I see you set several parameters that I can't find very detailed explanations for. Is there a detailed parameter guide, anywhere? For example, what's the difference between Highest Output Frequency and Maximum Voltage Output Frequency (P00.04 and 05)? What do the Middle Frequency and Middle Voltage parameters (P00.07 and 08) do? What do the VF Curve setting options (P00.12) 0 through 4 represent? It seems like a solid product, but the documentation is a little sparse in areas that seem kind of important. Any ideas where I could look for more details?
Hi, your vfd YL620 works very well for me.The machine has withstood a water leak in the pipes of my house very well. I use mach3 and I can control on/off with the program, but I'd like controlling speed with the lines of my g-code/m-code. Can you give me any orientations about the parameter I have to change? I have a manual from you but amb not sure if I understand right how to do it? Thank you in advance.
Hi do you have a wiring diagram that shows connections to be run from a external 0-10 volt signal? I would like to operate turn on and off and set speed from my cnc control, Thanks
hi! thank you for the video it help so much! any I have a problem with the inverter I need your help. The spindle is suddenly stops running and the VFD shows Error 4. I already watch some tutorial and i set up again by doing factory reset. The error 4 disappeared but when i try to rotate the panel potentiometer the frequency shows 10Hz the spindle is not move, until i set 47 Hz the spindle is move. But the rotation is different, it is less noisy but i feel there is something wrong. Do you have any idea? thank you
ayuda... yo tengo un VFD YL620-A.. un spindle de 2.2Kw ambos para 220v...Yo estoy en Mexico. el voltaje es de 220V, el problema es que el spindle se calienta muy rapido. Quiero saber como configurarlo... Los parametros que pones, los tienes en 50hz yo en 400hz... esta bien?? o como debo de configurarlo?
me enviaron la siguiente configuracion... Code Function Set Range& Function Explanation Factory Setting P00.00 Main Frequency 0-120HZ(400HZ) 400HZ P00.01 Source of Run Control mode 0: .Operator board 0 1:.External terminal P00.03 Stopping Mode 0:Decelerating stop 1:Coasting stop 0 2:DC brake stop P01.00 REV Run Setting 0:Rev Run Enable 0 1:Rev Run forbidden P03.09 Upper limit of panel potentiometer frequency 0-120HZ(400HZ) 400HZ
P03.11 Upper limit of 1 AD value for analog input 0-1023 1010 P03.13 Upper limit of the analog input 1 0-120HZ(400HZ) 400HZ P07.08 Frequency source selection 1 0: Operator board 1: Pre~set Frequency, P00.00 3: Analog Input. 0 P07.09 Frequency source selection 2 2 P07.10 Frequency source selection 3 2 P07.11 Frequency source selection 4 2 P07.12 Frequency source selection 5 2 P07.13 Frequency source selection 6 2 P07.14 Frequency source selection 7 2 Note:three control methods (P07.08) 1.The motor speed is controlled by the operating panel 2.Motor speed control by external terminals (Potentiometer 10K). P00.01 set to 1, P07.08 set to 3 3.Motor speed control by external terminals. P00.01 set to 1,P07.08 set to 1.
@@cristhianodamata ¿Cuál es su correo? Puedo enviarle la configuración que me envió el vendedor de mi kit (que aún no ha llegado pero estoy preocupado por la configuración del inversor))
Hello, I have a YL 620 A and I still can't get the spindle to start automatically by the GCode of my machining program.. (M3 start/M5 stop) P00.01=1 and P00.16=2 Could you give me the solution.. When I keep P00.01=0 and P00.16=0 everything works in manual correctly thank you Philip
When the frequency Converter YL600-2.2 KW-220V is plugged in 220V, the fan turns on. And the fan does not turn off at all (even more than a minute - does not turn off). You can only turn off the fan by pressing the stop button. Is there any way to configure it so that fan doesn't turn on when plugged in 220V, or at least turns off a minute after it's turned on?
i need install in one cnc control ,M3 M4 gnd and 10 v , Yuhai 990 M IS THE Control and can t work ,analog speed 0 10 v, would you help me ,Invt use s1,s2, GND A01 AND 24 V AND WORK OK, We bougth 20 set YL620 and need the connection
I have a yo 620-A and when I start the spindle by operation panel, the spindle runs but i cannot stop or adjust ist anymore. All lights on operation Panel blink in this situation. Does anyone have a Solution
I have inverter yl620g , but when im opration for my machine with 5,5 kw capacity . Myachine cant move. What the problem ? My inverter not powerfull i think .may my inverter have a mistake program Please help me give ure solution thanks
Hello, is the YL620A model suitable for INPUT 220 single phase and OUTPUT 380 three phase? I see that the input connections are 3, RST. There is something wrong?
I see you set several parameters that I can't find very detailed explanations for. Is there a detailed parameter guide, anywhere? For example, what's the difference between Highest Output Frequency and Maximum Voltage Output Frequency (P00.04 and 05)? What do the Middle Frequency and Middle Voltage parameters (P00.07 and 08) do? What do the VF Curve setting options (P00.12) 0 through 4 represent? It seems like a solid product, but the documentation is a little sparse in areas that seem kind of important. Any ideas where I could look for more details?
Thank you for the video. WHAT'S a difference 620 and 620-A models? I guess A is newer. And ...?
How do you perform a factory reset?
this series have a rs485 connection or not??
Hi, your vfd YL620 works very well for me.The machine has withstood a water leak in the pipes of my house very well. I use mach3 and I can control on/off with the program, but I'd like controlling speed with the lines of my g-code/m-code. Can you give me any orientations about the parameter I have to change? I have a manual from you but amb not sure if I understand right how to do it? Thank you in advance.
Hello what are the settings for the maximum power. I have an engine from a car lift and it doesn't have enough power
Hi do you have a wiring diagram that shows connections to be run from a external 0-10 volt signal? I would like to operate turn on and off and set speed from my cnc control, Thanks
i am stuck there now, fw/rev no prob, but i cant pwm it via mach3, got a way?
hi! thank you for the video it help so much! any I have a problem with the inverter I need your help. The spindle is suddenly stops running and the VFD shows Error 4. I already watch some tutorial and i set up again by doing factory reset. The error 4 disappeared but when i try to rotate the panel potentiometer the frequency shows 10Hz the spindle is not move, until i set 47 Hz the spindle is move. But the rotation is different, it is less noisy but i feel there is something wrong. Do you have any idea? thank you
Does anyone know where can I get the manual of a YL620-A in spanish? I really need it.
Hola encontraste el manual
Hi . Whats reason of error 0005 and error 0007
ayuda... yo tengo un VFD YL620-A.. un spindle de 2.2Kw ambos para 220v...Yo estoy en Mexico. el voltaje es de 220V, el problema es que el spindle se calienta muy rapido. Quiero saber como configurarlo... Los parametros que pones, los tienes en 50hz yo en 400hz... esta bien?? o como debo de configurarlo?
Estimado que descubrió la configuración del inversor?
@@ИгорьАрутюнов-м5т que tal, gracias por contestar. Aun no logro hacer que no se caliente.
me enviaron la siguiente configuracion...
Code Function
Set Range&
Function
Explanation
Factory
Setting
P00.00 Main Frequency 0-120HZ(400HZ) 400HZ
P00.01
Source of Run
Control mode
0: .Operator board
0
1:.External terminal
P00.03 Stopping Mode
0:Decelerating stop
1:Coasting stop 0
2:DC brake stop
P01.00 REV Run Setting
0:Rev Run Enable
0
1:Rev Run forbidden
P03.09
Upper limit of panel potentiometer
frequency
0-120HZ(400HZ) 400HZ
P03.11 Upper limit of 1 AD value for analog input 0-1023 1010
P03.13 Upper limit of the analog input 1 0-120HZ(400HZ) 400HZ
P07.08 Frequency source selection 1 0: Operator board
1: Pre~set Frequency,
P00.00
3: Analog Input.
0
P07.09 Frequency source selection 2 2
P07.10 Frequency source selection 3 2
P07.11 Frequency source selection 4 2
P07.12 Frequency source selection 5 2
P07.13 Frequency source selection 6 2
P07.14 Frequency source selection 7 2
Note:three
control
methods
(P07.08)
1.The motor speed is controlled by the operating panel
2.Motor speed control by external terminals (Potentiometer 10K).
P00.01 set to 1, P07.08 set to 3
3.Motor speed control by external terminals. P00.01 set to 1,P07.08
set to 1.
@@cristhianodamata ¿Cuál es su correo? Puedo enviarle la configuración que me envió el vendedor de mi kit (que aún no ha llegado pero estoy preocupado por la configuración del inversor))
Hi, I connected the VFD YL 620 A to 220V line monophase the motor turns but has no lifting power.
Hello
Where to connrct stop buton
How to display RPM instead of Frequency on this vfd
You can contact me by email at 402241468@qq.com
Did you ever figure this out? Im in the same boat....
Hello, I have a YL 620 A and I still can't get the spindle to start automatically by the GCode of my machining program.. (M3 start/M5 stop)
P00.01=1 and P00.16=2
Could you give me the solution..
When I keep P00.01=0 and P00.16=0 everything works in manual correctly
thank you
Philip
I have buy yalang yl600 but always error 04! what the problem? how to detail setting the yl 600 parameter?
did you find out the problem and solution?
When the frequency Converter YL600-2.2 KW-220V is plugged in 220V, the fan turns on. And the fan does not turn off at all (even more than a minute - does not turn off). You can only turn off the fan by pressing the stop button. Is there any way to configure it so that fan doesn't turn on when plugged in 220V, or at least turns off a minute after it's turned on?
You can set the fan operation mode by setting parameters P12.11 and P12.12
Can you tell me about RS485 communication in this product?
You can contact me by email at 402241468@qq.com
Did you get any info on this?
i need install in one cnc control ,M3 M4 gnd and 10 v , Yuhai 990 M IS THE Control and can t work ,analog speed 0 10 v,
would you help me ,Invt use s1,s2, GND A01 AND 24 V AND WORK OK, We bougth 20 set YL620 and need the connection
I have a YL620A. If the input voltage is 110V, what is the value of p005 and P006?
First of all, you have to determine whether the VFD you purchased is 110V or 220V, please contact me by email
Hello!
I have a 3 kw inverter but the motor is only 2.2 kw.
Where can I set the inverter to 2.2 kw? Where to enter
The output power does not need to be set, it is automatically adaptive according to the input voltage and current of the motor
0.3 kW. do 2.2 kW motors have the same settings?
Is the engine not burning?
Thanks for the reply!!!
@@Bignac As long as the frequency of the motor is the same as the set frequency of the VFD, the motor will not be burned out
@@jackzhou1683 I see, thank you!
I have a yo 620-A and when I start the spindle by operation panel, the spindle runs but i cannot stop or adjust ist anymore. All lights on operation Panel blink in this situation. Does anyone have a Solution
I have inverter yl620g , but when im opration for my machine with 5,5 kw capacity . Myachine cant move. What the problem ? My inverter not powerfull i think .may my inverter have a mistake program
Please help me give ure solution thanks
if my input voltage is 220v then p0005 is set at 400 hz,and the p0006 should be set at 50%?
tengo la misma pregunta...
My yl600 runs fine for about 45 minutes the freezes with the lights flashing and can't turn off by using the control very dangerous
Hello can you help setup please
Contact me by email, I will guide you to set up VFD
Can you send email please
Email: 402241468@qq.com
@@jackzhou1683 Hi Jack how do I clear the alarm er 09
Hello, is the YL620A model suitable for INPUT 220 single phase and OUTPUT 380 three phase? I see that the input connections are 3, RST. There is something wrong?
NO, this VFD is a single-phase 220V input, three-phase 220V output, suitable for 220V motor
This VFD is junk. Used 6 times and the board blew
Can you tell me about RS485 communication in this product?