DIY Electrical Wiring Basics for Hot Tub Installation

Поделиться
HTML-код
  • Опубликовано: 20 окт 2024
  • Forgot to mention in the video that the disconnect is 60 amps. Always ensure you have the correct size wiring and equipment for the current you will be running.
    Use Romex wires: Indoors
    Use THHN wires: Wet Locations (outside)
    Donate to Turbine Guy at Patreon: / turbine_guy
    Ampacity Chart: www.cerrowire....
    Quality Nordic Hot Tubs: www.djscompani...
    Hot Tub Parts for most manufacturers: MARKDJSHVAC@GMAIL.COM
    Follow me as I travel and explore real projects across the USA.
    Please subscribe to my channel !!

Комментарии • 25

  • @theseattlegreen1871
    @theseattlegreen1871 Год назад +4

    The hotspot manufacturer is calling for a number 8 AWG copper with a 2 pole 50 amp circuit breaker GFCI.
    It's in there diagram and schematics showing all number 8's.
    I wanted to run number 6 gauge copper but their terminals would not fit it.
    What are your thoughts on this please? Thank you

    • @TurbineGuy
      @TurbineGuy  Год назад

      If I wanted to run bigger wires like you so that I have less chance of hot wires and voltage drop over a long distance, I would simply trim the ends just enough to fit in the lugs.

    • @theseattlegreen1871
      @theseattlegreen1871 Год назад +1

      @@TurbineGuy
      Never trim the ends of any wire. I would have to 100% disagree with you there

    • @Zodiaccz_
      @Zodiaccz_ Год назад

      @@theseattlegreen1871 8 copper can hold 50-55 depending on type of wire and temp

  • @johndavies2949
    @johndavies2949 10 месяцев назад +1

    Do you experience nuisance tripping of your 50amp gfci breaker you put in your main electrical panel? You might have been better off using a standard 2 pole breaker in the panel and installing a box outside that would accommodate the 2 pole 50 amp gfci spa breaker.

  • @michael7324
    @michael7324 2 года назад

    Question. Should you be using THWN wire for wet areas? I thought you said THHN wire. Im not an elastration so Im asking...

    • @theseattlegreen1871
      @theseattlegreen1871 Год назад +1

      If you look closely THHN and THWN will always be written on the wire next to each other.
      THHN stands for Thermoplastic High Heat-resistant Nylon-coated. THWN wire is the same, but the "W" stands for water-resistant. The main difference between these two standards is their maximum temperature in wet locations.

  • @josephgraham1065
    @josephgraham1065 2 года назад +1

    Could I install a 50 amp breaker in house box and then use a 50 amp gfci disconnect box?

    • @TurbineGuy
      @TurbineGuy  2 года назад

      Yes, that should be fine. key is to have the gfci somewhere.

  • @russell311000
    @russell311000 Год назад +1

    I know i can do it. How do you want me fried or extra crispy?

  • @TeaHeart93
    @TeaHeart93 5 месяцев назад

    How in the world is your neutral wires bonded to the disconnect? Needs to be your ground!!

  • @eriepazap6701
    @eriepazap6701 Год назад

    No gfci.?

  • @scundoorsup5342
    @scundoorsup5342 3 года назад +1

    Wiring is a mess , not professional for sure

    • @TurbineGuy
      @TurbineGuy  3 года назад +1

      That is really funny. Passed the electrical inspection just fine. Not sure how you could do it any better given the circumstance I had with the house setup as is.

    • @pandherguri
      @pandherguri Год назад

      The lug you have used for neutral in disconnect, is for ground wires and neutral wires have to be connected with isolated lug in disconnect.

    • @pandherguri
      @pandherguri Год назад +1

      Instead of using gfci breaker in main panel…better to install gfci protected disconnect