayer2929 10 месяцев назад

      I’ve heard of this happening. When I replace OG motors I end up getting new motors that come with the ring grounding kits installed already. There’s also a product out that look like current donuts but instead they help prevent arc from VFD’s. My thing is I have original motors that are close to 20 years old on VFD’s they are still rocking. But anything coming out from the last 5 years seems like pure trash does not last.

  • @bigdaddy4975
    @bigdaddy4975 10 месяцев назад

    You don’t run it like that right? Is it leaking when it’s off?

    • @hvacslayer2929
      @hvacslayer2929 10 месяцев назад

      No you take the cap off when running it. While moving it around some residual oil would leak out that’s why I cap it.

    • @bigdaddy4975
      @bigdaddy4975 10 месяцев назад

      @@hvacslayer2929 okay I get it now

  • @diegoavina8435
    @diegoavina8435 10 месяцев назад

    Does it throw a lot of steam threw the exhaust

  • @FIREBIRDC9
    @FIREBIRDC9 10 месяцев назад

    Going in April , i have also pre-selected , can't wait!

    • @hvacslayer2929
      @hvacslayer2929 10 месяцев назад

      HCAR and the Czech scorpion are my favorites. That HCAR will rattle your face very intense blast wave as well.

  • @juancastro6812
    @juancastro6812 10 месяцев назад

    I had another pump where they sent me the spacer that goes on the motor shaft, I am assuming you don't need to change the spacer?

    • @antoinesmith3983
      @antoinesmith3983 3 месяца назад

      Only if it's damaged or cracked otherwise sand it and get it back together, keep the new sleeve for another motor incase

  • @mauriciovizcarraguajardo9262
    @mauriciovizcarraguajardo9262 11 месяцев назад

    Q buen tema colega!

  • @octaviomenesesrueda
    @octaviomenesesrueda 11 месяцев назад

    NICE. THANKS.

  • @speculatorfaecum6938
    @speculatorfaecum6938 Год назад

    Has anyone ever told you that you sound like Kermit the frog?

  • @afbigfish1
    @afbigfish1 Год назад

    I might be crazy but I expected it to pull down way faster than that especially with the trublu hose. Looks like you are using the legacy fittings on the trublu they have newer high flow ones now that are less restrictive and machined out of one piece.

  • @davebrunson125
    @davebrunson125 Год назад

    That Accutrak is a cheap piece of junk. I love ultrasonic but that one is junk. Break down and buy a nice one. It need wide frequency adjustment to cancel out different ultrasonic sounds. You should be able to hear a leak that big from 10-15 ft and hone in on it in seconds. I do know Accutrak makes one that cost around $5K it maybe better. I know my Fisher will blow that thing out the water. You can complain about the price but a good one will find a huge leak like that 10X faster with more accuracy

  • @aaronmcclain1279
    @aaronmcclain1279 Год назад

    Did you ever change the from the compact to 6-1 Milwaukee fastback.

    • @hvacslayer2929
      @hvacslayer2929 Год назад

      I’m still rocking my OG fastback but I’m intrigued by that 6-1 I’ll probably end up getting it sometime soon here. 🤘🏻