Our reception area has high ceilings of 5/6m we need to turn on the high ceiling mode as high fan speed alone is not enough to get warm air down to floor level. The controller suggests that high ceiling mode is Mode number 13 (23) followed by first code 0 then we have second code numbers of 01 (normal 2.7m) or 03 (extra high >3.0). On our other floors setting option 03 actually reduces the fan output and you can hear the fan and airflow is less, setting it to 01 where you would expect it to be the least actually makes the fan speed up the fastest. Also on this controller there is an option for static pressure which is not available on the ducted units on the other floors so our reception ducted unit is clearly a diff unit. The issue is on the reception unit we cannot hear the fan anyway due to the height of the ceiling and the noise level from the busy street so we need to know the correct settings as they do not seem to correspond to what its saying in the field settings. Even the engineers when they come out are confused by this and say that code 03 is high ceiling mode even though this slows the fan down even slower. As the FM for this site I am having to resolve this myself now due to the call out costs. Anyone any idea on what is the correct settings? The system is about 6 years old now and is a big VRV system with some areas having localised controllers - the reception area included. The rest are controlled from itouch controllers in the riser cupboards.
good job Daikin . thanks for sharing 👍
Wow
Our
reception area has high ceilings of 5/6m we need to turn on the high
ceiling mode as high fan speed alone is not enough to get warm air down
to floor level.
The controller suggests that high ceiling mode is Mode number 13 (23)
followed by first code 0 then we have second code numbers of 01 (normal
2.7m) or 03 (extra high >3.0).
On our other floors setting option 03 actually reduces the fan output
and you can hear the fan and airflow is less, setting it to 01 where you
would expect it to be the least actually makes the fan speed up the
fastest. Also on this controller there is an option for static pressure
which is not available on the ducted units on the other floors so our
reception ducted unit is clearly a diff unit.
The issue is on the reception unit we cannot hear the fan anyway due to
the height of the ceiling and the noise level from the busy street so we
need to know the correct settings as they do not seem to correspond to
what its saying in the field settings. Even the engineers when they come
out are confused by this and say that code 03 is high ceiling mode even
though this slows the fan down even slower. As the FM for this site I
am having to resolve this myself now due to the call out costs.
Anyone any idea on what is the correct settings? The system is about 6
years old now and is a big VRV system with some areas having localised
controllers - the reception area included. The rest are controlled from
itouch controllers in the riser cupboards.
😅😅😅😅😅😅😅😮😅
THANK you
THANKS
Daikin SG, can you please help me to get a Daikin mobile tool device?
Can this able appli for fxmq50 pve?
Hi, not possible as the setting is different.
Tengo una alarma en el test con una llave y no me deja que activa el arranque del compresor
Hello can you help me in hacking the ac controller ...it does not on ... only a red light keeps blinking ...pls
red light blinking seem unit have alarm, if not mistaken