Is it the(faulty) Filter Pcb output voltage to Inverter Pcb is incomplete, then causing Inverter Pcb fail to work and no DC voltage output to DC fan Pcb right ?
@@BonMj I have a doubt sir how to find faulty Standard comp-1 & Standard comp-2 at VRV-3 total 03 No's of compressor have (01 inverter comp,02 standard comp )
Good Job!
Work the clouds 34.
😎🇧🇷
Thanks
Change the whole pcb and u good
i think inverter pcb bcoz bcos fan pcb power supply from inveter pcb if im correct .usually i change both pcb
sir, how much is the normal refrigerant pressure for the ac vrv ?
You Must change the Inverter PCB because the middle phase of the noice filter whaits confirmation from the inverter pcb to close the cycle.
👍
Replace both filter and fan PCB.. that should do the trick
Is it the(faulty) Filter Pcb output voltage to Inverter Pcb is incomplete, then causing Inverter Pcb fail to work and no DC voltage output to DC fan Pcb right ?
👍
So this is which PCB faulty
Noise filter PCB,& inverter pcb
Thanks
👍🧿
Thanks
How much chaker
Is faulty filter pcb ?
Yes
@@BonMj I have a doubt sir how to find faulty Standard comp-1 & Standard comp-2 at VRV-3 total 03 No's of compressor have (01 inverter comp,02 standard comp )
Inveat the standard compressor setting no 2, 19
I think inverter pcb. Cz i was found error LC/L5. Then i replace it and done
Thanks
Thanks
Same problem Right now sir
OUTDOOR Model no. RKH50SRV16 DAIKIN INVERTER SPLIT TELL ME DISCHARGE THERMISTOR VALUE AT 32°
Hi Bon can can I reach you on a personal contact?
I think inverter PCB
Thanks
Noise filter Pcb
Thanks
1500 error code mitsubishi? Vrf
May overcharge
ok thanks .i no charging gas.
Th4 thermistor 114 koms its ok ?
Filter PCB
Thanks
Filter pcb then check
Thanks
Replace Filter PCB, Inverter PCB and Compressor. Compressor likely damaged.
Thanks
Thanks
Hello. how to fix UC error code daikin vrv 3.