Great 'LIVE' video shot on a neat Smart Solar installation. Evidence that SMART SOLAR is all about in-depth knowledge & intrinsic know-how what to do when it comes to install professionally. Top notch!
Am i right by saying this is a 12kva single phase inverter and not a 3 phase inverter ? I see has 3 load outputs so its seem to be 3phase but his only using 0ne phase
Do you mind explaining why the inverter wouldn't allow the 300 you wanted and didn't you check the specs and calculate everything before the job? Also is the avr single or three phase?
Same question i asked if its single phase or 3 phase. Because im searching to see if the Deye 12kva are also in single phase but only 3 phase comes up.
I am just curious! Will that building besides where the pv modules are being mounted not cast Shadow on them, hence reducing their optimal performance.
so you allow the batteries to be charged by the grid, what happens when the sun comes up? I thought you will just let the grid pass through without charging the batteries so the sun will do that in the morning or when the weather becomes OK for that? just wondering...
So Deye does the charging priority automatically (based on your settings). In this particular site, I set the system never to use Grid for both charging & passing through from 6:00 to 21:00. You can alter these settings at will.
Hi, please kindly check your Inverter manual and confirm how you installed the white magnetic beads. The bead is to be installed on the either the live or the neutral lines. the way you connected it now is leading to the cancellations of magnetic field. Please kindly correct it when you visit next time.
I appreciate your feedback. But for Deye, that is the proper way to connect the magnetic ring (the way we used it in the video, pass both wires through it). Manual link below! chrome-extension://efaidnbmnnnibpcajpcglclefindmkaj/www.deyeinverter.com/deyeinverter/2024/08/13/rand/4249/instructions_sun-12-16k-sg01lp1-eu_240813_en1.pdf
Yes, I confirm your magnetic beads installation ok from your attached manual. I never see this bead arrangements in some of the Deye Inverter I've done. I just concluded 80KW Deye Inverter installation (with 4 units of 16KW) and never see that. Thanks for sharing.
Hi, I like the work you guys have done. what is the input voltage to the mppt (inverter) from the solar system? Is your client house running a 3 phase setup or single?
Ok. How many rooms does the property have as I am interested in the setup however wondering if having 30kw is an over kill, only if it less than 6 rooms
Deye inverters come with in-bulit DC breakers (in this case, two battery inputs with a 200A breaker each). Also, each of the Deye batteries in use comes with a 125A MCB breaker.
Great 'LIVE' video shot on a neat Smart Solar installation. Evidence that SMART SOLAR is all about in-depth knowledge & intrinsic know-how what to do when it comes to install professionally. Top notch!
Appreciate the kind words!
Good job 👍
Thanks! 🙏
battery cables in my country needs to be 50mm2 for dc 12kw great work
Thanks
The battery cable here was 100mm2(50mm2 x2 battery inputs.
Thanks for the feedback
Very neat installation man!
Thanks!
Great work you are doing.
Where do you get your DEYE products?
We do sell Deye & other products
Great job 💯
Thank you 👍
The use of ferrules or terminal blocks would be best in wire connections and cable terminations to avoid arcing.
Thanks
You are welcome! 🙏
Am i right by saying this is a 12kva single phase inverter and not a 3 phase inverter ? I see has 3 load outputs so its seem to be 3phase but his only using 0ne phase
It’s a single phase inverter
Do you mind explaining why the inverter wouldn't allow the 300 you wanted and didn't you check the specs and calculate everything before the job?
Also is the avr single or three phase?
The AVR is 3phase
The max charging and discharging current for Deye 12KW is below 300A (around 290A there about)
is the grid the input in the AVR ?
Can you please share the version of Deye Inverter? Also is it Single Phase or Three Phase?
Same question i asked if its single phase or 3 phase. Because im searching to see if the Deye 12kva are also in single phase but only 3 phase comes up.
I am just curious! Will that building besides where the pv modules are being mounted not cast Shadow on them, hence reducing their optimal performance.
2:37
The building will not, the carport on the north-south line.
💯💯
I was wondering Why use 580w panels when there is 750w panels, won't you be using less of those and having more space to work with?
580W was the biggest size available at the period of the project
so you allow the batteries to be charged by the grid, what happens when the sun comes up? I thought you will just let the grid pass through without charging the batteries so the sun will do that in the morning or when the weather becomes OK for that? just wondering...
So Deye does the charging priority automatically (based on your settings). In this particular site, I set the system never to use Grid for both charging & passing through from 6:00 to 21:00.
You can alter these settings at will.
@ I get it now
In one of your settings shot I saw grid charging so I thought you left it at that…great work buddy
This is a good job. What could be the cost of this 12kw with 30kva lithium battery, please?
Approximately 22million Naira
What’s a roughly budget for the equivalent .
22million naira
Please can you send me a link of where you get your enclosure boxes! By the way nice and neat job
I do sell enclosure boxes, kindly inbox
Pls are u in lagos i will to get this enclosure box for a project pls ur line..@@zurriannetworks
Are you accepting apprentice
Where’s your location?
@zurriannetworks Mararaba
contact via our Instagram, @zurriannetworks
or send mail to zurriannetworks@gmail.com
Hi, please kindly check your Inverter manual and confirm how you installed the white magnetic beads. The bead is to be installed on the either the live or the neutral lines. the way you connected it now is leading to the cancellations of magnetic field. Please kindly correct it when you visit next time.
I appreciate your feedback.
But for Deye, that is the proper way to connect the magnetic ring (the way we used it in the video, pass both wires through it).
Manual link below!
chrome-extension://efaidnbmnnnibpcajpcglclefindmkaj/www.deyeinverter.com/deyeinverter/2024/08/13/rand/4249/instructions_sun-12-16k-sg01lp1-eu_240813_en1.pdf
@@zurriannetworks Alright Bros, I do appreciate your feedback. Very neat installation by the way
Yes, I confirm your magnetic beads installation ok from your attached manual. I never see this bead arrangements in some of the Deye Inverter I've done.
I just concluded 80KW Deye Inverter installation (with 4 units of 16KW) and never see that. Thanks for sharing.
I see, 16kw doesn’t come with any of the rings.
It’s peculiar to their 8kw & 12kw.
One love brother!
Hi, I like the work you guys have done. what is the input voltage to the mppt (inverter) from the solar system? Is your client house running a 3 phase setup or single?
It’s a single phase setup.
Input Voltage is 120 - 500V
Ok. How many rooms does the property have as I am interested in the setup however wondering if having 30kw is an over kill, only if it less than 6 rooms
Where is your location in Nigeria
Abuja
I find your wires size smaller than required....
My thoughts exactly
Ты похож на 50-cent
The panels location is heavily shaded.
No battery protection.
Cables not correctly sized(fire hazard)
I also noticed he has no protection between Inverter and batteries
Deye batteries have internal protections. My thought
you are correct
Deye inverters come with in-bulit DC breakers (in this case, two battery inputs with a 200A breaker each).
Also, each of the Deye batteries in use comes with a 125A MCB breaker.
Didn't explain anything shaaaa
I need the 12kw inverter.. kindly contact me soonest..
Inbox our Instagram, @zurriannetworks
Or email us, zurriannetworks@gmail.com