JIGNESH PATEL a HART AI or AO module can communicate to HART devices for re-ranging or reading a second variable for a transmitter. It can do all this while still using the conventional 4-20 mA signal. Foundation Fieldbus (FF) is strictly a digital only protocol and not compatible with 4-20 mA. You can have multiple devices on a FF segment that are hooked in parallel and all communicate back to the FF module. This saves on wiring. FF Fieldbus devices are also capable of executing logic right in the device.
I have never tried making this mode change from a Trex Communicator. Is your system using Foundation Fieldbus? Otherwise, I don’t think you can use the Trex to make the change.
JIGNESH PATEL I teach in a two-year Instrumentation Engineering Technology diploma program at Red Deer College in Red Deer, AB in Canada. Here’s a like to our program. We are open for applicants for the fall (September) of 2021. www.rdc.ab.ca/programs/engineering-and-technologies/instrumentation-engineering-technology-diploma
HERMAN NELSON KUETE I have about 10 other videos for DeltaV that might be of interest to you. Have you seen the others? If you search my name along with “DeltaV 12.3.1” this should bring up most of the videos. I setup some graphics and PID blocks in the other videos.
I would love to, but sorry I am busy teaching other courses at the moment. We do have wireless HART gateways. If I find some free time, I will definitely make a video!
I haven’t use Oviation DCS, only DeltaV. But I see Oviation is an Emerson product. To download DeltaV you need to have access to a Guardian account at guardian.Emerson.com. To have access to Guardian you need to have purchased a Guardian Support contract. If the company you work for has Guardian Support, you should be able to gain access.
If you download the card and the controller still has a blue triangle, you will need to download the controller as well. I may have went one level too high in the video, you may only need to download the controller when you add a whole new card to the DeltaV system. If downloading just the card removes all blue triangles, you are good to just do the card. Thanks for checking!
I’m sorry. I’m not familiar with ORCAView. It is a different piece of software in this video. This video is for Emerson’s DeltaV control system, not ORCAView.
This is Emerson’s DeltaV DCS: www.emerson.com/en-ca/automation/control-and-safety-systems/distributed-control-systems-dcs/deltav-distributed-control-system
@@rockmacwan3533 haha, okay. DeltaV Explorer is where you enable inputs and outputs. Control Studio is where you program logic and DeltaV Operate (Configure) is where you configure the graphics.
THANK YOU FOR SHARING GOOD SKILL!!
林士航 no problem! I’m glad I could help!
Thank you
Great knowledge sharing sir..
I want to know about what is difference in HART AI,AO AND FF MODULE IN DELTA PROGRAMMING
JIGNESH PATEL a HART AI or AO module can communicate to HART devices for re-ranging or reading a second variable for a transmitter. It can do all this while still using the conventional 4-20 mA signal.
Foundation Fieldbus (FF) is strictly a digital only protocol and not compatible with 4-20 mA. You can have multiple devices on a FF segment that are hooked in parallel and all communicate back to the FF module. This saves on wiring. FF Fieldbus devices are also capable of executing logic right in the device.
Good day sir, please do you conduct training on complete installation configuration and maintenance. I am really interested.
Sorry, I do not. Emerson offers training.
Who is the manufacture of the control valve - it looks to be electric - would love to get one. Great video.
Blair MacInnis The valve is made by Samson.
Sir ,the Actual mode of the analog input AI block of my Level transmitter is in OOS can i change this using trex communicator?
I have never tried making this mode change from a Trex Communicator. Is your system using Foundation Fieldbus? Otherwise, I don’t think you can use the Trex to make the change.
Are u taking classes ?, I am interested sir
JIGNESH PATEL I teach in a two-year Instrumentation Engineering Technology diploma program at Red Deer College in Red Deer, AB in Canada. Here’s a like to our program. We are open for applicants for the fall (September) of 2021.
www.rdc.ab.ca/programs/engineering-and-technologies/instrumentation-engineering-technology-diploma
Great video sir. Please can you make a sample project video using DeltaV
HERMAN NELSON KUETE I have about 10 other videos for DeltaV that might be of interest to you. Have you seen the others? If you search my name along with “DeltaV 12.3.1” this should bring up most of the videos. I setup some graphics and PID blocks in the other videos.
Can you add a tutorial for a wireless set up. Thank you.
I would love to, but sorry I am busy teaching other courses at the moment. We do have wireless HART gateways. If I find some free time, I will definitely make a video!
Hello sir can I download this software for learning Ovation DCS?
I haven’t use Oviation DCS, only DeltaV. But I see Oviation is an Emerson product. To download DeltaV you need to have access to a Guardian account at guardian.Emerson.com. To have access to Guardian you need to have purchased a Guardian Support contract. If the company you work for has Guardian Support, you should be able to gain access.
master, why download the controle completely and not just the card?
If you download the card and the controller still has a blue triangle, you will need to download the controller as well. I may have went one level too high in the video, you may only need to download the controller when you add a whole new card to the DeltaV system. If downloading just the card removes all blue triangles, you are good to just do the card. Thanks for checking!
In orcaview showing multiple connection enabled how to resolve this problem?
I’m sorry. I’m not familiar with ORCAView. It is a different piece of software in this video. This video is for Emerson’s DeltaV control system, not ORCAView.
which sofware is this sir
This is Emerson’s DeltaV DCS: www.emerson.com/en-ca/automation/control-and-safety-systems/distributed-control-systems-dcs/deltav-distributed-control-system
I know that but which software did u open to configure new tag in delta v thats what m askin
@@rockmacwan3533 haha, okay. DeltaV Explorer is where you enable inputs and outputs. Control Studio is where you program logic and DeltaV Operate (Configure) is where you configure the graphics.
@@AutomationCliff thank you very much
@@rockmacwan3533 your welcome!
I tried but the option is not editing
Ok, is this a Foundation Fieldbus device? Are you not able to make this mode change from DeltaV? What version of DeltaV are you using?
Hello sir
Hello to you too!
please provide a video on serial communication in delta v MQ controller
parammukku I would love too, but I do not have a DeltaV M-series serial module for making the video. If I did, I would definitely make a video!