Thank you so much for this vidio. Would you like to explain me why we kept sprinkler 10.3 feet from vertical wall? According to rule, it shall be (distance from wall-S/2.). So it shall be 7.5 feet insted of 10.3 feet.
Distance from wall is 1/2 the sprinkler distance , In your case is 15 feet , divide by 2 is come out to be 7.5 feet max distance from wall. You keep 10 feet from which un able to cover the area
sir. according to NFPA13. the distance of the sprinkler to wall should not exceed half the distance between sprinkler to sprinkler. as per your placement of sprinkler the distance was 15' so the distance from a sprinkler to wall should not exceed 7'5". is it okay to add one more sprinklers to design so we will not violate the code?
As per code, Adding one more sprinkler is also unwanted, so better to keep the distance and make sure you will place extinguishers in that distance differences
These piping systems comes by default while you're installing Revit software but you can edit them and can create new system by just going to piping systems in project browser
Kindly see the video before this video. That is related to how to create fire template and creating levels in Revit then you will come to know the answer of your question
Thank you so much for this vidio.
Would you like to explain me why we kept sprinkler 10.3 feet from vertical wall?
According to rule, it shall be (distance from wall-S/2.).
So it shall be 7.5 feet insted of 10.3 feet.
Thank you, do you know a method to make a circle around the head to show the sprinkler coverage to place heads more easy.
Distance from wall is 1/2 the sprinkler distance , In your case is 15 feet , divide by 2 is come out to be 7.5 feet max distance from wall. You keep 10 feet from which un able to cover the area
sir. according to NFPA13. the distance of the sprinkler to wall should not exceed half the distance between sprinkler to sprinkler. as per your placement of sprinkler the distance was 15' so the distance from a sprinkler to wall should not exceed 7'5". is it okay to add one more sprinklers to design so we will not violate the code?
As per code, Adding one more sprinkler is also unwanted, so better to keep the distance and make sure you will place extinguishers in that distance differences
the quantity of sprinklers on the code is minimum, you can add 2 more sprinklers
Requested to make videos on hvac controls
Did you find any videos now?
Thank you very much I wait for your videos .Pls make videos on Designing of FIRE FIGHTING System with calculation
Yeah sure
Sir , would you please show how you did Piping Systems for each trade and how you placed them in Piping System, to have them handy. Thank you,
These piping systems comes by default while you're installing Revit software but you can edit them and can create new system by just going to piping systems in project browser
How do you make the room tags appear in ceiling plan in revit?
Kindly see the video before this video. That is related to how to create fire template and creating levels in Revit then you will come to know the answer of your question
@@MEPEngineeringTutorials thanks!
hey can you send excel worksheets , thanks
The placing still dosent conform with NFPA 13 as maximum distance between wall and sprinkler need to be 2.3 m and 2.7 from any single wall.