ASDA-B2 Factory Reset

Поделиться
HTML-код
  • Опубликовано: 18 дек 2020
  • How to reset parameters of ASDA-B2 Delta AC-Servo Drive, back to Factory default.

Комментарии • 15

  • @qutubkhan8113
    @qutubkhan8113 Год назад

    Do you Know Drive Working Speed setings

  • @eduardoflores5945
    @eduardoflores5945 Год назад

    AL025?

  • @bouhlelaymen3885
    @bouhlelaymen3885 2 года назад

    please Do you know the solution for alarm 009?

    • @yapselectro2946
      @yapselectro2946  2 года назад

      Sorry for late reply,
      AL009: Excessive deviation of Position Command
      Causes Checking Method Corrective Actions
      Parameter P2-35 is set too small
      Check the setting value of parameter
      P2-35 (The warning condition of excessive position deviation).
      Increase the setting value of P2-35 (The warning condition of excessive position deviation).
      The setting of the gain value is too small.
      Check if the setting value is appropriate.
      Correctly adjust the gain value.
      The torque limit is too low. Check the torque limit value. Correctly adjust the torque limit value.
      Excessive external load Check the external load.
      Reduce the external load or evaluate the motor capacity again.

  • @hamara4457
    @hamara4457 3 года назад

    Do you know the solution for alarm 009?

    • @yapselectro2946
      @yapselectro2946  2 года назад

      Sorry for late reply,
      AL009: Excessive deviation of Position Command
      Causes Checking Method Corrective Actions
      Parameter P2-35 is set too small
      Check the setting value of parameter
      P2-35 (The warning condition of excessive position deviation).
      Increase the setting value of P2-35 (The warning condition of excessive position deviation).
      The setting of the gain value is too small.
      Check if the setting value is appropriate.
      Correctly adjust the gain value.
      The torque limit is too low. Check the torque limit value. Correctly adjust the torque limit value.
      Excessive external load Check the external load.
      Reduce the external load or evaluate the motor capacity again.

    • @qutubkhan8113
      @qutubkhan8113 Год назад

      Please AL.009 Discuss and Connecting Wiring Image

  • @sanjeevsai1332
    @sanjeevsai1332 Год назад

    Please send position mode wiring details

  • @kostasvasiliou8290
    @kostasvasiliou8290 2 года назад

    Do you know the solution for al022?

    • @yapselectro2946
      @yapselectro2946  2 года назад

      Sorry for late reply,
      AL022 Main circuit power lack phase:
      Check if RST power cable is loose or does not connect to the power. This alarm occurs when no power connects to single phase servo drive.

    • @qutubkhan8113
      @qutubkhan8113 Год назад

      Please Contact CN1 Wiring Image

  • @atulram3111
    @atulram3111 3 года назад

    Al.o11 ka alarms kese remove hoga

  • @leandrootavio1409
    @leandrootavio1409 2 года назад

    P2 - 08 = 10

  • @juanlezama7930
    @juanlezama7930 2 года назад

    Please solution Al009