DIFFERANTIAL RELAY|| CT POLARITY AND EFFECT OF CT POLARITY REVERSE FOR TRANF. DIFFERENTIAL RELAY

Поделиться
HTML-код
  • Опубликовано: 27 окт 2021

Комментарии • 5

  • @surendrakverma555
    @surendrakverma555 Год назад

    Very good. Thanks 🙏🙏🙏🙏🙏

  • @sivaprakashjayapal4719
    @sivaprakashjayapal4719 2 месяца назад

    Sir why we connect LV side P2 to P1?
    Normally current flow source(LV side of transformer)to load

  • @santhoshr53
    @santhoshr53 2 года назад +1

    Actually star side of transformer ct should be in the form of Delta and other side of transformer ct should be star connection.

    • @relayprotectionelectrical
      @relayprotectionelectrical  2 года назад +1

      Yes that should be in case of static relay to eliminate phase shift and to match the current fed to the relay in both side of transformer is equal and interposing current transformers are used for that purpose. But in case of numerical no such ICTs are required. Relay will do all that phase shift and matching factor.

    • @santhoshr53
      @santhoshr53 2 года назад

      @@relayprotectionelectrical thanks🙏