VFD Braking Resistor Calculation | Breaking Resistor Ohm & Wattage | VFD Braking

Поделиться
HTML-код
  • Опубликовано: 6 янв 2025

Комментарии • 55

  • @NerdyNairTech
    @NerdyNairTech  3 года назад +2

    NOTE : At 3:56 by mistake I said 775.5 X 2 it's actually->
    Get square of 775.5 that is 775.5 X 775.5
    = 601400.25 divided by 3300 = 182.2425

  • @yohanesrochadim.mar.e4725
    @yohanesrochadim.mar.e4725 2 года назад +1

    Thank you very much Mr. Nair for the practical explanation that I have been looking for all this time. Very easy to understand, greetings from Yohanes Indonesia, success

  • @TheGrEEnadiers
    @TheGrEEnadiers 9 месяцев назад

    Easiest calculation that i have found. Keep up good work!

  • @Conroyen
    @Conroyen 2 месяца назад

    Brother what happen when braking resistor flows 2 amp current during normal run of motor with VFD

  • @Logicmart5754
    @Logicmart5754 2 года назад

    Mr Nair, I'm using Delta VFD 450C43S-00, 45KW in my project along with DBU VFD4045. How to select BR (Brake resistance) and wire size between VFD to DBU and DBU to BR. Please suggest the type of OLR as well for Brake resistance.

  • @vorapobautomation9760
    @vorapobautomation9760 3 месяца назад

    I use 1.5/100 kw brake but the output go in to PLC sometime cause of fault.
    How ca I solve it ?

  • @evandroleandro5277
    @evandroleandro5277 2 года назад

    Very good the video, I searched a lot on the subject, however, this video solved all my doubts you very much.

  • @JesusRodriguez-ku9kg
    @JesusRodriguez-ku9kg Год назад

    Where do the 1.5 and the 10 come from?

  • @sangn1696
    @sangn1696 11 месяцев назад

    Can I get the percentage of torque from a motor nameplate?

  • @ToronydaruTDH
    @ToronydaruTDH Год назад

    Very useful. Thanks a lot!

  • @shubhamsaluja1992
    @shubhamsaluja1992 4 года назад +3

    How did you get the value of 182.24 ohm
    775*2/3300

    • @generalleeloaded
      @generalleeloaded 3 года назад +1

      ​ @Nerdy Nair Tech Please answer this question so I am not wasting my time here, Thanks!

    • @NerdyNairTech
      @NerdyNairTech  3 года назад +1

      Get square of 775.5 that is 775.5 X 775.5 = 601400.25 divided by 3300 = 182.2425.
      Hope you got it.

    • @NerdyNairTech
      @NerdyNairTech  3 года назад

      You are not wasting your time bro. Pls be Subscribed, more tutorials are on the way.

  • @omargaray9457
    @omargaray9457 2 года назад +1

    Hello, I have an issue with my dynamic breaking, I'm using a Delta VFD-EL for a 220V, 2 HP motor, the manual says that I need to use a BUE-20015 dynamic break module with a 100 ohm and 300 Watt resistor, my trouble starts as soon as I turn on the VFD, the resistor starts to burn, I've already burn one resistor, Do you have any idea of what can I do or what could be happening? Bests.

    • @NerdyNairTech
      @NerdyNairTech  2 года назад

      Okay so where did you connect the resistor to? Did you use the Brake module?

    • @omargaray9457
      @omargaray9457 2 года назад

      @@NerdyNairTech Thanks a lot for your answer 🙏, I connect the resistor to the break module, an the module to the VFD (+) & (-), the resistor to the B1 & B2 terminals of the module.

    • @omargaray9457
      @omargaray9457 2 года назад

      @@NerdyNairTech By the way, the module doesn't overheat, is just the resistor, and I also have connected the resistor directly to the VFD and the results are the same "overheating".

    • @omargaray9457
      @omargaray9457 2 года назад

      Today I have checked the voltage between the resistor terminals and it is always having 350V DC, it is never on 0V, Any thoughts what could it be?. Bests.

  • @farhatunraihan1902
    @farhatunraihan1902 3 года назад +1

    Hello. Is it the percentage of braking IGBT is same for all model?

    • @NerdyNairTech
      @NerdyNairTech  3 года назад

      Mostly If for Heavy braking apllications such as Crane, Hoisting etc you can refer to the manual for Resistor specification as per the VFD manufacturer. You can also send the model no. and I will try to give link for the Manual.

    • @farhatunraihan1902
      @farhatunraihan1902 3 года назад

      @@NerdyNairTech im using Aqua drive

    • @NerdyNairTech
      @NerdyNairTech  3 года назад

      @@farhatunraihan1902 Model No.? and KW

    • @farhatunraihan1902
      @farhatunraihan1902 3 года назад

      @@NerdyNairTech im not sure about the model no but im using danfoss brand for 15 HP

  • @satyaprakashsingh4581
    @satyaprakashsingh4581 3 года назад

    Good nair keep it up

  • @PTinvest
    @PTinvest 3 года назад

    Great , can you show me in video how to wiring the VFD 2,2 kw at :
    + fuse
    + safety relay
    + filter
    + braking resistor
    + contactor
    + e-stop
    + reset button
    + switch main power

  • @biswajitkhilar4042
    @biswajitkhilar4042 9 месяцев назад

    Why to devide 10 ? What is the reason

    • @NerdyNairTech
      @NerdyNairTech  9 месяцев назад

      Motor peak power divided by 10 to get brake resistor power rating.

  • @aymnslah7096
    @aymnslah7096 3 года назад

    Thanks for the good information

  • @Logicmart5754
    @Logicmart5754 2 года назад

    Nicely explained

  • @aasouz7141
    @aasouz7141 Год назад

    Why tge breaking register is getting overheating

    • @NerdyNairTech
      @NerdyNairTech  Год назад

      The rating may not be according to the requirements

  • @anisnono4169
    @anisnono4169 4 года назад

    hello . i have hitachi inverter 3G3MX2 11kw, and i connected braking resistor 100 ohm , but alwyas i have problem error E06.3 ,E06.2, ....i try to adjust: b090, b095, b096,b097, these parameters many time but th same problem

    • @NerdyNairTech
      @NerdyNairTech  4 года назад +1

      Will check & tell. Send pic of vfd

    • @anisnono4169
      @anisnono4169 4 года назад

      @@NerdyNairTech I send you in messenger

  • @SK-uo2wo
    @SK-uo2wo 3 года назад

    Which parameter needs to be set for braking resistance

  • @anggaradedy
    @anggaradedy 3 года назад

    hello Nerdy..
    I have put calculation from your formula.
    Inverter Rating is 132 kW
    I found the resistor value = 3 ohm
    and power rating = 19.800 watt
    is that correct ? pls let me know..
    thx

    • @NerdyNairTech
      @NerdyNairTech  3 года назад

      What is the Application?

    • @NerdyNairTech
      @NerdyNairTech  3 года назад

      Yes it's correct. 3Ohms & 19800 Watt or 19.8 KW

    • @anggaradedy
      @anggaradedy 3 года назад

      @@NerdyNairTech using your formula..

    • @anggaradedy
      @anggaradedy 3 года назад +1

      @@NerdyNairTech many thanks for your answer

    • @NerdyNairTech
      @NerdyNairTech  3 года назад

      @@anggaradedy Which VFD are you using? The manual or catalog will also have the exact rating according to the same.

  • @devadsp2010
    @devadsp2010 Год назад

    What is this 10

  • @kimberlyjacobsen4148
    @kimberlyjacobsen4148 3 года назад

    Have a 2.2KwH Spindel. Got a electric heater 500W 100~ Ohm.
    Should work fine as breaking resistor 🤟 (fingers crossed)

    • @NerdyNairTech
      @NerdyNairTech  3 года назад

      Should work but life of heater will be less it burnout.

  • @DamithRathnayake
    @DamithRathnayake Месяц назад

    Tx❤

  • @nsnnsn5445
    @nsnnsn5445 3 года назад

    Where is duty cycle

  • @qliqelabdelkarim5416
    @qliqelabdelkarim5416 2 года назад

    THANKS BROO

  • @mathiyazhaganramalingam2254
    @mathiyazhaganramalingam2254 3 года назад

    Same video but in Hind I saw