There are thousands videos on net about running hybrid during load shedding and only few like this person. He is telling truth, this is how we are bombarded with lies on social media.
I have an observation on his example. He assumed a solar output of 3000 Watts. Let us agree that this output would be achieved between say 1030 hours and 1530 hours in Summer ( June/July). If load shedding takes place during this time we can still run say 3 fans, (390W) one LED TV, (60 W), Laptop (60 W) Wifi (20W) and say 3 LED lights (30W) giving a total of 560 W. This can easily be handled by 3000W output. Sensible people wire their PV power so that heavy loads like Toaster, AC, washing machine, fridge, motor are NOT switched on during loadshedding.
Theoretically, you are right, but the problem is that, again, this 3000W will not be stable during the load shedding. What if there are clouds, etc. during this 3000W time period. It may come down to 1000W (say) or even lower, and if the clouds are cleared, the output will again jump to higher value. To handle the situation, you need a very intelligent & sophisticated piece of electronic switching circuit as manual switching between different appliances is not practically feasible. The problem is not the availability of lowered output during electricity shut down, but the continuous variation in the output as there is no battery or grid supply available, which could act as a sink or reservoir to keep the output smooth and stable at a fixed power level.
Bhai apko load bhi manage krna hota. zahir si baat hai agar load shedding din kai waqt hogi aur apkai paas batteries nahi hai to ap sirf PV pai dependent hogai. Aesay mai inverter ko trip sai bachanay kayliay apna load bhi kaam krna hoga simple. You can run a hybrid inverter without batteries on PV+Grid in normal case and with only PV during day time grid outage if you manage the load. Batteries are still too expensive and not worth it from a ROI perspective in my opinion.
Agree beteris bht expensive hain ab drop taiz jo gi to load chlata hai ager drop kam hai to load b kam krna ho ga to kam chlay ga.... ab ye to pagal pan hai drop kam hai or sab kuch on kia hwa hai load kam kro kse nae chaly ga.... betry b laga lo phirnye socho k g soler laga hai sab free chly ga ohir paway dhop na niklo ho😅 Dhop kam ho to load b kam krna pry ga phir sae chaly ga.... Dhop kam ho to wo betry pr lay ae ga us k bad sham may lite gae to betry b khali😅 phir kia kry ga bnda..... Load kam krna ka btao bhai logo ko.... Mai lagwao ga ab bagiar betry k sin may soler sag or wapda cut off.... usi solar say ghr ka ups b chrge ho ga sham ho gi to upes on jab betry kam ho gi to waoda on simple subha phir soler chalo phir betry b charge ups say
Jitni ki batteries aati hain,,aap utna extra pv lga lain.humesha aisa inverter choose kren,jiska pv zyada ho as compare to output load.masla hal ho jaye ga ,,batery se jan chut jaye gi
نیٹ میترنگ کرا لیین بجائے بیتریان رکھنے کے ۔ایک یو پی ایس لگا لیین 12 وولٹ کی ایک بیتری والا ۔ساتھ واپڈا شیرنگ چلائین ۔یونٹ خود ہی امپورٹ ایکسپورٹ ہوتے رہین گے
Ham ny kal net metering ki ha bhai but pahly kah rhy thy ky ap log battery na lagain ab kah rhy hain lagao .yeah kia bat hoi jab wapda nai ho gi to invertor hybride ha direct kiun ni Ac chala sakta 🤔🤔🤔
My question is can hybrid system be used as only grid tied? In hour of load shedding to trip completely? The problem with hybrid is very well explained.
Bilkal thek bat btae apny inverter ko 2nd source mila wa ho to ye work sae krta chaey wapda sharing ho ya battery...mene knoxx 3kw argon 4500 lgya sath 4 panel attached keay abi 575 Canadian byfical..only pv py frigde non inverter.+ Fans ni chlty but wapda sharing py koi issue ni hota ..halnk wapda Sharing m 0 ampire show hota ...bas 2nd source available hona chaeay ...
Ik question h..3000w stabled ni hai ok..2000w bh stabled h to 1000w to use ho skty h phir bh...solar zrurt h.local invertor bht cheap h as compare to any imported invertor..repair krna bh asan or cost effective h.local 3kv invertor k sath 6 plate ka system 3 lkh tk install ho jata h...to mera ni khiyal k din time me jitni mrzi load shefing ho 100w sy nichy phir bh aye ga
بھائی صرف اپنا بل کم کرنے کے لیے لگایا جاتا ہے ہمارے پاکستان میں ایک سوسائٹی ایسی بھی ہے جہاں لائٹ نہیں جاتی بحریہ میں ڈی ایچ اے میں بڑی بڑی سوسائٹیوں میں لوڈ شیڈنگ نہیں ہوتی
Hi, I have installed Afore 6 KW Single Phase Hybrid Inverter Model No. AF6K-SL . All the load has been connected to EPS out. The onverter is installed without batteries. However whenever, PV is powered off through DC breakers or at night the EPS load is not shifted to Main Grid Source and is turned off. How to resolve this issue. Lastly what is difference between GridFeed and GridBack
Torque Load par nai chale ga , like ac fridge motor, and load aik dam load dal do to trip hojaye ga because solar panel ya solar inverter jitna load hota hai chal raha ho
بھائی جان آپ ساڑھے آٹھ ہزار واٹ لگا کر تین ہزار واٹ کا لوڈ لے رہے ہیں وہ بھی پیک اور میں آپ ادا لوڈ بھی نہیں لے پا رہے جس دن بادل ہوں گے کچھ نہیں چلے گا
Sir g agar baghair battery waly inverter 3.2 ko laga kar os k aagy ups lagaya ja sakta hai? single battery wala light load k lye jasy pankha aur light waghaira ups par chal jaeyn
اس کا بلکل کوئی فائدہ نہیں آپ تھری پوائنٹ ٹو کے اوپر دو بیٹری لگا لیں ایک بیٹری آپ کے پاس ہے دوسری بیٹری پرچیز کرلی آپ کو زیادہ لوڈ اور زیادہ فائدہ ملے گا شکریہ
Plz guide me.me 3.5kilowat inverter k sath 315 ka solar panel 24 v waly kitny attach krny hain or kitny bateeries lagany hain...off grid hai.no wapda.plz guide me
آپ بالکل صحیح کہہ رہے ہیں اور آپ کا بتانے کا طریقہ بہت ہی بہترین اور اچھا طریقہ ہے
He really knows what he is talking abt. Thumbs up
آپ بالکل صحیح کہہ رہے ہیں اور آپ کا بتانے کا طریقہ بہت ہی بہترین اور اچھا طریقہ ہے
جس طرح آپ نے بتایا ہے اس طرح کوئی بھی نہیں بتاتا
کام کرنے والا کام کرکے دیتا ہے اور کام کروانے والے کام کرواتے ہیں مگر پتہ دونوں کو ہی نہیں ہوتا ہے کہ اس کو کس طرح چلانا ہے اور اس کا فائدہ اور نقصان کیا ہے
السلام علیکم آپ لوگ اسی طرح میری حوصلہ افزائی کرتے رہیں اور میں آپ کے لیے اچھی اچھی ویڈیو بناتا رہونگا بہت مہربانی
اللہ تعالیٰ اپکو جزائے خیر دے ہم یہ سسٹم خریدنے لگے تھے رہنمائی کا بہت شکریہ
Boht shukriya kafi din Mai tention me Tha lekin AAP Ki video ne Mera masla hal ho gia gai
بلکل درست بات ہے زبردست ویڈیو بہت اچھا مشورہ دیا ہے
competent professional very well expalined
Excellent Sir G, actually Solar is necessary not Luxury, when ever i visit any client first educate them, really appreciate ur video.
There are thousands videos on net about running hybrid during load shedding and only few like this person.
He is telling truth, this is how we are bombarded with lies on social media.
آپ کا بتانے کا طریقہ بہت ہی بہترین اور اچھا طریقہ ہے
Thanks 😊👍
Very good informative video
Very informative Sir
good information sir
Well explained in simple language and words for users....very informative
Thanks a lot
بہت اچھی معلومات
شکریہ
Thnks Master g .........Its really very helpfull and infomtive video
Most welcome
Very useful and informative Video.
💕
بہوت بہوت شکریہ جناب اپکی وجہ سے ہماری بچت ہو گئی ورنہ ہم بھی بغیر بیٹری والا سسٹم لگوانے جا رہے تھے
Acha guide kya ap ney thanks
Very informative info...
Thanx dear sir!
🙏😘
Aslam o alakum.right said.
Very informative
Good Master sb
آپ نے میری سوچ بدل دی
شکریہ
Thanks bro for best information
I have an observation on his example. He assumed a solar output of 3000 Watts. Let us agree that this output would be achieved between say 1030 hours and 1530 hours in Summer ( June/July). If load shedding takes place during this time we can still run say 3 fans, (390W) one LED TV, (60 W), Laptop (60 W) Wifi (20W) and say 3 LED lights (30W) giving a total of 560 W. This can easily be handled by 3000W output. Sensible people wire their PV power so that heavy loads like Toaster, AC, washing machine, fridge, motor are NOT switched on during loadshedding.
Theoretically, you are right, but the problem is that, again, this 3000W will not be stable during the load shedding. What if there are clouds, etc. during this 3000W time period. It may come down to 1000W (say) or even lower, and if the clouds are cleared, the output will again jump to higher value. To handle the situation, you need a very intelligent & sophisticated piece of electronic switching circuit as manual switching between different appliances is not practically feasible.
The problem is not the availability of lowered output during electricity shut down, but the continuous variation in the output as there is no battery or grid supply available, which could act as a sink or reservoir to keep the output smooth and stable at a fixed power level.
Brother, not everyone is as smart as you who can manage these things.
100% right sir battery k bina Pakistan main solor nakm
💓
if the Solar system w/o batteries is generating 3000 W , keep the load around 2000-2200 W, the system will not trip.
Jazakallah. Very valid points
Thanx bhai ap ny Sach btaya hy ,,koee invertor beghair battery kam nhi krta sab jhoot bolty hen
جی بالکل بھائی یہی بات ہے
Day tym pai load manage karlo to chalta hai Bhai Jin sai load manage NAHI hota wah tripping Hoti hai
@@malik8733bhai load kese manage kren ge agar achanak se cloudy hota hai ??
بہت خوب جناب
Shukrea bahai
Well explained
ماشاءاللہ بہت خوب
Excellent. Great explanation. (y)
Thanks 👍
with wapda sharing
with pda sharing
Bhai apko load bhi manage krna hota.
zahir si baat hai agar load shedding din kai waqt hogi aur apkai paas batteries nahi hai to ap sirf PV pai dependent hogai. Aesay mai inverter ko trip sai bachanay kayliay apna load bhi kaam krna hoga simple.
You can run a hybrid inverter without batteries on PV+Grid in normal case and with only PV during day time grid outage if you manage the load.
Batteries are still too expensive and not worth it from a ROI perspective in my opinion.
exactly..... Paai koe gusssa nikal raha hai... apna
Agree beteris bht expensive hain ab drop taiz jo gi to load chlata hai ager drop kam hai to load b kam krna ho ga to kam chlay ga.... ab ye to pagal pan hai drop kam hai or sab kuch on kia hwa hai load kam kro kse nae chaly ga.... betry b laga lo phirnye socho k g soler laga hai sab free chly ga ohir paway dhop na niklo ho😅
Dhop kam ho to load b kam krna pry ga phir sae chaly ga....
Dhop kam ho to wo betry pr lay ae ga us k bad sham may lite gae to betry b khali😅 phir kia kry ga bnda.....
Load kam krna ka btao bhai logo ko....
Mai lagwao ga ab bagiar betry k sin may soler sag or wapda cut off.... usi solar say ghr ka ups b chrge ho ga sham ho gi to upes on jab betry kam ho gi to waoda on simple subha phir soler chalo phir betry b charge ups say
Very good good sir 👍😌
exactly. loadshading pr load trip ho jata hai.
Good infomation sir
So nice of you
Mashallah you are right
Thanks dear
Jitni ki batteries aati hain,,aap utna extra pv lga lain.humesha aisa inverter choose kren,jiska pv zyada ho as compare to output load.masla hal ho jaye ga ,,batery se jan chut jaye gi
not agreed.jitny b pv laga lo jesy hi badal aain gy inverter trip kr jye ga.
right Shahid Kaleem sahib
good work
khair mery pass tu pehly se hi is ki info hai.
THANKS
Absolutely right
نیٹ میترنگ کرا لیین بجائے بیتریان رکھنے کے ۔ایک یو پی ایس لگا لیین 12 وولٹ کی ایک بیتری والا ۔ساتھ واپڈا شیرنگ چلائین ۔یونٹ خود ہی امپورٹ ایکسپورٹ ہوتے رہین گے
Ham ny kal net metering ki ha bhai but pahly kah rhy thy ky ap log battery na lagain ab kah rhy hain lagao .yeah kia bat hoi jab wapda nai ho gi to invertor hybride ha direct kiun ni Ac chala sakta 🤔🤔🤔
بھائی پاکستان سندھ میں نیٹ میٹرنگ نہیں ہے۔۔
البتہ پاکستان پنجاب میں نیٹ میٹرنگ ہے۔۔
Mane ongrid with net metter laga huwa hy.
6.2kw solar inverter without battery - 4500 watt solar panel
2 ac 1 ton k DC inverter aasani se use kr rahy hai light free ha sb
mere paas long life 3.5kw inverter he without battery or wapda chalta he alhamdolilla
Konsa inverter and price
@@WaqasAhmed-hv5rn long life 3.5kw bro or jitne bhi vm2 vm3 inverter aate hein sab chalte hein
Master sb tussi chah gae ho
What kind of batteries were you using. Are they lithium ion like the Tesla wall, or Lg Lithium ion. Both these come with 10 year warranty’s in the US
Good sir g
Honest opinion
Good explanation.i experienced the same situation.
Bhai jaan agar inverter band ho jaye to ac wagira kharab tu nahi hote aur inverter
@@Rrizwan aesa kuch nhi hai
Proud of you
My question is can hybrid system be used as only grid tied? In hour of load shedding to trip completely? The problem with hybrid is very well explained.
Did you get answer.?😢
Bilkal thek bat btae apny inverter ko 2nd source mila wa ho to ye work sae krta chaey wapda sharing ho ya battery...mene knoxx 3kw argon 4500 lgya sath 4 panel attached keay abi 575 Canadian byfical..only pv py frigde non inverter.+ Fans ni chlty but wapda sharing py koi issue ni hota ..halnk wapda Sharing m 0 ampire show hota ...bas 2nd source available hona chaeay ...
i solute master sab
good.
Nice
101% Agreed
👍👍👍👍👍👍
Masha Allah
Ik question h..3000w stabled ni hai ok..2000w bh stabled h to 1000w to use ho skty h phir bh...solar zrurt h.local invertor bht cheap h as compare to any imported invertor..repair krna bh asan or cost effective h.local 3kv invertor k sath 6 plate ka system 3 lkh tk install ho jata h...to mera ni khiyal k din time me jitni mrzi load shefing ho 100w sy nichy phir bh aye ga
❤❤❤❤❤❤❤❤❤
good idea
Good work
Thanks 😊
Boht ashi malomati viedieo ha
Sahi bat hy bilkul
Inverex veyron 2 is working perfectly fine without batteries
Nice 👍
💯% true
correct
I am agreed
AOA. Sir kia Ap battry sy raat ko Fan ka load ly sakty hain?
Sir U R right
❤
4.5 kv Zewnic lagana hai, backup naheen chahye. Chhoti battery kitnay amp ki honee chahye?
very true
🌹🌹
Dear main nay tesla hole sirf pv pay chalay hain wo bilkul baghai bettery kam kar rakhay hain
AoA, Shakoor Sb AP khariyat Sy hn. Kafi arsay Sy AP ki koi video nahi AA Rahi, Allah Pak AP ko sahat atta farmay.
use dual output inverter for auto management of load simply
Load Shieding jahan nahi to phir kon pagal lagaye ga..
بھائی صرف اپنا بل کم کرنے کے لیے لگایا جاتا ہے ہمارے پاکستان میں ایک سوسائٹی ایسی بھی ہے جہاں لائٹ نہیں جاتی بحریہ میں ڈی ایچ اے میں بڑی بڑی سوسائٹیوں میں لوڈ شیڈنگ نہیں ہوتی
Load sa zeyada solar panels installed hon tab bhi yahi masla raha ga?
Good
IT CAN BE SOLVED BY INTELLIGENT INVERTOR BY SETTING PERFERENCE BY APP . ITS AUTOMATICALLY KEEP MANAGING
Hi, I have installed Afore 6 KW Single Phase Hybrid Inverter Model No. AF6K-SL . All the load has been connected to EPS out. The onverter is installed without batteries. However whenever, PV is powered off through DC breakers or at night the EPS load is not shifted to Main Grid Source and is turned off. How to resolve this issue. Lastly what is difference between GridFeed and GridBack
If u have 3 kv inverter without Betary u extend maximum 10 solar plate 575w then your problem dissolved. If u have UPS then good for night.
Torque Load par nai chale ga , like ac fridge motor, and load aik dam load dal do to trip hojaye ga because solar panel ya solar inverter jitna load hota hai chal raha ho
@pro bro bhai apna num dengy thori info chaye mea b withoit battery lgwaana chara hu
بھائی جان آپ ساڑھے آٹھ ہزار واٹ لگا کر تین ہزار واٹ کا لوڈ لے رہے ہیں
وہ بھی پیک اور میں آپ ادا لوڈ بھی نہیں لے پا رہے جس دن بادل ہوں گے کچھ نہیں چلے گا
Jase ups ka load hum devide karte hain jase 1room ma 1 fan or 1 bulb aisay he use karo to i think without battery chaly ga
G
زبردست شکریہ
🥰🥰🥰🥰🥰🥰🥰🥰
Sir g agar baghair battery waly inverter 3.2 ko laga kar os k aagy ups lagaya ja sakta hai? single battery wala light load k lye jasy pankha aur light waghaira ups par chal jaeyn
اس کا بلکل کوئی فائدہ نہیں آپ تھری پوائنٹ ٹو کے اوپر دو بیٹری لگا لیں
ایک بیٹری آپ کے پاس ہے دوسری بیٹری پرچیز کرلی آپ کو زیادہ لوڈ اور زیادہ فائدہ ملے گا شکریہ
🇵🇰 پاکستان زندہ باد 🇵🇰
Plz guide me.me 3.5kilowat inverter k sath 315 ka solar panel 24 v waly kitny attach krny hain or kitny bateeries lagany hain...off grid hai.no wapda.plz guide me
آپ دس پینل لگا سکتے ہیں
لیکن 5/5 کی دو سیریز کرنی پڑیں گی
اور پھر اس کو پیرلر کر کے لگا دیں
ان شاء اللہ کوئی مسئلہ نہیں ہوگا
Is par load km dal lo or es se ek charger lga k battery chrge kro
بھائی میں sofar کا انویٹر لینا چاہتا ہون کیا وہ صرف ایک Ac پر کام کرے گا
Agar solar increse kar len tu?
Mere sath yehe ho raha same
O bhai panel barha do , battery wala kam fazul hai ….. thori research kr leni thi phly lolzzzz
Sir ak baat bx yie pochni thi k agr muje grid inverter may battery add krni hay tw kiya krn.
جسٹ ان گریڈ سسٹم میں بیٹری نہیں لگتی بیٹری کے لیے ہائبریڈ سسٹم لگانا ضروری ہے
ہمارا انورٹر واپڈا شئیرنگ کریں تو پھر سولر موڈ پر شفٹ نہی ہوتا۔ بیٹریاں ابھی نہی لگائیں۔