Aap alarm reset nehi kar sakte ho.... Agar kuch alarm show ho raha hai, wo dekh k apko action Lena padega. Alarm hai trip ka previous stage . Iska matlab aap ko awareness deta hai ki yeh fault a sakta hai.
Hey brother i learned alot from your videos never in life worked on any vfd but i learned alot from you I changed ramo up and ramp down but i am getting W7 and W8 warnings 😢
Thank u for your valuable comment. W7 - is Over voltage W8- is under voltage. I think the value of Ramp Down which u set is too short . Plz increase the ramp down and ramp up time and warning will be gone.
Sir thank you for your informative video pls keep posting it encourages us I have Danfoss VLT FC102 250kw iam facing issue in DC Over Voltage A7 error I have increased the Ramp Down time but still the problem exist could you pls share your experience I will be thankful to you
You have to check following things 1. Input voltage should not greater than 415 v 2. If not solve you can use DBR( Dynamic Breaking Resistor) 3. Set the acceleration and deacceleration time 20 sec. Can you tell me the application of your motor drive?
@@TechnicalManas1 Thank you for your prompt response below things I have done Increased the Ramp Up time from 8sec/12sec Increased the Ramp Down time from 8sec/30sec Increased parameter 4-16 Trip Delay at Inverter Fault Activated function in parameter 2-10 Brake Function Brake Resistor unable to install due to no option available in Hardware Board Application : Mycom Compressor 250kw
Sir, when i remotely Stop the motor,the HMI shows stopand the current and speed slows down but due to its not getting stop in time the motor trip and alarm shows illegal motor current.
Alarm reset kaise karte hai uska video banaiye sir
Aap alarm reset nehi kar sakte ho.... Agar kuch alarm show ho raha hai, wo dekh k apko action Lena padega. Alarm hai trip ka previous stage . Iska matlab aap ko awareness deta hai ki yeh fault a sakta hai.
Great sir ❤️
Please upload more video in danfoss drive
Sir field me RPM indicator me RPM show karna ho to kon sa parameter setting karna hoga
Hey brother i learned alot from your videos never in life worked on any vfd but i learned alot from you
I changed ramo up and ramp down but i am getting W7 and W8 warnings 😢
Thank u for your valuable comment.
W7 - is Over voltage
W8- is under voltage.
I think the value of Ramp Down which u set is too short . Plz increase the ramp down and ramp up time and warning will be gone.
@@TechnicalManas1 Thankyou bro, the Alarm is gone but the warning is still there 😭
Please full video banaiy sir
Aur ek part hai .
VFD me kon kon se fault aata he us pe bhi video bnao
Sir. Can you please make a video of the complete setup of Danfoss drive vlt?
There have 3 videoes..... there have also a video on Digital Input & out put configuration.
@@TechnicalManas1 send mora give link
Push button se chalu nay ho raha he konsa parameter dalna he plz bataye
Humko Instagram mai msg kijiye, with photo.
@@TechnicalManas1 instagram nay he sir
Sir thank you for your informative video pls keep posting it encourages us I have Danfoss VLT FC102 250kw iam facing issue in DC Over Voltage A7 error I have increased the Ramp Down time but still the problem exist could you pls share your experience I will be thankful to you
You have to check following things
1. Input voltage should not greater than 415 v
2. If not solve you can use DBR( Dynamic Breaking Resistor)
3. Set the acceleration and deacceleration time 20 sec.
Can you tell me the application of your motor drive?
@@TechnicalManas1 Thank you for your prompt response below things I have done
Increased the Ramp Up time from 8sec/12sec
Increased the Ramp Down time from 8sec/30sec
Increased parameter 4-16 Trip Delay at Inverter Fault
Activated function in parameter 2-10 Brake Function
Brake Resistor unable to install due to no option available in Hardware Board
Application : Mycom Compressor 250kw
Input Voltage is 360/380volts
Thanks for share your knowledge
😊😊😊😊😊9
How can manual setting parameter
Manual mode running parameter setting
Sir, when i remotely Stop the motor,the HMI shows stopand the current and speed slows down but due to its not getting stop in time the motor trip and alarm shows illegal motor current.
First check the deacceleration time. If it higher .... Please set it 10 to 15 sec
Danfoss micro vlt drive me al13 alarm ko kaise troubleshoot karenge
W49 speed error ati he kya problem ho sakta he
Aap ka Drive ki application kaya hai ?
@@TechnicalManas1 jab normal condition hoti he tab frequancy batata he drive
@@TechnicalManas1 jab 3 ganta motor ko bandh rakha uske bad chalu kiya to chalu ho gaya .
How to reset after trip
First you have to press "Reset" botton then press 'Hand on' botton
Hand on botton konsa
Iska drawing ka pdf or isko kese padhte he is pr bhi video bnao
Stay tuned with us
Ye setup pura nahe huya he esko pura karao
Agar kuch baki reh gaya toh plz suggest kijiye 🙏
Alarm problem solution by
You have to check the particular problem. Which alarm it shows.
Yaar aap apna wattssapp number day sktay ho kya
Aap yaha pe boliye... Main ak wapp group create karunga then aap sabhi ko link de dunga
@@TechnicalManas1 bhai danfoss 5000 operator k saath jo motor hai wo start nhi ho rhi
Or saath main likh kr aarha hai k earth fault
@@TechnicalManas1 group create kiye kya
Group Create nehi Kiya. Aap instgram mai call kar sakte hain. If any doubt.