310.15(E) Neutral Conductor

Поделиться
HTML-код
  • Опубликовано: 7 фев 2022
  • Explanation of when and why we count a neutral as a current carrying conductor for the purpose of derating (ampacity adjustment).

Комментарии • 78

  • @joeljahnke9000
    @joeljahnke9000 Год назад +25

    Dave, you are an exceptional teacher. I appreciate, so much, your organized and sequential manner in which you teach. You rock!

  • @Calico5string1962
    @Calico5string1962 Год назад +11

    Your video presentations are simply the BEST I have ever watched. So we'll explained and presented.
    As an industrial/commercial electrician for over 40 years, I really enjoy watching your stuff! It's always a great refresher for me.
    Thank you, Dave, for sharing your knowledge and insight!

  • @JesseKlaus
    @JesseKlaus 8 месяцев назад +6

    This is probably the most thorough explanation of shared neutrals I've seen - well done.

  • @danielelise7348
    @danielelise7348 10 месяцев назад +5

    This guy actually makes learning this complex stuff enjoyable.🤔⚡

  • @khanhho8471
    @khanhho8471 Месяц назад

    Thank you Dave.
    You make it very easy to understand.

  • @stephendavis6408
    @stephendavis6408 Год назад +6

    Clear and concise explainations of both the theory and the NEC. Thank you.

  • @pamdemonia
    @pamdemonia Год назад +5

    That was great! Wish you had been my code teacher when I was an apprentice!

  • @michaeldonnelly2977
    @michaeldonnelly2977 Год назад +4

    THANK YOU! I was looking for an explanation of exactly HOW current can possibly flow back to the source through the second hot leg on a multi wire circuit, from an electrical theory point of view. You explained it very simply and eloquently with your “trading post“ analogy. Thank you, sir! This was very, very helpful!

  • @bahbee5659
    @bahbee5659 Год назад +4

    “Oop, keep my thumb down.” A great educator & can bring a smile to my face👍

  • @soundman2604
    @soundman2604 11 месяцев назад +1

    Best teacher ever, and above all correct!

  • @martf1061
    @martf1061 Год назад +2

    16:35
    Thank you. Now i understand why, sometimes, the engineers asked for a double wired neutral in transformers.
    I learned more in 2h watching your explainations, than i did in 20 years .
    I suggest you do some videos about motors.

  • @doctorgoodwrench
    @doctorgoodwrench 2 года назад +5

    Thanks for continuing to post, Dave. Your explanations are remarkable.

    • @davegordon6819
      @davegordon6819  2 года назад +1

      Thanks for your vote of confidence, and thanks for engaging with the other viewer. I put a link to my new "open neutral" video in the responses below if you're interested.

  • @charlieperez6844
    @charlieperez6844 7 месяцев назад +2

    Im so glad i subscribed to your channel. Your videos have helped me understand a bit more. Thank you!

  • @johnnyelectric7572
    @johnnyelectric7572 Год назад +1

    again....just a great Teacher. Thanks!

  • @benfurnish9948
    @benfurnish9948 Год назад +1

    Fantastic video. It makes total sense now. Plus a bonus for having the Soli Deo Gloria posted.

    • @davegordon6819
      @davegordon6819  Год назад +2

      Thanks brother. I am thankful for God's mercy to me and may He help us both to use what He has given us for His glory.

  • @renediaz5162
    @renediaz5162 Год назад

    Thanks for the awesome and useful class!

  • @DanielRamos-bq8py
    @DanielRamos-bq8py Месяц назад

    excellent job sir ! well explained and much appreciated !

  • @michaelcostello6991
    @michaelcostello6991 Год назад

    Excellent lecture. So well explained. Cannot think of any questions after this

  • @ryanjourneymanwireman4937
    @ryanjourneymanwireman4937 Год назад +1

    One of the best electrical videos I've seen (hoping info is correct) but thanks

  • @paulmullen573
    @paulmullen573 Год назад +5

    Great videos, Dave. A suggestion... a set of videos on Grounding and Bonding would be super helpful. I understand the concepts, but I don't understand how the grounding and bonding topics are organized in the NEC and I spend a lot of time flipping pages to be sure.

  • @mcarroll598
    @mcarroll598 Год назад

    Excellent explanation!

  • @mph5986
    @mph5986 2 года назад +2

    Clearly and easy understand. 👍

  • @Lazdinger
    @Lazdinger Год назад

    Soli Deo Gloria for this man’s videos.

  • @user-xw5ve7nc9k
    @user-xw5ve7nc9k 10 месяцев назад +1

    Thank you very much.

  • @MrKandela10
    @MrKandela10 Год назад

    the best explanation!

  • @michaelarriaga08
    @michaelarriaga08 Год назад

    Excellent video thank you so much

  • @ochoaelectric5175
    @ochoaelectric5175 Год назад

    Nicely done

  • @abigalanderson7494
    @abigalanderson7494 Год назад

    I like how Dave puts the code section next to his pictures

  • @ramonqo1
    @ramonqo1 Год назад

    You are the best.

  • @daveculbertson602
    @daveculbertson602 Год назад

    Very informative video.

  • @TheCompton1963
    @TheCompton1963 Год назад

    Dave is the best! 🧑🏻‍🏫

  • @Peace88Hi
    @Peace88Hi Год назад

    Thank you prof.

  • @tfun101
    @tfun101 9 месяцев назад +1

    At 6:40 I was like….”ohhhhh duh” and it all finally made sense. 🙃

  • @xevierred6330
    @xevierred6330 Год назад

    Fascinating

  • @justd3123
    @justd3123 Год назад

    so clear, tnx

  • @safetythirdified
    @safetythirdified Год назад

    Where have you been all my life!

  • @chadhardwick9214
    @chadhardwick9214 Год назад +1

    Dudes a correction factor ninja….😎

  • @tommywatterson5276
    @tommywatterson5276 5 месяцев назад

    I remember something about neutral ampacity rating at 70% of phase voltage

  • @brentcory8194
    @brentcory8194 2 года назад +1

    Great video! So am I correct in saying in most commercial applications i.e. office buildings, schools, medical offices, etc. we should be counting the neutral due to 310.15(E)(3)?

  • @morelightpm457
    @morelightpm457 Год назад

    Excellent video.
    JW - LU #613

  • @RustyJeepHole
    @RustyJeepHole Год назад

    Thank you sir

  • @mariogregory4922
    @mariogregory4922 Год назад

    I like Dave!

  • @NeoN-PeoN
    @NeoN-PeoN 5 месяцев назад +1

    Is it not the case that basically all home setups are unbalanced? I mean, no one is going through their homes and adding the amps up on each circuit to ensure they're balanced. So in the neutral is probably always carrying current, right?

  • @warrenjtaylor8714
    @warrenjtaylor8714 2 месяца назад

    The first system is slightly wrong i thought because the coils are wound in opposite direction, so line to line is 180 out of phase. Hence the 'split'. Also tell them it's a voltage source not current source if any load asks...

  • @yusprogres5271
    @yusprogres5271 Год назад

    Yessss

  • @faroutdesign
    @faroutdesign 4 месяца назад

    Great video! I don’t get to work with a lot of wye systems. I have seen a 10 awg neutral on a shared system with non linear loads. Is this a code article requirement or just a good work practice?

  • @alyssaisaackson6797
    @alyssaisaackson6797 Год назад

    I have a 3 phase solar inverter combiner panel the load is balanced on all 3 phases. I don’t even think the neutral Carry’s current would I have to count it ?

  • @markchidester6239
    @markchidester6239 Год назад

    Is there a situation where the neutral wire needs to be larger gauge than the "hot" wires because it has the potential of carrying more amps than the "hot" wires?

  • @pakistanian2325
    @pakistanian2325 3 месяца назад

    May Allah bless u.❤

  • @Victorkorchemniy
    @Victorkorchemniy 8 месяцев назад

    “Counting the individual neutral, with one hot.” I get the electrical theory, but it’s not in writing in the code book. How come ? They should add a #4 to clarify that even though is common sense, it’s not mandated in code in specific writing

  • @brianskellenger9344
    @brianskellenger9344 2 месяца назад

    🎯

  • @ericthered9655
    @ericthered9655 2 года назад

    Why doesn't the voltage increase if the waves are out of phase?

  • @TheMinecraftACMan
    @TheMinecraftACMan 2 года назад

    For the single phase drawing at the top, where you had two separate multi-wire circuits, would it introduce the potential for any weirdness if the two non-shared neutrals were accidentally swapped?

    • @davegordon6819
      @davegordon6819  2 года назад +6

      Good question. If the two neutrals were swapped on the right side of the top diagram it could create a big problem. You would then have the lower black wire sharing a neutral with the upper black wire. The result would be that that neutral would carry the addition of the two black wires - meaning that if each was carrying 20 amps, the neutral would be carrying 40 amps. They would not cancel each other out. It would be like sharing a neutral between two wires from the same leg (bus) in a residential panel.
      This is why when we are working with 120/240 V single-phase panels we need to make sure that if we share neutrals, we share them between one wire from one bus and one wire from the other bus. Likewise, in other facilities where we run more than one multiwire branch circuit within the same conduit, we must identify which neutrals go with which phase conductors [see NEC 200.4(B)].
      Alternately, if you tied the two neutrals together, you could entertain similar issues depending on how much current is flowing on each hot conductor...
      I plan, at some point, to make videos that focus on current flow with the various systems and point out these sorts of problems.

  • @stevebrule6172
    @stevebrule6172 Год назад

    I have a tricky multiple choice question, hopefully someone with more knowledge can help me out
    A White/grey wire in a feeder circuit ________:
    A)Be bonded or have a circuit breaker
    B)Is the largest wire in that circuit
    C)Should not have a voltage to ground
    My notes:
    On the main panel, neutral is connected to the bar that is bonded with the panel, the green grounding wire is also connected to the same bar. (so does that mean the answer is A?)
    In the sub panel, the neutral wire is connected to the neutral bar which is isolated from the metal box with plastic between them, the Green grounding wire is separated and is connected to its own bar that is bonded to the sub panel box.
    In the circuit that this question applies to,
    --------- “The neutral wire is going to be sized larger than the Green grounding wire”
    (But that doesn’t mean it’s the LARGEST in the circuit right? Because the two hot wire could be the same size)
    --------"The neutral should have no potential difference(voltage) to the ground" (does that mean the answer is C?)
    (But that doesn’t mean it’s the LARGEST in the circuit right? Because the two hot wire could be the same size)

    • @muradzeynal
      @muradzeynal Год назад

      hey brother, did you find the answer? I want to know as well

  • @mikebavoso26
    @mikebavoso26 11 месяцев назад

    Very good. Does anyone know if Dave is a professor at a nationally recognized University?

  • @patricksmith2414
    @patricksmith2414 2 года назад

    Would the neutral count if it were a 4-wire, 3 phase wye connected system with only 1 phase conductor and the neutral?

    • @BG-eng
      @BG-eng Год назад

      Every time you have a single phase a neutral Carry the current back so that group is counted as 2 wires

  • @TM-cm4gb
    @TM-cm4gb Год назад

    Quite interesting, as european i wasnt sure how US 120/240V thing works but logical ofc. Fault with open neutral would cause all kinds of shenanigans in the the system then whereas in EU system it would fully turn off the circuit. I wonder if it is a problem with devices getting destroyed etc with that kind of fault.

    • @okaro6595
      @okaro6595 Год назад

      Three phase is common in Europe and in it the results are similar to what in the US split phase. On the other hand in the UK style single phase broken neutral puts full 240 V to equipment cases. In split phase and three phase it can be smaller than the full mains.

  • @Waffel-eb2gf
    @Waffel-eb2gf Год назад

    whta does it mean when you say "add heat" ?

  • @GailsonPvPwtf
    @GailsonPvPwtf Год назад

    *raises hand* If you take 2 of the hots in a 3 phase service to power a 1 phase device, wouldn't the voltage be irregular since the waves and troughs of the AC current aren't oppsite and balanced? Apprentice here.

    • @WorBlux
      @WorBlux Год назад

      Assuming a wye configuration - peak to peak Voltage across 2 phases is 2(cos(30)) of p2p-V on and single phase. So 208 on a 120 Wye. But it's still a regular sine wine. (Any addition of sine waves at the same frequency is another sine wave on that frequency.

    • @etherealrose2139
      @etherealrose2139 Год назад

      Power goes in and out both conductors. It's a perfect sine wave at whatever voltage the two are at line to line.

  • @jeanv4871
    @jeanv4871 2 года назад

    Hi Dave, my husband has some questions and wanted to know if you do one on one video calls plz let me know! Thank you!!

  • @dlp7130
    @dlp7130 2 года назад

    Hello mrs Dav.. so if the main neutral wire loose what is going to happen to the system?

    • @davegordon6819
      @davegordon6819  2 года назад

      If the neutral is still connected but loose, it could create a high-resistance point in the circuit that would not only get hotter than it should, but could create voltage drop due to the high-resistance point being in series with rest of the circuit.
      However, if you are asking what happens if it gets disconnected, then I'll refer you to a video I just made that addresses that exact issue of an "open neutral": ruclips.net/video/LJvyb_WujZg/видео.html

    • @dlp7130
      @dlp7130 2 года назад

      Thk you very much mrs Dave

  • @P8ntmagnit
    @P8ntmagnit Год назад

    What song is this?

  • @TrevorSachko
    @TrevorSachko Год назад +1

    Balanced load, don't use a neutral. Unbalanced load, use a neutral.

  • @grabir01
    @grabir01 Год назад

    Remove the earth ground. Then what you say is true.

  • @timault8209
    @timault8209 Год назад

    Dave... Why do you call power carried by a conductor "heat". I 'think' I know why. But can you explain your use of that word in the context of this lecture, please?
    (Notice, fellow viewers, that I ask DAVE... and not YOU... for Dave's explanation.)

  • @JAYDELROSARIQ
    @JAYDELROSARIQ 5 месяцев назад

    There are no harmonic you need flux

  • @abdelghanich7804
    @abdelghanich7804 Год назад

    hello, Dave i have a question and if you have a time answer me please , first of all thanks for every efforts that you give us
    so , In a single-phase transformer input, one wire getting entry as live, another as neutral. But what would be in case of its output? In output, which-wire would be phase, and which-one would be neutral?
    pasteboard.co/dlGFszYF6Iai.png

    • @BG-eng
      @BG-eng Год назад

      The system is AC, any one can be hot or neutral. but usually ground/bond is connected to one of the wire which is than identified as neutral. Let’s wait for Dave to comment further