Bro each pump have specify cut in and cut off pressure so in that pressure once reached pumps.will work setting pressures in pressure switches if pressure increase first check why pressure increase then do the further operation😊
Nozzle la oru 13 floor hight irukura building la water flow aagum poodhu evallow pressure ra namma body hold pannum antha pressure evalo weight irukum konjam solluga sir,
13 floor building height ku pump oda head height irukkanum.. Set Pressure 6-7 bar irutha , electrical pump start aanathum 11-12 bar pogum.. Hose hold pannurathu problem illa, correct na position irutha easy tha
Depends on pressure, pressure set pannuvaga... Jockey pump intha pressure la on aagum, intha pressure vantha off aagum... Same way electrical pump Diesel engine.... Jockey 7 bar na Electrical 6 bar Diesel 5 bar Appadi set pannuvanga.... Okay va
Anna apo jockey pump panel kila oru 2 small valve irukula anna athu ethuku anna enga senior oruthavanga atha pressure down agurapo liteah thiruvi thiruvi operate panaru pumpla sound ketuchu athu ethuku Anna
1.Fire line la air irutha pumps la sound varum , so air release pannuna sound reduce aagum... 2. High speed la run aagum pothu sound irukkum. 3. Incorrect settings in pump.
Auto and manual irukkum, auto water pressure reduce aagum pothu automatically work aagum.. Manual neega start stop iukkum same tha motor ON OFF pannura mathiri
Each pump have setting pressure... Example 5 bar is setting pressure means when pressure come to 4 bar.... Pump turn ON Then Pressure reach 5 pump turn off.... Electrical pump once turn it ON , off after 10 minutes.... Diesel pump once turn it On, not off automatically, we need to off manually
All the best for your own business.. Unga head office la details Kelluga bro... 1. Agreement 2. Dealership certificate Ippadi neraya irukkum... Kettu paarunga.. 💕😍
Normally DG la sound irukkum bro Manual mode la load irukkathu so sound less... Auto model la load irukkum so sound irukkum... Otherwise DG service pannuga bro
Jacky pumpla pressure increase anavudan. Fire alaram act ayiruthu. Aprm electric pumb on ayiruchu. Ipa 3 pumb off pannanuma epadi
Settings pressure reach aanathum pumps off aayidum...
Electrical pump 10 minutes time delay irukkum...
Diesel pump manual tha off pannanum
Puriyutha bro....
Video innoru time paarunga....
Bro unga what's app number
9789066998
Bro each pump have specify cut in and cut off pressure so in that pressure once reached pumps.will work setting pressures in pressure switches if pressure increase first check why pressure increase then do the further operation😊
Thanks for your guidance❤
Thanks for your valuable feedback
Give more for motor specifications and pipeline systems briefly explain
Okay brother
Nice explain
Thanks for your valuable comment
நல்ல தகவல்
Thanks for your valuable comment
Ship fire Fighting System- TAMIL
ruclips.net/video/8PHEbeaR81E/видео.html
Anna... Parts of fire alarm system, fire pump system and it's purpose of each parts... Ippidi explain panni oru video podunga
Okay brother, kandippa
What are the matetials involved in fire room as bellows nrv air cussion tank. Explain
Okay
Hii sir, shop drawings vachi aprm practical enna enna irukoo apdi explain pannu gala with electrical panel
Okay ma
Sir explained nicely ,which ISstandard is reffered while installation
Sorry, I don't know deeply..
If anybody know about reply it.🙏
Explain to Duty pump or stand pump difference
Duty pumps are always in operation,
Standby pumps any operation pump repair or maintenance, then it will be active for operation
அருமை தம்பி 👍
Thanks for your valuable comment brother
Ship fire Fighting System- TAMIL
ruclips.net/video/8PHEbeaR81E/видео.html
Nozzle la oru 13 floor hight irukura building la water flow aagum poodhu evallow pressure ra namma body hold pannum antha pressure evalo weight irukum konjam solluga sir,
13 floor building height ku pump oda head height irukkanum..
Set Pressure 6-7 bar irutha , electrical pump start aanathum 11-12 bar pogum..
Hose hold pannurathu problem illa, correct na position irutha easy tha
100 Sprinkler, 2fire hose cabinet 2um orea time la work pannuma apdi work pannuna eathuna gpm capacity veanum pump ku
99401 57501
Please contact this number
maintenance video and name for all this (eg)psi full form, y we use cooland, what is prv , deisel pump saprparts full names video podu thaliva❤
Sure... Kandippa electrical basic and maintenance related , AC , plumbing video podururan brother
@@knowyoursafety2040 NFPA stand pathi poduga pump room
Basic fire safety video podunga
Okay brother
Athemathiri electric pumpla check pandrapo pressure drop na ena enna athu epdi check pandrathu
Same tha electric pump panel pressure transducer irukkum antha line oru valve irukkum atha open panna water drain aagum
Without leak jockey hydrant la water release pannita continue ah evvalavu neram motor run pannalam
Depend on motor capacity...
Over heat aanatha motor run aagathu so 1 or 2 hour oodum....
Pressure cut in cut off set method explain
In case real fire ahettu 1st electrical power off panniruvanga
Ipo FM standards ennana
1st jockey
2nd Diesel
3 main pump
Ithhuthan ipo avanga standard
Yes correct
1st jockey
2nd electrical pump
3rd generator ..
Unga comment correct read pannala ...
Depend on situation
Good
Thanks for your valuable feedback
First jockey pump,electrical pump ,disel pump intha varusaila varuma ella jockey pump aduthu disel pump aduthu electrical pump ipdi run aguma konjam soulluga brother
Depends on pressure, pressure set pannuvaga...
Jockey pump intha pressure la on aagum, intha pressure vantha off aagum...
Same way electrical pump
Diesel engine....
Jockey 7 bar na
Electrical 6 bar
Diesel 5 bar
Appadi set pannuvanga.... Okay va
Anna apo jockey pump panel kila oru 2 small valve irukula anna athu ethuku anna enga senior oruthavanga atha pressure down agurapo liteah thiruvi thiruvi operate panaru pumpla sound ketuchu athu ethuku Anna
Antha valve check panni paarunga...
Water drain aagum, water drain aagum pothum line pressure reduce aagum , appo pressure cutin value varum pothu pump start aagum...
Pressure setting reach aanathum cutoff aagum...
Hydrant Jockey Pump & Sprinkler Jockey Pump hotterஎதனால சவுண்டு வருகிறது please tell me sir
1.Fire line la air irutha pumps la sound varum , so air release pannuna sound reduce aagum...
2. High speed la run aagum pothu sound irukkum.
3. Incorrect settings in pump.
Control panel epudi use pananum sollunga
Auto and manual irukkum, auto water pressure reduce aagum pothu automatically work aagum..
Manual neega start stop iukkum same tha motor ON OFF pannura mathiri
Good one👌👌
Thanks for your valuable comment
Ship fire Fighting System- TAMIL
ruclips.net/video/8PHEbeaR81E/видео.html
Pressure transducers setting method explain
Each pump have setting pressure...
Example 5 bar is setting pressure means when pressure come to 4 bar....
Pump turn ON
Then
Pressure reach 5 pump turn off....
Electrical pump once turn it ON , off after 10 minutes....
Diesel pump once turn it On, not off automatically, we need to off manually
We need to change pressure in panel settings only...
Authorised person only change that... Or can through BMS
Bro can explain to pump curve
Curve means pump flow vs head ah
Bro na fire safety la three years ah work panren... Safety equipment dealership thodanga poren adhukku thevaiyana procedure sollunga
All the best for your own business..
Unga head office la details Kelluga bro...
1. Agreement
2. Dealership certificate
Ippadi neraya irukkum...
Kettu paarunga..
💕😍
Thanks bro
Jocky pump எதனால் ஓடுகிறது. Disel. Petrol. Elect.
Electrical power
Ji intha pump room community center thana
Pump room control community centre la irukkum
How calculate pump pressure plz
Pressure transducer is a device used to measure pressure.
Brother fire alarm technician related videos upload pannunga please
ruclips.net/video/PNzvfGZR_U0/видео.htmlsi=QOMDoxIN3prZ9NOE
ruclips.net/video/ke58gcEq8qs/видео.htmlsi=pgreqaObImNb4HJq
2 video irukku athu poga FM200 , sprinkler, alarm check valve videos channal la irukku bro...
@@knowyoursafety2040bro fire fighting technicisn ku course irukka?
Evalavu heat la Springaler blast agum bro
Orange colour sprinkler 57 ° celcius
Red 68° celcius ....
Innum neraya colour la sprinkler irukku but commonly intha two types tha use pannuvanga bro
ruclips.net/video/SEh4BChFP5A/видео.html
Full video for sprinkler
Hi bro diesel pump automatic on why can't off automatically what the reason
Diesel pump ON at low pressure, it means emergency situation electricity would be OFF building and may be can't reach pump area, and safety reason....
Secondary line use panratha pathi solluga
Oru video poduran brother
பொதுவாக ஜாக்கி பம்ப் ஒரு நாளைக்கு ஒரு முறை on ஆனால் ஏதாவது பிரச்சினையா
இல்லை
ஏதாவது சின்னதாக லிக் இருக்கும்.... பிரச்சினை இல்லை...
தொடர்ந்து ஓடிக் கொண்டிருந்ததால் கண்டிப்பாக லிக் அல்லது NRV problem irukkum
Pump material name and panel programming
Do you fire hose cabinets pump sizing
Fire hose cabinet size or reel hose size.?
No pump in fire hose cabinet..
Sir, is there any institutions to learn this kind of work
Fire fighting course available
@@knowyoursafety2040 I am requesting you to share the details pls
DG Auto mode la ON pannu pothu, DG la sound athikama varuthu.
Manual mode la panna DG sound illa, ena problem bro
Normally DG la sound irukkum bro
Manual mode la load irukkathu so sound less...
Auto model la load irukkum so sound irukkum...
Otherwise DG service pannuga bro
Anna pump on ayiruchuna epadi off pannurathu
Jockey pump continues ah running la iruthal pipes la leak irukkum....
HOW TO CONNECT FITTINGS IN PUMP ROOM
What fitting.?
Fire alarm system any troubles shooter video update
Okay
What type of starter to be used in Jockey pump?
Dual starter because of jockey pump is below 5hp
@@knowyoursafety2040 okay then in case DOL starter we can use??
Electrical pump we have selected S/D starter correct??
I said dual means DOL
Yes... Exactly
Safety officer vacancy tell me sir
Okay
Nrv na Enna bro
Non returnable valve...
Water flow oru direction la tha pogum...
Water return varathu
@@knowyoursafety2040 thanks for reply bro
niraya fire alarm pathi video podunga vro
pump Room maintenance
pressure gauge open
later jokey pump then?
how to monthly maintenance
in pump room bro
As per schedule pump maintenance as usual...
Fire tank clean 3 month once..
Pressure gauge open later.???
Puriyala
Jockey pump start aagum..
Innum pressure down aana electrical pump start aagum...
Innum down aana Diesel engine start aagum
Bro I need to speak you
Video la Idama uniform la varudhu😂
😍
@@knowyoursafety2040 neenga ejadah la ya work panndringa bro??
@statuztamila353 farnek la work pannan.. Ippo Chennai
Jockey pump, Electrical driven pump ethana HP irukanu..
Generally jockey pump 7-10 hp
Electrical pump 300-350 hp irukkum...
Aana building height and requirement vachi pump size different aagum..
English please
Okay, i will do it
வாட்ஸ்அப் நம்பர் அனுப்புங்க 🙏🙏🙏🙏🙏🙏
9789066998
Bro pressure switch la epdi pressjr adjust