SolarEpic EPEVER Tracer AN Series 50A/60A/80A/100A MPPT Solar Charge Controller

Поделиться
HTML-код
  • Опубликовано: 17 дек 2024

Комментарии • 58

  • @SolarEpic
    @SolarEpic  3 года назад +1

    Unboxing 2:07
    Installation 3:36
    LCD Display Setting 7:26
    Uninstall 8:10

  • @wipika01
    @wipika01 3 года назад +7

    How is the Load Control Relay connected?

  • @johnmqorae5853
    @johnmqorae5853 Год назад +1

    How can I connect the DC load in this charge controller?

  • @phildxyz
    @phildxyz 3 года назад +3

    What I don't understand about these controllers is that as the load is controlled by an external relay the controller cannot measure the load current. Yet the display still shows load current and wattage and so does the app. Is there some additional device that can signal the load current back to the controller, or am I missing something?

    • @SolarEpic
      @SolarEpic  3 года назад +1

      Hi, The load current/volts listed because we leave a backup plan for those who wants to customize our charge controller with load feature for bulk orders, so we have it on it, in case when it happens we don't need to redesign the controller firmware. For our common charge controller, we just put it on and no interface for load terminals.

    • @boscodog4358
      @boscodog4358 2 года назад +1

      What does the MPPT fuse protect and what size is it??

  • @seriouszen5670
    @seriouszen5670 4 года назад +2

    Utility relay? Where to find it.. Can i just charge the battery using AC to DC battery charger without connect the output cable from AC to DC charger to the mppt?

  • @byondlight
    @byondlight 2 года назад +1

    So after numerous searches you are the only one showing installing the temp sensor. It is the reverse polarity light you took out .. correct?

    • @The_River
      @The_River 2 года назад +1

      That's what I wonder about. Epic Solar is not clear regarding the temp sensor.

  • @almirluisdebrito4503
    @almirluisdebrito4503 Год назад

    Tinha de ter Mostrar qual disjuntor foi utilizado

  • @bellofiore894
    @bellofiore894 2 года назад

    Hi In this video ALL is OK for you BUT I have one 6415 AN 60 A and when I do the same you do, SOUND THE ALARM FOR REVERSE POLARITY ! WHAT Polarity I have changed two of this in a Week !!!!! Both had the same problem !!!

    • @SolarEpic
      @SolarEpic  2 года назад

      Hi, please send your question to support@solarepic.com so that we can understand your question in detail.

  • @cosiendojuntos6278
    @cosiendojuntos6278 4 года назад +4

    Sorry for my questions but I don’t know the answer. I see you connect the voltage sensor cables in the controller, but the other end, where I need the connect?

    • @leejeremy4755
      @leejeremy4755 4 года назад +1

      It sense the battery voltage, other end must be battery's Pos and Neg connector

    • @shemmo
      @shemmo 4 года назад +2

      @@leejeremy4755 i am wondering why this is needed if distance between MPPT and battery is lets say 0.5m. When it makes sense to use the Voltage sensor cable?

  • @qaisehayati9373
    @qaisehayati9373 Год назад

    Can it start and stop diesel generator?
    My mean can it give command on Diesel generator

    • @SolarEpic
      @SolarEpic  Год назад

      Hi, it supports what you said.
      The load/utility/generator dry contact to connect external devices conveniently composes a hybrid power system easily.

  • @bimmers323ci
    @bimmers323ci 3 года назад +1

    hi//i have 2 of the tracer an10420 controller and i am not getting any power from the load relay need help please///i have a multy meter to test it and no power is coming from any of them even when you turn the load power on

  • @asifsaleem2282
    @asifsaleem2282 2 года назад

    I am in need to learn generator ON/Off in case of chargeing battery

  • @jamest.5001
    @jamest.5001 4 года назад +1

    Does this charge lithium batteries? And not why? I really like these charge controllers, and need more than the two 40 amp controllers I have, I'm needing like 200 amps charging for lithium batteries! Thanks

  • @boscodog4358
    @boscodog4358 Год назад

    What do Epever call "Absorption voltage " and what is it 🤔?
    Float voltage?
    I don't understand your terminology compared to other manufacturers. Very Very frustrating!
    Do you have any technical support in the USA???

  • @marcvictoreykens3140
    @marcvictoreykens3140 4 года назад

    i own the same controller, wondering mine dusnt have the cable bridges to secure the cable

  • @johnwolf1475
    @johnwolf1475 Год назад

    uninstall for the return as nothing mentioned about the workings of temp sensor

    • @SolarEpic
      @SolarEpic  Год назад

      The function of a temperature sensor is to detect the ambient temperature of the battery. It allows the controller to adjust the charging voltage given to the battery based on the ambient temperature. This provides better protection for the battery and extends its lifespan.

  • @napalmholocaust9093
    @napalmholocaust9093 3 года назад +1

    Why are the actual instructions different from your video? You show the controller's battery and pv cables being slipped into the terminals then tightened. The instructions show to open the clamp on the terminal before insertion then tighten. If you just insert the cables as you show wouldn't they be on the wrong side of the screw terminal? Shouldn't it be opened first?

    • @leejeremy4755
      @leejeremy4755 3 года назад

      ruclips.net/video/uix-nLA_8G0/видео.html Please check here, the solar panel's wire sequence is Neg to Pos.

  • @asifsaleem2282
    @asifsaleem2282 2 года назад

    How much load in amp does its dc load can bear?

  • @RandyMoncion
    @RandyMoncion 2 года назад

    I have 3x 455w solar panels and a bank of 2 6v batteries in series that are 12v, which EPEVER MPPT do you recommend the 60a or the 80a?

    • @SolarEpic
      @SolarEpic  2 года назад +1

      Hi, we will recommend you use 100amp, as the 80A only handles 1000W solar panel on 12v battery, 100Amp charge controller can handle 1250W solar panel.

    • @RandyMoncion
      @RandyMoncion 2 года назад

      @@SolarEpic Thank you

  • @chiapasjosue145
    @chiapasjosue145 Год назад

    Hola muchas gracias por el video, tengo una pregunta, para que sirve el segundo cable que conectó a la batería?
    Bueno, el positivo y negativo con caimanes, yo tengo uno como ése controlador de 60 ah.
    Espero que ayudes, o alguien que me apoye por favor, se lo agradecería mucho
    Gracias

    • @SolarEpic
      @SolarEpic  Год назад

      Hi, das zweite Kabel, das in diesem Video an die Batterie angeschlossen ist, ist ein ferngesteuerter Spannungssensor. Wir können ihn verwenden, um die Spannung unserer Batterie zu kalibrieren.

    • @chiapasjosue145
      @chiapasjosue145 Год назад

      @@SolarEpic muchísimas gracias, lo siento, yo no hablo el idioma que tú hablas, me costó mucho trabajo en traducirlo, entonces lo puedo hacer también esa instalación a mi sistema?
      Tengo el controlador epever modelo TRACER6415AN 60 ah.
      Lo qué pasa es que tengo un problema con este controlador, mi sistema es a 48 v. Pero el voltaje llega hasta 61 v. Entonces mi inversor no soporta ese voltaje se apaga

    • @SolarEpic
      @SolarEpic  Год назад

      @@chiapasjosue145 Hola,
      ¿Cuál es el rango de voltaje de su inversor? ¿O cuál es el voltaje máximo que puede manejar su inversor?

    • @chiapasjosue145
      @chiapasjosue145 Год назад

      @@SolarEpic el rango de voltaje es 40-60 v cd.
      pero ya después de 60 ya se apaga, como que aveces el controlador no corta el voltaje, mi sistema es de 48 v. Tengo 4 baterías selladas AGM VRLA
      Obviamente están conectadas en serie

    • @SolarEpic
      @SolarEpic  Год назад

      @@chiapasjosue145 Hi, please send your question to support@solarepic.com so that we can understand your question in detail.

  • @wisalahmad1867
    @wisalahmad1867 3 года назад

    Hello can I connect 3 150watt panels to 30amp epever

  • @seb1739
    @seb1739 4 года назад +1

    hello. How to connect generator ?

    • @SolarEpic
      @SolarEpic  4 года назад +1

      It requires your diesel generator has the feature to receive this relay signals when battery drops to a certain point, the controller will send the signal to the generator and you can use the generator to charge the battery as a backup charging source. Not all generators have this feature.

  • @danielrajszczak
    @danielrajszczak 3 года назад +1

    I received a few days ago the EPEVER 6420 device. I have a problem. Three PVs of 450Wp each are connected (about 140V, maks. 10A). Battery 24V 100Ah. On a sunny day, the battery can only be charged up to 1A. When I turn on the inverter, it increases to about 2A. When it starts up other devices, the charging increases to 16A-20A. How to make the battery charge with a specific current, e.g. 10A? I looked closely at the software and found no such function. In addition, I would like to limit the voltage because it is sometimes above 30V and activates the protection in the converter. I am asking for help as I have been trying for a few days and exhausted my ideas. Thank you.

  • @JerryJones1914
    @JerryJones1914 4 года назад +1

    What size of wire are you using in that controller thank you.

    • @SolarEpic
      @SolarEpic  4 года назад +4

      I'm using #7 awg wire.

    • @faisalyousuf3484
      @faisalyousuf3484 3 года назад

      @@SolarEpic 48 volt system ko charge karega

  • @qwertyui90qwertyui90
    @qwertyui90qwertyui90 4 года назад

    Can you stack these controllers and have them talk to one another ? like a master and a slave ?

  • @mont5584
    @mont5584 2 года назад

    Is SOLAREPIC MPPT also a EPEVER MPPT CHARGE CONTROLLER? Are they made from the same company? Both seem to have the similar traits.

    • @SolarEpic
      @SolarEpic  2 года назад

      Hi, Yes, we are the distributor of EPEVER.

  • @ewartbain5463
    @ewartbain5463 4 года назад

    Hello SolarEpic, I have a Tracer 5420AN and thinking of upgrading my array to a Voc of 170v and Isc of 45A. Do you know whether this charge controller is capable of handeling that input? The specifications says Max Solar Input is 200V and it is a 50A charger controller as you may know. Thanks in advance for your assistance.

    • @SolarEpic
      @SolarEpic  4 года назад

      Hi, the 200V version will handle 170V (Voc) solar panel, but the solar panel's power, it can only handles 625W if you are charging 12v battery. We are not calculating the solar panel's current as the charge controller will step down the voltage and boost the current, 50A is the max current it can handle. So we will limit the input power.

  • @nppkm771
    @nppkm771 4 года назад

    I wnat buy this product.but not available for india

  • @FreedoomRock
    @FreedoomRock 4 года назад +7

    Explainations would have much better than stupid music

    • @TreeLBollingTreeMan
      @TreeLBollingTreeMan 4 года назад +2

      What language would you have them use out of the 7,117 languages in the world? Oh that's right, the one you use. Hahahahaha!