How we can avoid low power factor issue during solar panel installation ? | लो पावर फैक्टर की समस्या

Поделиться
HTML-код
  • Опубликовано: 4 фев 2025

Комментарии • 91

  • @syedaimal253
    @syedaimal253 20 дней назад

    Very good ma esee maslay ma pans gaya ta app na bohat achay sa samjaya aur hamara kamm bee teek hogaya

  • @002det-lanujkumar5
    @002det-lanujkumar5 2 дня назад

    Perfect video for the solar & gread system pf management

  • @vijaytsakhare
    @vijaytsakhare 2 года назад +2

    I am facing power factor problem after installation of solar system. I got perfect solution through this viedeo. Thanks...

  • @velmuruganperumal5322
    @velmuruganperumal5322 3 месяца назад

    Well and systematically explained. Good job and keep up to benefit engineering communities. Let God give all the well being to you to continue on this path.

  • @sunnysoni8208
    @sunnysoni8208 Год назад +2

    Great 👍

  • @pankajnagar3600
    @pankajnagar3600 2 года назад +1

    Very interesting video

  • @nirmalsinghmann
    @nirmalsinghmann Год назад +1

    very infomative video bro.thanx for explain in details.

  • @BhagyeshAutomotives
    @BhagyeshAutomotives 10 месяцев назад

    you have just earned a subscriber. Very informative video with perfect explanation. Thank you so much !!

  • @sujitmalli300
    @sujitmalli300 Год назад +1

    Thanks Ramanji for sharing such a usefull information.

  • @alearner2020
    @alearner2020 Месяц назад

    Excellent 👍👍👍

  • @sunilminotra1462
    @sunilminotra1462 11 месяцев назад

    Thanks for valuable jankari di 🙏👌👍

  • @yashwantverma4511
    @yashwantverma4511 2 года назад +1

    Very useful information

    • @solarfacts4242
      @solarfacts4242  2 года назад

      Thanks 🙏
      Please share with your friends

  • @saisantosh341
    @saisantosh341 2 года назад

    VERY VERY INFORMATIVE RAMAN JI

  • @rakeshchoure6272
    @rakeshchoure6272 2 года назад +1

    Good teaching style and explanation...

  • @gniraj8501
    @gniraj8501 2 года назад

    Very informative video ramanji, keep on making such a core technical informative video, we will keep on watching your video👍

  • @maheshkachare7375
    @maheshkachare7375 10 месяцев назад

    Really Good information Sir Thank You ❤

  • @user-hr4xs8ne3m
    @user-hr4xs8ne3m 2 месяца назад

    Do reactive power control option in delta solar inverter works for pf correction?

  • @rakeshchoure6272
    @rakeshchoure6272 2 года назад +1

    Thank you sir.

    • @solarfacts4242
      @solarfacts4242  2 года назад

      Thank you 🙏
      Please share with your friends

  • @muhammadusman8606
    @muhammadusman8606 6 месяцев назад

    Can we change the inverter setting to improve this?

  • @RamodayaBaragur
    @RamodayaBaragur 2 месяца назад

    You are explaning like a technician. It will more effective if you explain as a Electrical engineer

  • @Velabadsha
    @Velabadsha Месяц назад

    Assalam o Alaikum sir Kiya solar ke sath power factor capistor on hote h

  • @harshakotha6927
    @harshakotha6927 25 дней назад

    We installed a solar plant for our industry. However, right from the beginning I was not confident about the position of our APFC panel. My questions were answered after watching this video.
    Thank you
    Can you please suggest the source (book) from which we can know more about the position of APFC panel in an industry with solar

  • @saimmukhtarhussain5060
    @saimmukhtarhussain5060 7 дней назад

    Hi dear. We are facing errors of "system fault" on our inverter whenever our capacitor bank for power factor controlling operate the relays of capacitors. Due to this error we are facing multiple dips and power loss from our solar generation plus it is very unwell for the inverter aswell. We have also set the PF value to .95 in inverter in order to rectify the problem but the system fault is occurring every now and then. Please guide in this regard.

  • @manoj0goyal
    @manoj0goyal 11 месяцев назад

    Can you please tell me , is it possible to connect two different make invertors with different load capacity in tqi different phases in 3 phase connection??

  • @sunilminotra1462
    @sunilminotra1462 11 месяцев назад

    Please tell us 5 kw 3 phase abhi lagwan hai kaya APFC panel residence may lagwana kaa faida hai please guide me

  • @Haldwani123-qz5rq
    @Haldwani123-qz5rq 10 месяцев назад

    Hello sir, main ek ZED cum DG sync solar plant lagana chata hu, but termination point kaha pe kare , jisme plant Grid or DG dono se operate ho. Aur power factor ki upor koi effect nehi ayi

  • @sunbeamedsavingsbysimer4483
    @sunbeamedsavingsbysimer4483 2 года назад +3

    A very informative video once again Raman
    Please explain how did you assume the value of Reactive power in this example
    Also generally the PF is indicated on the existing electricity bills, one can calculate the Reactive power working backwards , however the Active power should be variable as the load requirements vary throughout the day , then is the MDI to be taken as the value of Active power to do the calculations

    • @solarfacts4242
      @solarfacts4242  2 года назад

      These values i have taken for the calculation only

    • @learnandcreation3744
      @learnandcreation3744 Год назад

      ​@@solarfacts4242I thought the same because the variable is only active power, KVar is fixed so the angle would not be as per 22.9KVar in your example.

  • @muhammadzaman8462
    @muhammadzaman8462 Год назад

    My question is that in big projects like 500kw ,should we install dc breaker with dc spd on string ,it is necessary or not please explain it,if yes and if not

  • @arupghosh3505
    @arupghosh3505 2 года назад

    Perfect

  • @rajeshparmar6944
    @rajeshparmar6944 8 месяцев назад

    Hi thx a lot it was great in depth explanation however one doubt is @ power consumed by Inverter. Can you pl address same also thx n regards
    Rajesh

  • @rajatgoyal7821
    @rajatgoyal7821 Год назад +1

    Raman Ji if the MDI has not fallen much after solar installation but the PF has come down from 0.99 to 0.54 will the APFC work in controlling as per the termination method u suggest. Earlier the industry has been using capacitors to maintain PF constant at 0.99. No APFC was their.

    • @solarfacts4242
      @solarfacts4242  Год назад

      In this case you have to check will your APFC panel is working proper or not

  • @93_52
    @93_52 9 месяцев назад

    Please discuss on leading power factor in this case sir

  • @wycliffemwangi3197
    @wycliffemwangi3197 2 года назад +1

    This is a nice tutorial..Please put in in English Subtitles

  • @mohamadsafwan4575
    @mohamadsafwan4575 2 года назад

    Thanks................

  • @shivsamratsingh
    @shivsamratsingh 3 месяца назад

    Sir please make a video BESS project

  • @mahtabalam-sy2eb
    @mahtabalam-sy2eb 10 месяцев назад

    How much distance between solar input from load panel

  • @AkhtarJan-q6y
    @AkhtarJan-q6y Год назад

    Kiya 50kva ke transformer 60kw solar system lagsata hai

  • @CricTalk
    @CricTalk 2 года назад +1

    Sir, our solar panel meter show 0.99f but in main meter of grid distribution occur of pf show 088 pf. Sir, will there be solution if we connect solar system before apfc panel ?

    • @solarfacts4242
      @solarfacts4242  2 года назад

      if you terminate solar plant output before APFC you will get the resolution

    • @learnandcreation3744
      @learnandcreation3744 Год назад

      ​@@solarfacts4242I think location B will be good. Because the power factor panel shows the resultant angle of net 40kW and 32.9KVar (fixed).

  • @karanrai4448
    @karanrai4448 2 года назад +1

    Agar m point a or point b pr apfc se ct lga du toh woh sahi load sense krega ??

    • @solarfacts4242
      @solarfacts4242  Год назад

      You can do only you have to see your load sensing should be ok

  • @CuongBeoDay
    @CuongBeoDay 6 месяцев назад

    I am also very concerned about this issue. Do you have English documents?

  • @bisharatahmad258
    @bisharatahmad258 4 месяца назад

    Hy sir I'm bsharat Ahmed form Pakistan

  • @hamxa_says
    @hamxa_says 2 года назад +1

    A scenario me 32.9Kvar kahan se lekr load ko supply kryga ? jab grid se requirement 0 hogayi tw

  • @naveenvignesh90
    @naveenvignesh90 2 года назад +1

    Is APFC panel needed even if we install bidirectional net metering sir ?

    • @solarfacts4242
      @solarfacts4242  2 года назад

      Yes

    • @naveenvignesh90
      @naveenvignesh90 2 года назад

      @@solarfacts4242 ok sir. Thank you for your quick response sir... We installed solar in our industry and bidirectional meter not yet installed by EB. We don't have APFC... We have installed capacitors by individual loads. So PF is affected while running in solar power. I thought installing a bidirectional meter would solve this issue...

  • @ssgaindhar
    @ssgaindhar 11 месяцев назад

    we have an installation of 15kw GTI , when GTI is connected the PF goes down to 0.6 in EB meter , when it is removed /disconnected , PF goes above 0.95 .APFC panel is not installed at site . Kindly Suggest how can we solve this issue , as before solar installation customer site PF was well above 0.9. Pl guide

  • @avikkumarpaul
    @avikkumarpaul Год назад +1

    Mera scenario B hai… project complete ho chuka hai. Abb kya solution ho sakta hai PF improve karne ka

  • @choudharinileshbhai6436
    @choudharinileshbhai6436 Год назад +1

    Agriculture motor power factor??

  • @mesh6969
    @mesh6969 5 месяцев назад

    Sir I'm from South Africa Hindi speaking but I'm 4th or 5th generations so I cannot understand. Can you please do a video in English or subtitle's.

  • @jahnavirefrigerationworks746
    @jahnavirefrigerationworks746 Год назад

    The solar on grid matter not only from PF metre not working

  • @shimbhudayaljangid8608
    @shimbhudayaljangid8608 Месяц назад

    Sir nhi ho rhA
    _23 rh jata h

  • @mdsahidbabber5172
    @mdsahidbabber5172 2 года назад +2

    APFC sense Power factor not running KW, if our plant will run in in 40 Kw at that time if power will down APFC will charge therre rest of all capacitor bank i guess

    • @solarfacts4242
      @solarfacts4242  2 года назад

      Sir you are correct I think we both are saying the point with different different angle, I am saying ACFC sense load and if load change then power factor will automatically change because of load behaviour.

    • @prakashmathad5563
      @prakashmathad5563 2 года назад

      I think Your gess is right.. APFC panel operate on PF only not sensing on load (kW)

    • @prakashmathad5563
      @prakashmathad5563 2 года назад +2

      @@solarfacts4242 It will not sense load. it will sense only pf value and try to make it correct pf..

  • @pratapsonawane1935
    @pratapsonawane1935 2 года назад +1

    What if we install 100kw Solar the Power factor issue will not be there??

    • @solarfacts4242
      @solarfacts4242  2 года назад

      There may be chances that load in the industry is mix of resistive and capacitive.

  • @kajalkoli5686
    @kajalkoli5686 2 года назад +1

    👌👍

  • @kaushikkhetalpar5101
    @kaushikkhetalpar5101 11 месяцев назад

    Raman sir can you share your contact, I have some doubts regarding PF , we have installed 400 kw solar power system.

  • @shankarsinghsisodiya4434
    @shankarsinghsisodiya4434 2 года назад

    यदि जब प्लांट बंद है तो सारी की सारी पावर ग्रिड में जाएगी उस समय पावर फेक्टर को कैसे मेंटेन करेंगे

  • @sathyaprasad1411
    @sathyaprasad1411 Год назад

    👏👏👏👏👏🏻👏🏻👏🏻👏🏻👏🏻🤝🤝🤝🤝🤝👍

  • @iiiMac
    @iiiMac 2 года назад

    Sir pls put in English please🙏

  • @chinnasamychinnasamy7578
    @chinnasamychinnasamy7578 4 месяца назад

    Tamil translation

  • @bisharatahmad258
    @bisharatahmad258 4 месяца назад

    Sir app ka whatsap nambar cahyee