Daikin | How to fault find (Error E6)

Поделиться
HTML-код
  • Опубликовано: 29 окт 2024

Комментарии • 62

  • @pitaahgotchakot8344
    @pitaahgotchakot8344 Год назад +1

    Hi Bony am young ac technician from south sudan i have gain most of my skills from you thank you.

  • @todmabotesimbine6588
    @todmabotesimbine6588 3 года назад +1

    Hi Bon MJ, may name is Todmabote, i'm from Mozambique, technician being 20 years, usually work with daikin, and i find your videos very Usefull on my daily fault find.Thank you so mauch Bon

    • @BonMj
      @BonMj  3 года назад

      Thanks watching my video.

  • @SeinWinHtun105
    @SeinWinHtun105 10 месяцев назад +1

    I always study the Daikin air-con. Thanks you Sir.

    • @BonMj
      @BonMj  10 месяцев назад

      You are welcome

  • @todmabotesimbine6588
    @todmabotesimbine6588 3 года назад +1

    I's my pleasure Sir..Your videos are changing significantly my fault finding on vrv system..Keep it up

    • @BonMj
      @BonMj  3 года назад

      Thanks

  • @sulthanabdulkadar8161
    @sulthanabdulkadar8161 3 года назад +1

    Very useful video... Thanks bro... Keep it up

    • @BonMj
      @BonMj  3 года назад

      Thanks bro

  • @sotirisgrig1406
    @sotirisgrig1406 3 года назад +1

    Μπράβο φίλε!

    • @BonMj
      @BonMj  3 года назад

      Thanks

  • @faisalsiregar6409
    @faisalsiregar6409 Год назад +1

    good morning Mr. BON MJ i have a question for ada. I have a DAIKIN 5PK AC with Model R125LUY14 error code E6. Does every problem with Daikin Ac with error code E6 always have to replace the compressor or is there another way to fix it?

  • @m.haslam8495
    @m.haslam8495 3 года назад +3

    If you have determined that one standard compressor is faulty (E6), are there any other parts that need to change at the same time like Inverter PCB board and will any of the other compressors be affected. Look forward to your reply.

    • @BonMj
      @BonMj  3 года назад

      If you confirm is standard compressor faulty.just replace the standard compressor.
      E6 u must check the current sensor.
      If caparally tube gas leak,please recommend change all the compressor.

    • @m.haslam8495
      @m.haslam8495 3 года назад +1

      @@BonMj Thank you so much for quick reply. Much appreciated Sir.

  • @hvacandvrvspecialvedoindus7891
    @hvacandvrvspecialvedoindus7891 2 года назад +1

    ❤️❤️❤️❤️☺️

    • @BonMj
      @BonMj  2 года назад

      Thanks

  • @jihanjalil5175
    @jihanjalil5175 2 года назад +1

    Good luck

    • @BonMj
      @BonMj  2 года назад

      Thanks

  • @welcometomydreamworld6812
    @welcometomydreamworld6812 3 года назад +1

    Thnxx

  • @brandonle4930
    @brandonle4930 3 года назад +1

    Good video!!!!!!

    • @BonMj
      @BonMj  3 года назад

      Thanks

  • @femshifemshi5895
    @femshifemshi5895 Год назад +1

    Nice

  • @sharjahraja6146
    @sharjahraja6146 3 года назад +1

    Hi Bon thanks

    • @BonMj
      @BonMj  3 года назад

      Welcome

    • @sharjahraja6146
      @sharjahraja6146 3 года назад +1

      @@BonMj could you please share your email

    • @BonMj
      @BonMj  3 года назад

      bonmj81@gmail.com

    • @harta9aaat779
      @harta9aaat779 3 года назад +1

      Thank you soo much ,for all of your video.

    • @BonMj
      @BonMj  3 года назад

      @@harta9aaat779 thanks bro

  • @karimchiu7527
    @karimchiu7527 Год назад +1

    Gan En sir Bon

  • @adelinochimbungule
    @adelinochimbungule 3 года назад +2

    Its good

    • @BonMj
      @BonMj  3 года назад

      Thanks bro

  • @harta9aaat779
    @harta9aaat779 3 года назад +1

    Thank you mr bon , can i ask about the emergency mode for standard compresseur 2 , and inverter 2 compresser " slave outdour "
    19 for the standard compresseur 2 ,with twice click on set ?
    Deactivation with 1 click on set button ?
    And how about inverter 2 compresseur" slave 1 " emergency setting .
    42 with twice click on set button
    And desactivation with 1 click on set button ?

    • @BonMj
      @BonMj  3 года назад

      Long press mode button till light 1 up.
      Press set button 19 times
      Press return button 1
      Press set button 1
      Press return button 2
      Press mode to exit

    • @BonMj
      @BonMj  3 года назад +1

      VRV3 only one inverter compressor.
      (Dun have inverter 2 compressor)
      If multi outdoor unit.
      Only can deactivate the slave cu.

    • @harta9aaat779
      @harta9aaat779 3 года назад +1

      Ok thank you soo much sir

  • @jairam425
    @jairam425 2 года назад +1

    Hii sir this settings can use vrv-x inverter compressor

    • @BonMj
      @BonMj  2 года назад +1

      VRV3 abd VRV4 is different

    • @jairam425
      @jairam425 2 года назад +1

      Thanks for reply

  • @janshaw5472
    @janshaw5472 3 года назад +1

    thanks MJ I am new at aircon. can learn from you ??😀

    • @BonMj
      @BonMj  3 года назад

      Hi..Jian Shao
      Sure..no problem.

  • @sandykaith9805
    @sandykaith9805 3 года назад +1

    Sir I just changed standard compressor 1 ... Vrv 3 .but indor not so cool ... How much maximum apm for standard 1 and standard 2..

    • @BonMj
      @BonMj  3 года назад +1

      Around 8 amps

    • @BonMj
      @BonMj  3 года назад

      What is the pressure reading.

  • @mohdmaqsoodshaikh5234
    @mohdmaqsoodshaikh5234 2 года назад +1

    Sir stended compressor 1 on but 2 compressor not start puss contector 1/2 amp ok but 2 compressor not start and errors e6

    • @BonMj
      @BonMj  2 года назад

      Please double confirm is standard 1 or standard 2

  • @TheRamsis2
    @TheRamsis2 3 года назад +1

    Plz how much BTU in vrv 3 8hp

    • @BonMj
      @BonMj  3 года назад

      72,000btu

  • @nikithasethu5922
    @nikithasethu5922 3 года назад +1

    How to check j2 error condector or current sensor which one defect.

    • @BonMj
      @BonMj  3 года назад

      U can measure the current sensor coil reading

  • @elvinrozzaq7820
    @elvinrozzaq7820 3 года назад +1

    Mr. Bon MJ, saya ingin reset E6 untuk yang pertama bisa di reset dan muncul ampernya, terus untuk yang kedua kali saya reset kok ngga bisa... Kenapa ya ?

    • @BonMj
      @BonMj  3 года назад

      E6 biasa starting amps nya lebih pada 10amps.
      E6 mahu check amps ya ,standard compressor starting amps dan juga running amps, tidak boleh lebih pada 10amps.

    • @elvinrozzaq7820
      @elvinrozzaq7820 3 года назад +1

      Terimakasih Mr. Bon mj...
      Kompresor standard yang no. 2 udah over current mencapai 14 ampere terus drop (0 ampere)...
      Yang mau saya tanyakan, cara setting emergency tombol untuk yang kedua kali melihat amperenya kok ngga bisa ? Please help me... (Step by step)

    • @elvinrozzaq7820
      @elvinrozzaq7820 3 года назад

      Gimana caranya biar kompresor standard no.2 bisa bekerja ( code errors E6 ) saat saya setting emergency kedua kali gagal terus... Mohon infonya Mr. Bon mj

    • @BonMj
      @BonMj  3 года назад

      @@elvinrozzaq7820 single CU or Multi CU

    • @BonMj
      @BonMj  3 года назад

      @@elvinrozzaq7820
      Emergency setting standard2 compressor
      1)Tekan MODE lebih 5saat sampai lampu H1P menyala.
      2)Tekan SET 19 kali
      3)Tekan RETURN satu kali
      4)Tekan SET satu kali
      5)Tekan RETURN 2 kali
      6)Tekan MODE satu kali

  • @sachinshettyacwork1102
    @sachinshettyacwork1102 3 года назад

    I want to larn vrv work

  • @pawankumar-er3rr
    @pawankumar-er3rr 3 года назад +1

    🙏 🙏 जय श्री राम 🙏 🙏