Will NAVAC Pumps compete in Commercial HVAC?

Поделиться
HTML-код
  • Опубликовано: 25 янв 2025

Комментарии • 51

  • @jaredkirkland4177
    @jaredkirkland4177 2 года назад +14

    Even pure nitrogen will drop in pressure with a temp drop. It just has much less of a drop than atmosphere or refrigerant. The HVAC school app has a calculator built in for figuring this. You can enter the starting temp and pressure, and enter the ending temp and pressure and see if it has actually leaked at all. Awesome video man!

    • @kaptaintrips
      @kaptaintrips 2 года назад

      Pure nitrogen will not raise nor drop unless in a perfect vacuum or headed to a star. All the other shit affected the delta...

    • @jonnymac31
      @jonnymac31 2 года назад +10

      @@kaptaintrips nitrogen follows the gas laws just like any other.

  • @czechmate6916
    @czechmate6916 2 года назад +5

    Things have really changed in this field since I retired. Some of it for the better and some of it for the not so better. Like this demonstration of the new equipment is awesome. Too bad it wasn’t available for me. I really love watching your videos, kind of keeps me updated on some of the new changes. MTT Brother.

  • @redman42s7
    @redman42s7 2 года назад +2

    Thanks for making the time to get this video out there!

  • @rich3670
    @rich3670 2 года назад +1

    Brilliant! pulling a vacuum before pressure testing!

  • @FrenchBeefCDN
    @FrenchBeefCDN Год назад +1

    I do every job with my 8cfm YJ. 3000ton YKs, 200 ton YVAAs, 2 ton Heat Pumps, Recovery Tanks, whatever. I try to use the biggest and shortest hose as possible and as many of them I can fit. Last big job I did was out in the snow, YLAA chiller, put a 3/8 hose on liquid service, 3/8 hose of suction charging valve, 1/4" hose on liquid line after EEV and micron gauge was on discharge pipe. Within an hour, I was at 480 microns (enough time to pack my tools and make one trip to my van and back up with the refrigerant.) The next morning I got to 340 where it stayed for 2 hours decaying. I ALWAYS leave my pump running overnight on anything bigger than 5 tons, unless I achieve sub 500 before lunchtime. All repair job are quoted as minimum two days or 1 and a half days, to get a quality evacuation. With a single 1/2" hose, I can pull a 2500 ton YK chiller from 14.4psia to 1200 microns in a couple hours and it takes the remainder of the night to get below 300 (boiling 15 gallons of refrigerant laden used oil.)
    Point is, I like this pump but would NEVER bring it to job sites. This seems like a great fit for a Chiller Plant to be dragged around to each unit... not so much a service van. Looks like it weighs over 100lbs.

  • @persimonsen8792
    @persimonsen8792 2 года назад +5

    You probably know it, after some years in the trade. After vacuum, and equalizing, take your pressure / temperature = number.
    After 24 hours, take pressure / temperature = same number, it's tight.

  • @paulb4496
    @paulb4496 2 года назад +1

    Rectorseal Tru Blu pipe sealant is my go to for threaded connections.

  • @jerzyaheardz6939
    @jerzyaheardz6939 2 года назад +3

    Interesting, you’ve had success with Nylog on those threaded fittings without leakage? I don’t know why I feel squirrelly about using it in those applications. My general go to is either Loctite 567 or 554.

  • @jasonjohnsonHVAC
    @jasonjohnsonHVAC 2 года назад +2

    I have an Accutools Pro....the app that you can use is fantastic and has plenty of recordable data. Pull down, decay test, graphs. I do like Navac products and they produce for a lot of manufacturers that just re-brand them. This was a cool video of some awesome products.
    Hahahaha the little quips were hilarious....they were blown...them right there...they blew because there blown.... 🤣

  • @SoutheastHVAC
    @SoutheastHVAC 2 года назад +1

    Could you possibly do a rigging video?Im new to the industrial side of hvac and found that my rigging skills are sub par😂

  • @HH-oi8hn
    @HH-oi8hn 2 года назад

    Please what capacity of vacuum pump ,thanks

  • @dkind82
    @dkind82 2 года назад +4

    Just a note, the hotter the oil in the pump the faster moisture will evaporate out of the oil. Is advantageous.

    • @kaptaintrips
      @kaptaintrips 2 года назад

      Just dont burn or boil said oil.

  • @mcdonrs
    @mcdonrs 2 года назад

    Just did an overhaul on cvhf with oversized barrels. 900# circuit. Same vacuum pump had it to 990 microns in 5-6 hrs and down to 170 when I came in the next morning.

  • @sterlingarcher46
    @sterlingarcher46 2 года назад +2

    Bloody Nora mate ! With the setup I've got it would've taken me ages to get to 3000 microns, let alone 350 !
    Holden mate , next time you talk to Navac could you please ask them why they're not available over in the EU ?
    And I don't wanna hear them say : oh but we are ! Nah man , they aren't, trust me I've looked for their products and nobody has heard of them over here 😒.

  • @Weird_1
    @Weird_1 2 года назад

    Used my first navac master series 4cyl recov machine. Thing is a beast. Not using push pull to charge 800lbs of r134 it had 300lbs in the chiller in around 3.5 hours. Next will be the vacuum pump

    • @Weird_1
      @Weird_1 2 года назад

      I did have it throttled down about halfway though because I was borrowing it to try it out. I’ll be excited to see the push pull on the other circuit with this same machine

  • @usmanshakeel1304
    @usmanshakeel1304 2 года назад

    Hello bro
    I have a problem york chiller ( Low Dischage Superheat ) can you help me out

  • @FrostHVAC
    @FrostHVAC 2 года назад +1

    My coworker calls them pecker heads too lol, i looked at him and said "what was that called again?" 😂
    Also i love that small baby york runnin next to these giants lol

  • @joshstevens9826
    @joshstevens9826 2 года назад

    I have only used a Welsh. What is your opinion on the two?

  • @LukeAvery-g5d
    @LukeAvery-g5d Год назад

    Hey hvac time, do you flow condenser water and chilled water on a water cooled chiller when entering nitrogen and during evacuation?

    • @HVACTIME
      @HVACTIME  Год назад

      No, I stop flow entirely for that process.

  • @1MaximusDecimusMeridius1
    @1MaximusDecimusMeridius1 2 года назад +1

    Idk, my guys use the yellowJacket bullets and they’re impressive-
    I was surprised

  • @thesilentonevictor
    @thesilentonevictor 2 года назад +1

    Great Job tech

  • @hvactechpr7872
    @hvactechpr7872 2 года назад +1

    There's a loctite you mentioned it there was a yellow one that's reefer safe

    • @jonnymac31
      @jonnymac31 2 года назад +1

      Loctite 554 is refrigerant rated.

  • @jonnymac31
    @jonnymac31 2 года назад

    Sweet, man. Thanks.

  • @reyrodriguez1005
    @reyrodriguez1005 2 года назад

    Did you force the EEV open during evacuation?

  • @aleksandrsolzhenitsyn6707
    @aleksandrsolzhenitsyn6707 2 года назад

    Isn’t nylog just a thread lubricant and not a sealant?

    • @jonnymac31
      @jonnymac31 2 года назад

      Yes that is correct.

  • @patriciap1214
    @patriciap1214 Год назад

    I’m a refrigeration tech here in Philadelphia I work on anhydrous ammonia and big ice machines I would like to know how they pump is working out for you I’m thinking about buying one your videos are really good because the real world videos in real service I really like you a lot. Let me know if you get this comment and let me know if this pump is working out for you. I’m thinking about buying one. Thank you great video video

    • @HVACTIME
      @HVACTIME  Год назад

      The pump has been completely fantastic. I've been such a big fan of the Apion G5 twin for such a long time but this one has become my new favorite. You can move refrigerant really well like the g5 twin but it's built-in subcooler is amazing and then the ability to bypass the subcooler to increase flow has been great. The other techs are constantly trying to borrow it. Anyway it's easy to say for somebody that had a given to him but I have truly loved this pump.

  • @hvactechnicalcentralac8740
    @hvactechnicalcentralac8740 2 года назад

    Very nice Work

  • @billyflanagan9657
    @billyflanagan9657 Год назад

    Oil in the refrigerant
    Always open the economizer solenoid before putting on hg pump

  • @BrannndonM
    @BrannndonM 2 года назад

    Your the goat, grouse vid

  • @sterlingarcher46
    @sterlingarcher46 2 года назад

    Here we use Trace-a-gas which is 95% nitrogen and 5% hydrogen, then you can use a hydrogen electronic leak detector to find leaks .
    Its good for looking for leaks but not so much for pressure testing because it's even more reactive to temperature changes .

  • @jeytee228
    @jeytee228 2 года назад

    Loved the video

  • @billyflanagan9657
    @billyflanagan9657 Год назад

    I love my appi for installing liquid

  • @B00stedGD
    @B00stedGD 2 года назад +1

    Nitrogen pressure will definitely rise and fall with temp swings. Like mentioned above, There are apps for It, Even websites that will calculate It for you. Good one to show apprentices Is the below formula.
    Nitrogen test
    P2 = (P1xT2)/T1
    P1 - Test pressure
    P2 - Verified pressure
    T1 - Ambient test pressure temp
    T2 - Ambient verified pressure test
    Need to convert F* to Kelvin
    K= (*F - 32 / 1.800 ) + 273.15
    Example:
    Test pressure 190# @ 94* (307.6 K)
    Verified pressure temp 70* (294.3 K)
    (190 x 294.3) / 307.6 = 181.78 PSI

    • @persimonsen8792
      @persimonsen8792 2 года назад

      Or start pressure / temp (measure on pipe) = a number. After pressure test. new pressure / new temperature = same number, it's tight.

  • @emailfilters
    @emailfilters 2 года назад

    9:01 - You gotta be kidding me! Not a fair comparison! Everything works better with TruBlu hoses! Just sayin'.

  • @billyflanagan9657
    @billyflanagan9657 Год назад

    Always megg the compressor at 1000 megg ohms out of the box before install.

  • @kaptaintrips
    @kaptaintrips 2 года назад

    Had a tech recently push too much N into a circut to leak check
    It pushed through the other circuit through the barrel. What a shit design. He claimed he only blew it up to 80#.

    • @jonnymac31
      @jonnymac31 2 года назад

      This can definitely happen.

  • @diabateadama8892
    @diabateadama8892 2 года назад

    Svp traduire en français

  • @1MaximusDecimusMeridius1
    @1MaximusDecimusMeridius1 2 года назад +1

    You must have run out of room -
    Because it’s spelled “available” 🫡
    Thanks for sharing!