    when we conect LPS earthing rods with the main earthing bar is the ohmic resistance for LPS earthing system should to be Equale the min. ohmic resistance for other systems ?
    or we make one integrated earthing rods and measure the resistance for all of them?

    • @DEHN-International
      @DEHN-International  Год назад

      @Eng.Mahmoud Eid: Thank you very much for your question. There should always be a single, integrated grounding system for all purposes (lightning protection, power supply, telecommunications equipment, etc). EN 62305-3 standard specifies that the grounding resistance should be less than or equal to 10 ohms. Here, the entire grounding system is always measured. If the grounding resistance is then higher than 10 ohms, additional depth grounding electrodes can be installed until the desired resistance is reached.
      Greetings from Neumarkt,
      Your DEHN Social Media Team

  • @vasudhaearthing1302
    @vasudhaearthing1302 5 лет назад

    very good... what is the minimum length GRP (insulator) and air termination system....

    • @DEHN-International
      @DEHN-International  5 лет назад

      @Vasudha Earthing: The length of the insulation of our HVI power conductor (part no 819 430) is 1835 mm. You can find that information in the drawing in the top right of the specification sheet: de.hn/en/a/819430