Schneider Micom P141 relay Navigation, parameter settings, relay testing, alarm/ fault/led reset
HTML-код
- Опубликовано: 18 сен 2024
- Schneider Easergy Micom P141 relay Navigation, parameter settings(CT-PT ratio setting, Overcurrent & Earth fault setting/relay basic configuration), relay testing, how to view Fault record & its time, alarm/ fault/led reset.,etc.
#p141, #relay #relay testing #relay configuration #schneider
Mashaallah very good sir
Keep it up
Good 👍
Great... Plz make a video on relay configuration
We need MICOM E1 Battery Box
what is the function of poledead in undervoltage on P142
If Voltage-current goes below set threshold value or CB open status through logic then it will be pole dead condition.
Make video on seimens and micom relay
You already have commented on micom relay video. For siemens relay visit ruclips.net/video/x9tH6mtwBBE/видео.html
Salam
Can I ask you for information? I have a problem with micom p142 when I inject the current I > the circuit breaker reacts and opens but when I inject the fault current the circuit breaker is in the open position it closes greetings
Check PSL if there any closing logic mistake, if necessary check real time monitoring, so u can check live status changes. If nothing there from relay side then you need to check external wiring.
Think you very much
can I send you PSL to check
Et ce que on peut avoir la traduction en francais
It will get available in English in near future. Yet to learn French.