Nice video sir Sir ek video ispe bhi bana dijye ke HVAC system mein kitne tarah ke valve lage hote hain aur kahan lagate hote hain aur uss valve ka kya kaam hai
Thank you bhai , aap ka explanation toh dil se aata hai. sir aapne bataya 8 AHU hai aur building me 10 floors hai . Itne high capacity waale 8 AHU hai toh floor sizes bohot bade honge. is it an office type building ?
Dear sir you give such a good knowledge to us. But if drain try full of water you said only 2 reason drain line Chowk and cooling coil was leak.anthor reason also if fahu and ahu bag filter and pre filter was fully bloke( darty) that time also water more in drain try and water came out to unit
Ahu ppm me Have to chwck 1. Ahu room cleaning 2.check temp gauge 3.Check Pressure gauge 4.check all dampers 5. AHU control panner wiring check filters 6. Check blower belt 7.check gressing 8.check motor terminal 9.check drain line 10.check limit switch Then preaper history chart as per your inspection Right sir .??
Sir ek request h ek video AhU ki bowler size ,rpm, kis type ka bowler use hota h ahu me,cooling ka size, types of cooling coil Interview point of view se
Sir apki har vdo super helpful hoti hy kasam sy Allah apko or bhi kambyabi dy ameen aor sir Happy birth day 🎂 sorry us din me apko wish karna bhool gaya Allah apko any wali zindagi me or bhi khushia dy amen
Thank you sir For Describe the PPM of AHU And Provided complete details about AHU step by step . Sir I have One question Describe the Heating system in HVAC And how to supply Hot air through out duct in a room. Please makes separate video of this question
iska matlab apke chiller pe 95% laod se jyada load hai ...aap use 100% FLA set karo .....agar tabhi bhi aata hai to apko second chiller start karna hoga
Sir i have one doubt about actuator u are saying actuator is always connect on return line of ahu bt i think it always connect in chw supply line so plz clear my doubt
Check the dscaling time ..matlab apka condenser ki kab descaling hui hai ...aor ye check kare ki apke cooling tower ka water parameter kya chal raha hai ...PPM,PH TDS Ppm apka 40 se 60 hona chahiye Ph apka 7.5 to 8.0 tak hona chahiye TDS apka 1200 se 1500 tak hona chahiye
👉Weekly ahu room clean and filter condition check And abnormal sound check 👉Monthly filter clean ahu room clean belt condition moter terminal check 👉Half yearly greasing in moter and bearing and blower terminal check 👉Yearly ।। Same repeat half yearly condition
😊 desi jugaad yaar ek hi hai ki jaise hi complaint aaye ki cooling jyada ho rahi hai ۔۔to aap actuator ko thoda sa off karde matlab 20 ٪ aor agar complaint aay ki cooling kam ho rahi hai to 100 ٪ open karde ۔۔actuator ke uper ke cover ko hataoge to apko ek nob dikhegi jise ghumane se on aor off actuator ho jata hai۔۔۔use aap ek scru paanha se open ya close kar sakte hai
delta ..mean difference T .. mean temperature yani difference temperature hota hai delta t ka matalab...ye ham chiller ke inlet watee temperature and outlet water temperature se nikalte hai ... jaise 👉 inlet watee temperature 12 digri celcius 👉and outlet water temperature 7 digri celcius.. to ...inlet aor out let ke beech ka difference 👉 5 digri celcius hai ...to yahi hamara delta t hoga 🤗
Sir video bahut mast hai
Apka har video powerfull hota, hm apke video se bahut kuch sikhe hai sir Or abhi our bhi jyada ummid hai apse Thanku Sir
Fully detailed information.
Thanks sir ji
thank you for supporting 👍
Aap bahot achha se samjhate hai sir aapka sabhi video mujhe pasand aata hai
thank you dost 👍
Aap bahot acche se samjhaye hai sir... Dil se sukriya😊
sukriya boss...
You ara a successful HVAC er sir ji
Bahoot sukriya ji apka 💐
👍👍👍 sir aapka video me bahut interested aata next video filters pe banye all filter details
Dear sir ur all video for HVAC very good 👍
Nice video sir
Sir ek video ispe bhi bana dijye ke HVAC system mein kitne tarah ke valve lage hote hain aur kahan lagate hote hain aur uss valve ka kya kaam hai
Sir your Chanel is a best channel for HVAC
Bahoot sukriya ji apka ۔۔💐💐
Bahut aasani se samjh mai aa gya sir❤
very good 😊👍
Nice video 👍
Sir Chiller Plant ka PPM pe bhi ek video banaye
Thank you bhai , aap ka explanation toh dil se aata hai. sir aapne bataya 8 AHU hai aur building me 10 floors hai . Itne high capacity waale 8 AHU hai toh floor sizes bohot bade honge. is it an office type building ?
Dear sir you give such a good knowledge to us. But if drain try full of water you said only 2 reason drain line Chowk and cooling coil was leak.anthor reason also if fahu and ahu bag filter and pre filter was fully bloke( darty) that time also water more in drain try and water came out to unit
Sir hum aap ke bahot bade fan ho gye h..
Ji bahoot sukriya apka 🤗🤗 my heart is full happy .. bas ap logo ko kuch seekhne ko mile hamare liye ye bahoot hai 🤗🤗
@@c4chiller9984 thank you sir thank you so much.
Sir aap kise hai, apke video khub accha rahety he,our aap practical dikhate hai bahut accha god bless you sir🌹🌹🌹
Bahoot sukriya ji apka .. 🙏
But .. mai apka Bhai hu ..koi sir nahi
Please Bhai bola kare 🤗
Ahu ppm me
Have to chwck
1. Ahu room cleaning
2.check temp gauge
3.Check Pressure gauge
4.check all dampers
5. AHU control panner wiring check filters
6. Check blower belt
7.check gressing
8.check motor terminal
9.check drain line
10.check limit switch
Then preaper history chart as per your inspection
Right sir .??
Brilliant 👌
Sir ek request h ek video AhU ki bowler size ,rpm, kis type ka bowler use hota h ahu me,cooling ka size, types of cooling coil
Interview point of view se
Sir apki har vdo super helpful hoti hy kasam sy Allah apko or bhi kambyabi dy ameen aor sir Happy birth day 🎂 sorry us din me apko wish karna bhool gaya Allah apko any wali zindagi me or bhi khushia dy amen
Ji bahoot sukriya apka 🎉
Nice information & knowledge
Bhai Jaan .. Mujhe janna hai.. Superhit high jata kis kis waja se Chiller me.. Or low kis kis waja se hota
Beautiful explanation 👌
Sir agar hvac mein antifreeze kharab ho jaye tou kya hoga
PPM Kitne dono baad karate hai ?
Carvising kitne dino me karte hai ?
Thank you sir
For Describe the PPM of AHU And Provided complete details about AHU step by step .
Sir I have One question
Describe the Heating system in HVAC And how to supply Hot air through out duct in a room.
Please makes separate video of this question
Thank you .. will upload your recommend vidio after free time
@@c4chiller9984 Thank you so much
Sir mera ek request hai ki jo chiller ki display hai uske bare mein ek puri video banayiye kaise Kam krta hai kya kya check krte hai .
Thank you
Sir ek video all Valve ke bare mai or uska work ke bare bataye please 🙏 sir please bahut jarurat hai sir
Very very good describing
👍
Really you are great sir
Sir High current limit kya hai ?
jab bhi chiller FLA ke hisab se jyada load leta hai to us time high current limit ka alarm show hone lagtA hai
Sir High current limit 95 set hai fir kyo esha ho rha hai
iska matlab apke chiller pe 95% laod se jyada load hai ...aap use 100% FLA set karo .....agar tabhi bhi aata hai to apko second chiller start karna hoga
Sir 2nd chiller on hai dono me yhi dikha rha hai high
delta T kya aa raha hai dost ?
Nyc video
One question sir .types off filter in Ahu please answer sir
Mujhse interview me pucha gya
maixmum use hone wale filter
1. pre filter
2. bag filter
Thank you for information 🙏
Sir compressor ka andar kya rahta hai kaise kam karta hai score Chillar ka
Sir blower fan motor ka ampere kitna hona chaye sir jab ppm.karte time karte hai
ahu ka blower hai apka ?
Thanks❤❤❤ Sir
Good information bro
Bahoot sukriya ji apka 👍
Nice info... thanks sir
Sukriya
Sir i have one doubt about actuator u are saying actuator is always connect on return line of ahu bt i think it always connect in chw supply line so plz clear my doubt
Its always connect in ahu out line ..
Dekhiye .. ..aap instagram pe aaiye apko qlear batate hai ji 👉its id kgufran195
Bhai out let me hota actuator
Hello sir good morning AHU ka PPM clear Ho gya hai
Sir 5 c aa rha ha delta t
4 se 5 digri celcius standard hai dost 👍
Sir matlab nahin samjha sar main fresher hun
Dost ...ye Instagram I'd hai meri aap yaha pe massage karo Mai clear karta hu apko ..I'd 👉 kgufran195
Sir aapka Instragram pe account nhi mil rha
VERY GOOD EXPLANATION THANKS
Ji sukriya apka 💐
Sir aap kaha se hai india me
Sir chiller main candancr approach temp 10 tk ja raha h koi advice dain kaya krna chaiya
10 kya hai celcius ya fahreniht
@@c4chiller9984 11.1 Fahrenheit h aj ki
Check the dscaling time ..matlab apka condenser ki kab descaling hui hai ...aor ye check kare ki apke cooling tower ka water parameter kya chal raha hai ...PPM,PH TDS
Ppm apka 40 se 60 hona chahiye
Ph apka 7.5 to 8.0 tak hona chahiye
TDS apka 1200 se 1500 tak hona chahiye
@@c4chiller9984 OK sir thanks plz agr ho saki to cooling tower solenoid valve kaha laga hota h wo explain kr dain
@@c4chiller9984 👌
Sir chiller 7 •c pani ka temp de rha hai TB AHU me kitna degree pahuchega
7.5 to 9 digri celcius depend on your distance
Ppm .. plan preventive maintenance
Ji wo plant nahi hota .
Plan hota hai ... Qki ham kisi cheej ko dekhte hai to प्लान karke dekhte hai ... Sukriya
@@c4chiller9984 ok right
Vfd ko kaise kaise set karte hai uska para meter kya hota hai sir
Super❤
history card m kya kya data update hota h
AHU me filter kitne type ke lage hote Hai
Ji ...ham is topic par vidio upload kar denge sukriya
Shukrya bhai
AHU kitne CFM ka hai kaise pta krenge ?
Good explain
Thanks for liking
SE Ahu Ka pph Kitana month pe karte h
every week and
every monthly
sir planium box ka kya use hota hai
Ji air ko ek tarah se store karne ke liye ki air ka presser duct me tez na ho aor noise kam karne ke liye
@@c4chiller9984 OK thanks sir.
very good
Ahu ka bearing kaise change krte hai
bhai ahu m weekly, monthly , half yearly , yearly m kya kya ppm hota h plz guide me
👉Weekly ahu room clean and filter condition check And abnormal sound check
👉Monthly filter clean ahu room clean belt condition moter terminal check
👉Half yearly greasing in moter and bearing and blower terminal check
👉Yearly ।। Same repeat half yearly condition
@@c4chiller9984 thanks bhai
@@c4chiller9984 apko konsa country m job kr rahe ho bhai
Sar ji RH ke bare mein bataiye
सर जी हमार AHU का auto function खराब हो गया है। कोई देसी जुगाड है actuator cantrol करने के लिए।
😊 desi jugaad yaar ek hi hai ki jaise hi complaint aaye ki cooling jyada ho rahi hai ۔۔to aap actuator ko thoda sa off karde matlab 20 ٪ aor agar complaint aay ki cooling kam ho rahi hai to 100 ٪ open karde ۔۔actuator ke uper ke cover ko hataoge to apko ek nob dikhegi jise ghumane se on aor off actuator ho jata hai۔۔۔use aap ek scru paanha se open ya close kar sakte hai
😜😜 यही तो कर रहे हैं।
लेकिन शाम चार बजे घर जाते समय बाहर का तापमान 38 तथा सुबह में 27 हो जाता है।
Ahu motor ka kya name hai?
Induction moter ... Prakash company
Good
👍👍
Super
🌹🌹❤️❤️🌹🌹
Sir cooling tower ka ppm kab ayega ?
Cooling tower ka ppm video bana do
Maine cooling tower ki vidio me hi ppm bataya hua hai aap dekh lena description me link hai
@@c4chiller9984 kis name se video mene tds coc ye dekhi h
🤗
😊
Hello sir
Sir chiller ka PPM ka video upload kar do Aap
Ji bilkul upload kar denge jaise hi time milega..👍
Thanks sir 🙏🙏🙏
Please explain delta T
delta ..mean difference
T .. mean temperature
yani difference temperature hota hai delta t ka matalab...ye ham chiller ke inlet watee temperature and outlet water temperature se nikalte hai ...
jaise
👉 inlet watee temperature 12 digri celcius 👉and outlet water temperature 7 digri celcius..
to ...inlet aor out let ke beech ka difference 👉 5 digri celcius hai ...to
yahi hamara delta t hoga 🤗
Plazma light 💡
special for corona 😊
How to chak CFM in AHU
Ji hamne already CFM pe vidio add ki hui hai aap link pe dekh sakte hai sukriya
32000 hazar cfm ka hai ahu
I hope
Hello vai
hellO 👍
Apki kon si company h sir??
Dost ..ye logicon maintenance company hai
Can I get your number sir?
this is my Instagram id you can ask any questions here id. 👉 kgufran195
Sir aap apna number send kijiye please
Dost its my Instagram id 👉 kgufran195
Mai Instagram nhi chalta hun
@@c4chiller9984 sir nhi aata h n मैंने बहुत बार कोशिश kiya
Sir aap kaha se hai india me
Up