Dapat may Valve Piercing Adapter ka sir para wala talagang ma suck na hangin galing sa oil mo kaya nag bobola sa sight glass ng compressor mo kasi may na suck na hangin, pero overall sir maganda ng explanation mo, thumbs up👍, Godbless po!
Thanks for your message...anyway meron po tayong tinatawag na self vacuum according to my content at ginagamitan po natin ng gauge to make it sure na fully vacuum ung system natin (no more air.)😊
may scerw adjuster sa itaas ng pressure switch depende sa brand meron sa kaliwa meron iba sa kanan ang differential makikita mo naman sa monitor ng pressure switch may nakasulat na DIFF. at mag aadjust ang pointer pataas at pababa kapag pinihit mo ung adjusting scew sa itaas. set mo sya by using gauge manifold😊
good day rin boss...sa refrigeration wala po tayong tinatawag na pump up...meron pump down, pump in at pump out...sa pump down is designed to protect compressor from liquid slugging and frequent operation with liquid in the refrigerant being drawn in.
@dodong3628 ang relief valve kalimitan nyan nakakabit sa liquid receiver at ang purpose nya ay mag release ng certain amount of refrigerant during high pressure kapag may sira ang pressure switch. mag release po sya ng refrigerant 10kg/min kaya make it sure na ok ung pressure switch masasayang lang ang 10kg😊
ganon din po dito sa video boss gayahin mo lang...dalawa option dyan using vacuum pump and without vacuum pump choice mo na yan bitzer din po itong nasa video ko umpisahan mo lang sa part 1😊
Sir kapag totally ka po mag change oil meaning drain yung langis walang langis hindi po ba delikado kasi walang lubrication?wala rin po kasi kaming vaccuum pump
yes kapag change oil...totally drain down all oil and change it a new one...sa video ko ay paano magkarga ng langis sa compressor... meron pa rin syang langis pero kulang i mean ( the way how to charge oil )...hindi po how to change oil...ok? dangerous po kapag mag change oil ka at paganahin mo ang compressor to use as a vacuum pump kapag wala po syang langis sa loob to lubricate mechanisms.😊
kung water cooled ang condensing unit...check Y-strainer baka restricted ung daloy ng tubig. purging ka baka kinabag ang linya ng tubig...water regulator valve baka hindi nag oopen ng maayos.
Sir bakit yong sa compressor namin walang bumabalik na langis? Nagpalit na kami bagong separator eh. Nag clean na rin kami ng mga piping wala pa ring langis na bumabalik
boss ang service valve ng compressor kapag sinara mo merong parte na nagbubukas at kapag binuksan mo naman ay meron ding nagsasara kaya kung mapapansin mo sa video may discharge pressure at may suction pressure.
boss Gibson Vergara ...kung pinanood mo ang video hanggang dulo mauunawaan mo at hindi ka magtatanong kung may moisture bang pumasok...anyway sabihin ko na rin sayo. kung mapansin mo sa dulo ng video sinara ko ung suction charging port ng cap bago ako nag self vacuum...kaya ang maba vacuum lang ng compressor ay ang air sa loob ng compressor at hindi na sa labas at ung air sa loob ng compressor inilabas na sa charging port ng discharge service valve dahil ung port na un ay open kapag gumagana ang compressor at magsasara din kung hihinto. completuhin ang video para completo din ang matutunan...ok😊
Sir sa ganitong model Na Compressor Na R 22 po ang Freon na Gina gamit nmin pwd po ba ang SL 32 suniso na brand model ng compressor ay LEE -201-EWL Copeland po
d pwede boss magkaiba ang vescosity ng oil ng R-22 kaysa mga bagong refrigerant ang R-22 ay hindi ozone friendly unlike R-404a, 134a etc pede sa R-22 mineral oil like suniso 3Gs and 4Gs
Kuya poul shout out
ok boss next video
Boss salamat madami ako natutunan. Parequest naman ng nitrogen blow sa linyada. Salamats
Salamat bossing sa shout out
Pol, good day sir... Sana makapag vlog Ka po ulit Kung paano Magpalit Ng oil SA compressor.. ingat pol
hopefully boss bc lang😊
Nice bro
Dapat may Valve Piercing Adapter ka sir para wala talagang ma suck na hangin galing sa oil mo kaya nag bobola sa sight glass ng compressor mo kasi may na suck na hangin, pero overall sir maganda ng explanation mo, thumbs up👍, Godbless po!
Thanks for your message...anyway meron po tayong tinatawag na self vacuum according to my content at ginagamitan po natin ng gauge to make it sure na fully vacuum ung system natin (no more air.)😊
Kuya paul pa shout out naman....
Maraming salamat ulit Pol Tubio
Alamin mo ang pangatlong paraan sa pagdagdag o pagkarga ng langis na walang ginagamit vacuum pump qt compressor
haha ayos 😁😁😁gawan kita ng video boss patungkol sa pangatlong paraan ng pag karga ng langis pagkatapos kong ie upload ung part 4...abangan mo nlng😊
Sir video nman pag karga ng refrigerant...nag aaral po ako...salamat po
hopefully boss pagnakagawa na ako ng fb page don na me mag upload may problema na ang yt channel ko
Boss gud day po mayroon po kaung video ng nagkakarga ng refrigerant sa Walk in freezer,, salamat po..
meron boss kaso nabura nagerror ang micro sdko nong nilipat ko ang video nag corrupt. gawa nalang me boss
Medio delikado yan Sir laluna sarado suction at discharge valve mo
salamat sa concern boss...pero dko naman gagawin yan kung delikado.😊
Sir, tanong ko po kung ilan po ba ang required pressure ng freon sa pagkakarga sa compressor ng AC at Provision compressor? Maraming salamat po.
depende po boss sa unit ung mga non- inverter dati 55 -60psi ngayon mga inverter na nasa 100-120psi, sa car a/c naman ay 30-40psi
Sir pano po mag adjust ng diperensial presure swixth
may scerw adjuster sa itaas ng pressure switch depende sa brand meron sa kaliwa meron iba sa kanan ang differential makikita mo naman sa monitor ng pressure switch may nakasulat na DIFF. at mag aadjust ang pointer pataas at pababa kapag pinihit mo ung adjusting scew sa itaas. set mo sya by using gauge manifold😊
Sir good day new subscriber po sana ma notice niyo po tanong ko paano po ba process ng pump up?
good day rin boss...sa refrigeration wala po tayong tinatawag na pump up...meron pump down, pump in at pump out...sa pump down is designed to protect compressor from liquid slugging and frequent operation with liquid in the refrigerant being drawn in.
sir relief valve poba tawag don , sa pina labasan nyo ng hangin ?
charging port po boss ng service valve
@@polractv5411 ahh ok po , yong natapos nya lahat mag charge ng oil ? kala ko po relief valve
@dodong3628 ang relief valve kalimitan nyan nakakabit sa liquid receiver at ang purpose nya ay mag release ng certain amount of refrigerant during high pressure kapag may sira ang pressure switch. mag release po sya ng refrigerant 10kg/min kaya make it sure na ok ung pressure switch masasayang lang ang 10kg😊
Sir pano po ung pag add ng oil sa bitzer 4TES-9y model?
ganon din po dito sa video boss gayahin mo lang...dalawa option dyan using vacuum pump and without vacuum pump choice mo na yan bitzer din po itong nasa video ko umpisahan mo lang sa part 1😊
Sir kapag totally ka po mag change oil meaning drain yung langis walang langis hindi po ba delikado kasi walang lubrication?wala rin po kasi kaming vaccuum pump
yes kapag change oil...totally drain down all oil and change it a new one...sa video ko ay paano magkarga ng langis sa compressor... meron pa rin syang langis pero kulang i mean ( the way how to charge oil )...hindi po how to change oil...ok? dangerous po kapag mag change oil ka at paganahin mo ang compressor to use as a vacuum pump kapag wala po syang langis sa loob to lubricate mechanisms.😊
Bro. Anong mga cause ng high pressure fault alarm sa compressor motor ng chiller Carrier Brand
kung water cooled ang condensing unit...check Y-strainer baka restricted ung daloy ng tubig. purging ka baka kinabag ang linya ng tubig...water regulator valve baka hindi nag oopen ng maayos.
pede rin defective na pressure switch
@@polractv5411 saan po exact location ng Pressure switch sensor
any part beside compressor boss...meron yan capillary tube na nakakabit sa high and low pressure pipes sa compressor or sa valves
boss may part 4?
d pa ako nakagawa boss nabura kasi video ko ng part4 nag corrupt ang memory card.hopefully by june makakapag upload uli ako
@@polractv5411 sana boss, kasi malaking tulong samin mga gustong matuto, salamat boss
sir wala yata ang part 4 na video mo?
sensya na boss...nererecover ko pa... kc ung lahat ng nakasave na video ko for uploading nabura lahat nag malfunction ung memory card
How many time I have to do self vacuum after adding oil to take moisture out ? 2-3 times ?
I mean start manualy compressor ?
one time only is enough boss...and applicable only for short system or compressor itself.
Thanks mate for your help much appreciated
Have a nice day !
yes do it manually...it won't work in auto mode
@ziomyyziomale3390 you're welcome 😊
Sir bakit yong sa compressor namin walang bumabalik na langis? Nagpalit na kami bagong separator eh. Nag clean na rin kami ng mga piping wala pa ring langis na bumabalik
un bang oil separator na pinalit nyo....d na ninyo nilagyan ng langis?
dapat kapag bago mag lagay kayo sa oil separator ng mga kahit isang litro
bago nyo paganahin at ang compressor ay may langis rin na 3/4 level
sir saang bansa kayo ngayon?
pinas boss
idol ilang hp yang comp. mu?
4hp
bakit nababawasan ang langis saan napunta, may leak ba
sa ibang sitwasyon may leak ang unit...ung iba because of abnormal operation minsan napupunta sa system at hindi nakabalik sa compressor😊
Di ba mcra compressor nyan sir inistart mo sarado discharge at suction valve
boss ang service valve ng compressor kapag sinara mo merong parte na nagbubukas at kapag binuksan mo naman ay meron ding nagsasara kaya kung mapapansin mo sa video may discharge pressure at may suction pressure.
masisira ang compressor kapag may mali ka sa procedure😊
Boss pano yan di nadagdagan moisture ng compressor dahil naka suck ng hangin?
boss Gibson Vergara ...kung pinanood mo ang video hanggang dulo mauunawaan mo at hindi ka magtatanong kung may moisture bang pumasok...anyway sabihin ko na rin sayo. kung mapansin mo sa dulo ng video sinara ko ung suction charging port ng cap bago ako nag self vacuum...kaya ang maba vacuum lang ng compressor ay ang air sa loob ng compressor at hindi na sa labas at ung air sa loob ng compressor inilabas na sa charging port ng discharge service valve dahil ung port na un ay open kapag gumagana ang compressor at magsasara din kung hihinto. completuhin ang video para completo din ang matutunan...ok😊
Sir sa ganitong model Na Compressor Na R 22 po ang Freon na Gina gamit nmin pwd po ba ang SL 32 suniso na brand model ng compressor ay LEE -201-EWL Copeland po
d pwede boss magkaiba ang vescosity ng oil ng R-22 kaysa mga bagong refrigerant ang R-22 ay hindi ozone friendly unlike R-404a, 134a etc pede sa R-22 mineral oil like suniso 3Gs and 4Gs
ang Sl-32 ay synthetic oil para sa mga refrigerant na ozone frielndly like R-404a 134a etc
Master anung langis ba Ang pwede sa r22
suniso oil 3GS/ 4GS