How do you troubleshoot an aircon LEV valve | Mitsubishi VRF

Поделиться
HTML-код
  • Опубликовано: 26 июл 2024
  • Brand : Mitsubishi Electric
    model : PDFY-P100VM-E (FCU-Ducted)
    Error code : no error.
    Complaint : aircon not cooling
    Symptoms : One of the FCU LEV fully open, CU TH 4 reading very low.
    Cause : LEV faulty
    #bonmj #mitsubishi #vrf

Комментарии • 49

  • @jonathanlarosa3279
    @jonathanlarosa3279 2 года назад +1

    Thank you Master 👌👏👏👏🙏🙏
    I watching all your vlogs at RUclips 👍🏾 very useful to me as AIRCON TECHNICIAN... thanks & More blessings to come.. stayed healthy and safe

    • @BonMj
      @BonMj  2 года назад +1

      You are welcome. Cheers.

    • @maharaja.s4628
      @maharaja.s4628 2 года назад +1

      OK bro thank you

  • @phillipcase8036
    @phillipcase8036 2 года назад +1

    Thank you you for the video keep them coming

    • @BonMj
      @BonMj  2 года назад

      Welcome

  • @goparismail9727
    @goparismail9727 2 года назад

    thank you mr bon sukses selalu ilmu yah goood👌👌👌👌👌

    • @BonMj
      @BonMj  2 года назад

      Terima kasih master.

  • @matazglb5346
    @matazglb5346 2 года назад +1

    Thanks you Boos 👍👍👍

    • @BonMj
      @BonMj  2 года назад

      Welcome

  • @karaors8970
    @karaors8970 2 года назад +1

    Lev outdoor nice Job bro

    • @BonMj
      @BonMj  2 года назад

      Thanks

  • @jaykenlopez6771
    @jaykenlopez6771 3 месяца назад +1

    Good day sir. What kind of software did you use to know the exact location of damage lev? Thanks

  • @kishoorre6930
    @kishoorre6930 2 года назад +1

    Thank you sir

    • @BonMj
      @BonMj  2 года назад +1

      Welcome

  • @vijaygani1179
    @vijaygani1179 2 года назад +1

    Thanks🙏🙏🙏

    • @BonMj
      @BonMj  2 года назад

      Welcome

  • @peramaraj2763
    @peramaraj2763 10 месяцев назад +1

    Hi sir i have a doubt sir can you see mitsubishi in CRC control every indoor unit address ?

  • @sonnyfuellas6208
    @sonnyfuellas6208 2 года назад +1

    Hello sir LG vrf you Also know. Tnx a lot

  • @edwinneilnovoa1047
    @edwinneilnovoa1047 2 года назад +1

    Good morning friend bom ,how are you? I

  • @edwinneilnovoa1047
    @edwinneilnovoa1047 2 года назад +1

    Good morning friend Bom haw are you?
    Iwanted to ask you if coold helpe.me
    I have a problem with .
    a misubishi havey vrf modelo fdc 560kxe6m .
    air conditioner. The compressors were changen becausse the were burt ,but the machine
    Dose not want to start .it is totall dead it does no give a start
    Sigñal but it does get power ,thenks friend bom happy day many blessing

  • @CCL13984
    @CCL13984 Год назад +1

    Hi sir, I never seem this installation method to LEV, have any side effect by new LEV in external connect without remove the old valve?

  • @g8s456
    @g8s456 2 года назад +2

    I have fault code 1302 on a similar system happening intermittently when I am not on site . Any tips ?

    • @BonMj
      @BonMj  2 года назад +1

      May high pressure over 550psi
      Or thermistor fault
      Or indoor lev
      Or solenoid valve clogged
      Or dirt heat exchanger
      Or indoor air short cycle
      And etc....

  • @muruganantham595
    @muruganantham595 Год назад +1

    Sir ,can we install the new valve in external connection without removing the existing valve from coil for the indoor ?

    • @BonMj
      @BonMj  Год назад

      Can,suggest remove the lev coil.

    • @muruganantham595
      @muruganantham595 Год назад +1

      Thanks for the suggestion sir

  • @shaikhsayeed6456
    @shaikhsayeed6456 2 года назад +1

    Sir please MITSUBISHI ELECTRIC CRC how to settings

  • @CircinusMusic
    @CircinusMusic 2 года назад +1

    Sir bon, Possoble to rectify without loptop if i replace LEV? should i check only at control panel monitor

    • @BonMj
      @BonMj  2 года назад +1

      Can..set fan mode to test and one of the unit set at cool mode to let compressor running.

  • @hairussalleh2087
    @hairussalleh2087 Год назад +1

    Hello sir , can i ask something? where and how to get the inverter checker box? also the software for mitsubishi aircond?

    • @BonMj
      @BonMj  Год назад

      From Daikin and Mitsubishi

  • @krishnaajaayajayaprakas5475
    @krishnaajaayajayaprakas5475 2 года назад +1

    Hi uncle mitsubishi heavy industries VRF is not working E49 what problem

  • @josephngmh2815
    @josephngmh2815 2 года назад +1

    Mr Bon, can let me know where can I purchase the diagnostic software?

    • @BonMj
      @BonMj  2 года назад

      Mitsubishi electric

    • @josephngmh2815
      @josephngmh2815 2 года назад

      U meant I could buy the diagnostic software from Mitsubishi electric?

  • @maharaja.s4628
    @maharaja.s4628 2 года назад +1

    Good morning bro, my daikin aircon got error code U4.I check out door power supply have, no power tripped, once reset Power supply again unit runing back to normal, any other reason bro for u4 error code

    • @BonMj
      @BonMj  2 года назад +1

      Check your indoor connect to any fire alarm or smoke detector

  • @karaors8970
    @karaors8970 2 года назад +1

    🍻🇹🇷🤳🛠️✋

    • @BonMj
      @BonMj  2 года назад

      Thanks

  • @idreesahemad5348
    @idreesahemad5348 Год назад +1

    sir wich country doing the job

    • @BonMj
      @BonMj  Год назад

      Singapore

  • @yadhukrishnacs995
    @yadhukrishnacs995 Год назад +1

    In my LG VRF FCU eev valve continue open in fan mode also cooling, what is the problem pls help me master.

    • @BonMj
      @BonMj  Год назад

      Most is eev or pcb

    • @yadhukrishnacs995
      @yadhukrishnacs995 Год назад +1

      @@BonMj while fcu switch offing the gas is circulating

    • @BonMj
      @BonMj  Год назад +1

      @@yadhukrishnacs995 yes.eev unable to close. (eev or pcb,)

  • @sirawing828
    @sirawing828 2 года назад +1

    if you have replaced the LEV but the LEV still doesn't open, where is the problem, sir?

    • @BonMj
      @BonMj  2 года назад

      Do you remove the faulty LEV

    • @BonMj
      @BonMj  2 года назад

      After replace need to reset outdoor.
      Of power supply and on back.