How to Add Outlets to a Room | Ask This Old House

Поделиться
HTML-код
  • Опубликовано: 16 авг 2017
  • Ask This Old House’s Electrician Scott Caron adds outlets to baseboards as well as floors. He runs electric wiring from the fuse box and gets the homeowner the coverage she needs.
    #ThisOldHouse #AskTOH
    SUBSCRIBE to This Old House: bit.ly/SubscribeThisOldHouse
    Cost: $20-100
    Skill Level: Medium
    Tools List for Adding Outlets to a Room:
    Drill
    Jigsaw or router
    Wire stripper
    Screwdrivers
    Shopping List:
    Insulation rod
    Outlet boxes.
    Electrical wires.
    Faceplates.
    Steps:
    1. Turn off all power to working area at main electrical panel.
    2. Trace out cut area for each elecrical box.
    3. Drill corner holes to pilot saw blade.
    4. If necessary, drill into framing for wiring
    5. Run electrical wires from outlet box holes to electrical panel, pulling 4 feet through the wall.
    6. Strip insulation from electrical wires and attach to electrical box
    7. Attach white wires to silver screws and black wires to brass screws and then the ground wire.
    8. Use electrical tape to tape around the box.
    9. Attach box to the wall and cover with outlet plate.
    10. Repeat for each outlet needed.
    11. De-energize the whole electrical panel by shutting off the house’s main breaker.
    12. Install and arc volt breaker by attaching white and black wire to the breaker.
    13. Attach white wire from the new breaker directly onto the electrical panel’s neutral bar.
    14. Turn the main breaker back on.
    15. Electricity is not a hobby, if you don’t feel comfortable with any of these steps, call an electrician.
    About This Old House TV:
    This Old House is the No. 1 multimedia home enthusiast brand, offering trusted information and expert advice through award-winning television, a highly regarded magazine, and an information-driven website. This Old House and Ask This Old House are produced by This Old House Ventures, LLC and are presented on PBS by WGBH Boston.
    Follow This Old House and Ask This Old House:
    Facebook: bit.ly/ThisOldHouseFB
    Twitter: bit.ly/ThisOldHouseTwitter
    bit.ly/AskTOHTwitter
    Pinterest: bit.ly/ThisOldHousePinterest
    Instagram: bit.ly/ThisOldHouseIG
    Tumblr: bit.ly/ThisOldHouseTumblr
    How to Add Outlets to a Room | Ask This Old House
    / thisoldhouse
  • ХоббиХобби

Комментарии • 879

  • @rfehr613
    @rfehr613 4 года назад +129

    Gotta love how everything always works out so perfect with the basement situation

    • @LostMySauce
      @LostMySauce 4 года назад +17

      Right, I'm on a slab. This wouldn't be nearly as easy for my house.

    • @jackpast
      @jackpast 3 года назад +3

      Yup. I’m guessing that panel was just added too.

    • @The_Savage_Wombat
      @The_Savage_Wombat 2 года назад +34

      It's best to install a basement under your slab before you do this.

    • @aaronbaraiya3692
      @aaronbaraiya3692 2 года назад +2

      @@The_Savage_Wombat lol

    • @EnchantedSmellyWolf
      @EnchantedSmellyWolf Год назад

      @@LostMySauce especially with mold, web, and spiders in attic.

  • @_DixonCider
    @_DixonCider 3 года назад +18

    4:15 They didn't even edit out when he hit the customer's wall with his pliers. Smooth.

  • @youdig3691
    @youdig3691 4 года назад +143

    showed everything and nothing at the same time, awesome job

    • @thunderpower5339
      @thunderpower5339 3 года назад +6

      One of the worst of "This Old House series". Wasted my time too.

    • @kw6713a
      @kw6713a Год назад +2

      Just run the romex up the bubble frame without any drilling, the junction box will just magically appear in the basement all wired up correct for you to run to these outlets. The romex runs itself too from the panel so don't worry about passing through joists correctly etc. What's so hard to understand lol.
      Though I never expected to be a licensed electrician after a six minute video.
      Btw my house is bubble frame and I'm gonna have to drill like a madman. Place is built like a tank. 120 years ago, they didn't think about me having to run some romex upstairs

    • @Googaliemoogalie
      @Googaliemoogalie Год назад +1

      I'm sure the actual episode had details.

  • @steakwilliams4448
    @steakwilliams4448 4 года назад +221

    I love TOH. The solution always involves an ample amount of space in a basement

    • @bbtank3000
      @bbtank3000 4 года назад +15

      Steak Williams and they always edit out some steps in the process

    • @puglydoodle
      @puglydoodle 4 года назад +32

      Oh you have a basement? Try installing outlets on the first floor of a two story home built on a concrete slab.

    • @christophercrawford2736
      @christophercrawford2736 4 года назад +3

      Vortex 369 that’s what I was hoping would be demonstrated.

    • @yomomma6492
      @yomomma6492 4 года назад +1

      Or adding a light on the first floor and having no strapping

    • @_DixonCider
      @_DixonCider 3 года назад +2

      Those of us not in century old houses on the upper East cost of the US are like; geez...thanks.

  • @ilo5736
    @ilo5736 5 лет назад +443

    “To get started i use an insulation rod...”
    “What is that? A drill-bit?”
    “Not really. It’s an insulation rod.”

    • @bfsgman
      @bfsgman 4 года назад +166

      "And we put it on the end of a drill and use it as a drill bit."

    • @bellyroar3206
      @bellyroar3206 4 года назад +10

      @Crotch Banister yup and I've used it many times for coax fishing. Nice because it's an easy hole to repair if you miss your mark. Only issue it they don't seem to make coat hangers like that anymore lol

    • @Geoff_G
      @Geoff_G 4 года назад +6

      I've used a cut coat hanger to drill a pilot hole from outside my house through the cedar siding, the house wrap, the sheathing, the insulation, the vapour barrier and the drywall. About 7-1/2" total thickness.

    • @JJ-rf7dg
      @JJ-rf7dg 4 года назад

      lol

    • @Justin1020304
      @Justin1020304 4 года назад +9

      This girl would be screwed without a man in her life

  • @FixItYerself
    @FixItYerself 6 лет назад +517

    "ok, pull about 4 feet". customer pulls 10 for good measure

    • @quiensoyyo900
      @quiensoyyo900 4 года назад +17

      Just in case, u never know...

    • @conqwiztadore2213
      @conqwiztadore2213 4 года назад +20

      They're not trades people ok. I bet they would cry if they had to use a Porto- potty with no running water everyday at work

    • @joshfenton5522
      @joshfenton5522 4 года назад +21

      That's why you charge double when the homeowner wants to help.

    • @davec.3198
      @davec.3198 4 года назад +17

      Sometimes it is nice to marry a woman who is really bad at measurements.
      Totally unrelated,,,small hands as well.

    • @Eleutherios1
      @Eleutherios1 4 года назад +7

      @@joshfenton5522 Its double when they want to watch, triple when they want to help.

  • @justgivemethetruth
    @justgivemethetruth 6 лет назад +143

    LOL .... "what is that, a drill bit?"
    no, this here's a long sharp wire we use as a drill bit.

  • @blackdog850
    @blackdog850 4 года назад +8

    What a great episode! Highly functional value for the homeowner! Great job THS! :)

  • @Geoff_G
    @Geoff_G 4 года назад +111

    So... that was easy in a hundred year old house.
    Now try adding an outlet in the ground level of a 1970's house on a concrete slab with no floor voids and 2" high baseboards. That would be my house, by the way.

    • @lilibetp
      @lilibetp 4 года назад +1

      Yeah, and my apartment.

    • @bleachfamingtoniii7196
      @bleachfamingtoniii7196 4 года назад +29

      And my axe

    • @DaniPrays
      @DaniPrays 4 года назад +2

      I was born in the 70’s....I am not “Old” 😩 I am Forever 21...Your house doesn’t apply 😁

    • @Geoff_G
      @Geoff_G 3 года назад

      @Mr. Meeseeks I ended up ripping into the ceiling because the attic is above the second floor. Some jobs there's just no easy way. LOL

    • @bb5242
      @bb5242 3 года назад +1

      my basement is finished, impossible to fish wires to the box due to duct work

  • @patriot1303
    @patriot1303 6 лет назад +132

    You should do a video showing how to wire it in through the attic (for those of us on a slab) and how to get through the fire blocking that is in most walls. It would be a great compliment to this video - im an electrician but i always find watching your videos to be interesting and i even learn some things sometimes too - keep it up

    • @ward26102
      @ward26102 6 лет назад +2

      Patriot1 Shouldn't one see how many other receptacles and fixtures are on the circuit and what they are being used for, prior to adding new receptacles? Might be exceeding available amperage otherwise?

    • @ZackFletcher1
      @ZackFletcher1 6 лет назад +11

      He ran a new circuit for the plugs he added. Watch the video.

    • @ward26102
      @ward26102 6 лет назад +4

      I stopped watching because I have a slab on grade so this doesn't really apply. Thanks for the info.

    • @cup_and_cone
      @cup_and_cone 6 лет назад +3

      Laura Ward -- Yup, about 9/10 homes featured on TOH are raised pier or crawl space homes. About every house in the South is concrete slab. Regional differences.

    • @RixCanDoit
      @RixCanDoit 6 лет назад +4

      Patriot1 I agree. My house is on slab. If I want to add additional outlets to the same room, I'm guessing I will have to tear up a lot of drywall in a straight horizontal direction in order to drill through studs for wiring. I can't imagine having to run each outlet wiring up into the attic and back down again for each additional outlet. Would love to see how a pro handles that.

  • @TarekFaham
    @TarekFaham 6 лет назад

    Just wow! I learned a lot by watching thus video and I will watch several more times just because I liked it... Thank you so much!

  • @matblack9288
    @matblack9288 3 года назад +1

    Happy New Year This Old House! May I wish you a prosperous, happy & healthy year! ❤️

  • @Jesse-gv9tf
    @Jesse-gv9tf 6 лет назад +4

    Sounds like a good project for this weekend.

  • @angelinimartini
    @angelinimartini 2 года назад +5

    I want to say, I’ve been watching This Old House for about two decades and I find this show to be such a treasure!!! I feel like I can do anything with my house! Of course, I won’t because some stuff requires more than one person but this show is just so awesome and informative!

  • @ericwood8745
    @ericwood8745 3 года назад +1

    When he beat on that box with his lineman’s I felt that lol

  • @andrewjames3908
    @andrewjames3908 6 лет назад +13

    At 5.45 i thought for a second he was wearing the tv on his back

  • @MrAndyCarlos
    @MrAndyCarlos 6 лет назад +96

    2:46 Watch your back, girl! Lol.

  • @patmash
    @patmash 6 лет назад +1

    Absolutely 1 clean job. Fantastic how to video.

  • @JoeClyde579
    @JoeClyde579 6 лет назад

    Very helpful. Makes it look so simple.

  • @bartcornelissen7090
    @bartcornelissen7090 6 лет назад

    Nicely done , Scott!

  • @HisLoveArmy
    @HisLoveArmy 6 лет назад +19

    These videos are great but you can totally tell that they give those questions for the client to ask. haha

    • @everynewdayisablessing8509
      @everynewdayisablessing8509 6 лет назад

      You are probably right. I dd not stand behind my electrician asking him questions.I wanted him to do it right, so I left him to it.You will not become an electrician in 20minutes.

  • @AJourneyOfYourSoul
    @AJourneyOfYourSoul 5 лет назад +5

    My new house has the outlets in the baseboards, but not installed sideways, installed the normal way. Looks so much better with them in the baseboard. Really cleans up the walls. It’s a nice little detail.

    • @blakerichardson8426
      @blakerichardson8426 3 года назад +2

      Really nice until you have to reach down to the floor to plug something in later on when your 70 years old. The lowest I’ll ever go is 18 inches to the bottom of my plugs.

  • @Danny-fs1hk
    @Danny-fs1hk 3 года назад

    Another great instructional video.

  • @BigGoldenYoshiFan
    @BigGoldenYoshiFan 4 года назад +2

    You taught me so much about how easy it is to do simple wiring like this, thanks!

  • @devingoins361
    @devingoins361 6 лет назад +4

    I love this show it is so informative

  • @sg5725
    @sg5725 3 года назад +1

    Cutting that beautiful molding.

  • @Bill-IONS
    @Bill-IONS 4 года назад +22

    Let’s see a video on how to repair the baseboard because some electrician drilled holes in your baseboards!

  • @KarlH1980
    @KarlH1980 6 лет назад +12

    Enjoyed reading the comments. Particularly found the comments from those outside the US interesting. As to the video I have some comments/questions. Why use metal boxes vs. plastic. I don't see the advantage and I've been installing outlets in my homes and for friends for many years.
    Also I strongly discourage putting the outlets in the baseboard and certainly don't like to do place them in sideways. I did that all over the second floor in our home when I ran into issues with lots of cracking when trying to put them into plaster. My wife H-A-T-E-D the sideways plugs. There were too many things that the plug is designed to be vertical not horizontal. She liked those oil fragrance things for awhile and she couldn't use them on the second floor. And you know what they say. If the wife ain't happy... tell her to get you a beer. That'll get her out of your hair for a minute. The biggest reason I won't use the baseboards again though is that I don't know what the home owner is going to want in 20, 30, 70 years. There is no repairing that hole you put into a solid oak board.
    I've actually come looking for better methods to install outlets into plaster walls than what I've used in the past. Too bad we weren't shown how he worked the entertainment system items.
    Thanks for making the video. I picked up some tips. One final question. You used a power drill to screw in the anchor screws. Why did you use a hand screwdriver to tighten the outlet screws. I'm impatient and lazy (in other words ... efficient). I use my power drill for everything. I'm so spoiled:) Speaking of which. I just got a battery for my original Black and Decker VersaPak screwdriver. That is THE BEST power screw driver I've ever had. I used to use it on everything small. Home stuff. computer stuff.

    • @thenexthobby
      @thenexthobby Год назад

      "Why use metal boxes vs. plastic." Because that wasn't being installed in drywall, which is the only kind of wall plastic boxes are intended for.

  • @Pure_KodiakWILD_Power
    @Pure_KodiakWILD_Power 6 лет назад +202

    "i'm going to give you outlets everywhere; how does that sound?"
    "well that sounds re---"
    "great, let's get on with it."
    😂😂

    • @richardm1075
      @richardm1075 6 лет назад

      LMAO :)

    • @johnsmith-qe2fd
      @johnsmith-qe2fd 6 лет назад +9

      “It’s a freakn outlet bonanza, now call ya friends we’re gonna have a potty”.....her: “ummmmm?”

    • @eksine
      @eksine 5 лет назад +1

      Next I'm gonna replace all your lamps with light sabers

    • @agarcia8800
      @agarcia8800 5 лет назад +1

      She said it sounds great.

  • @cillyede
    @cillyede 6 лет назад

    Well done!

  • @larrygill2223
    @larrygill2223 4 года назад +42

    Good lord! Did they specifically scout for the easiest place to work?? Like many others have said, this isn’t normal lol.

    • @johnnyboy13642
      @johnnyboy13642 3 года назад

      Yeah that is just...not right...LOL.

    • @LuisGomez-le4vk
      @LuisGomez-le4vk 3 года назад

      Is a tv scam no real job no concrete in wall no damage drill bit very easy no dust

    • @adam1885282
      @adam1885282 3 года назад

      They absolutely do, every one of these videos has 100% easy access to whatever needs fixing.

  • @kingraiderr
    @kingraiderr 4 года назад

    This guy is amazing .

  • @thellanosfamiy
    @thellanosfamiy 4 года назад

    awesome work.

  • @chrisofnottingham
    @chrisofnottingham 6 лет назад +434

    How to Add Outlets to a Room - that is unlike 99% of rooms

    • @lucaschan9079
      @lucaschan9079 5 лет назад +67

      next on this old house how to install an outlet in the bottom of your bathtub for your hairdryer

    • @vwtroy
      @vwtroy 5 лет назад +24

      i guess its a different part of the country , cause i aint never seen it be that easy.

    • @valentingutierrez9374
      @valentingutierrez9374 4 года назад +2

      @@vwtroy that's what I said 😂😂

    • @jsprdn
      @jsprdn 4 года назад +45

      That's a standard room in ... an old house. Kinda like the title of the tv show !!

    • @wizard3z868
      @wizard3z868 4 года назад +17

      Yup a lot of homes in the north east are like this one

  • @vampiregoat69
    @vampiregoat69 2 года назад

    I LOVE the look of the house

  • @cdoublejj
    @cdoublejj 5 лет назад

    Great information!

  • @RoastBeefSandwich
    @RoastBeefSandwich 3 года назад

    floor outlets are wonderful.

    • @minermen16
      @minermen16 3 года назад +1

      They are unless you are elderly or have a back problem or worse. Having a water damage in that area and have to take up that floor and water could have damaged that outlet sometimes causing a fire because either the box is outdated with no safety measures or simply because there was no ground.

  • @chrisdaniels4674
    @chrisdaniels4674 4 года назад +22

    when did he run the hdmi wires and how

    • @faraanhadi
      @faraanhadi 3 года назад

      Probably a PVC pipe or just behind drywall with pipe fitting

  • @Joseph1NJ
    @Joseph1NJ 6 лет назад +3

    I respect that he pays attention to aesthetics when doing work in people's homes.

    • @MAGAMAN
      @MAGAMAN 2 года назад

      You mean putting outlets in sideways?

  • @hedwardrodriguez2538
    @hedwardrodriguez2538 6 лет назад +2

    Nice work

  • @smilinj6074
    @smilinj6074 4 года назад +4

    Me: follows instructions and has 5 wires going to circuit breaker.

  • @azeraeth
    @azeraeth 2 года назад

    That was a great video!

  • @toddkratzer7953
    @toddkratzer7953 2 года назад

    Good job.

  • @TitanicTruths
    @TitanicTruths 6 лет назад +10

    Actually, as long as you use a power strip as intended, it will be just fine even when fully loaded. What you dont want to do is put more than one together, or add splitters to create more plugs than the manufacturer gave. The strips and surge protectors and other safe guards buily in, use them right and youll be fine. As with anything.

  • @athay14
    @athay14 3 года назад +6

    I am so done. I told an electrician I wanted my outlets recessed into the wall and he told me he couldn't without tearing the wall apart. His solution was putting those ugly external boxes on the baseboards. Had no idea this was an option.

    • @NeighborSenpai
      @NeighborSenpai 3 года назад +3

      Idk man this electrician doesn't look very professional or maybe you have a cement wall

    • @electriciantv5174
      @electriciantv5174 3 года назад +1

      I would’ve called a new electrician when you heard him say that

    • @phlythaiguy1
      @phlythaiguy1 3 года назад +2

      If you have a wall with typical stud construction and no void spaces, the only other way would be to open up the wall 12” wide the length of the wall 18” above the floor. Then you’d have to drill every stud to run wiring. Your electrician is right

    • @noelv1976
      @noelv1976 3 года назад

      This house sbown is not common in other parts of the country. There are no basements in Texas, I can tell you that much. What he did in this video would require a massive demo and replacement of drywall, if you want the outlet to be recessed with the wall.

    • @MAGAMAN
      @MAGAMAN 2 года назад +1

      This is only an option in a perfect scenario. Do you have a basement or crawl space? No? then this won't work.
      shows like this give people an unrealistic expectation. Not only is this scenario rare, they cut out all of the hard work from the video, making it look really easy.

  • @kingraiderr
    @kingraiderr 6 лет назад

    Brilliant

  • @lal12
    @lal12 5 лет назад +3

    The cables allowed here in Germany are definitely rigid enough to withstand stepping on it, unless maybe you are in some kind of hotel where very many people would step on it for years. But besides the would only be one arc before the breaker or the residual current circuit breaker depending on the wires touching. This usually cannot make a fire.

    • @JohnSmith-ys4nl
      @JohnSmith-ys4nl 5 лет назад +3

      Old houses like this don't have arc fault breakers. Arc fault breakers became code in the U.S. around the year 2000. And it's only been in the past few years that they are required on all circuits. That said, I agree with the guy in this video. You should avoid extension cables where possible.

  • @mss627
    @mss627 6 лет назад +4

    Yeah, it always looks so easy on TV. Snaking wires requires major drywall work in most homes.

    • @wizard3z868
      @wizard3z868 4 года назад

      Like a lot of homes in the north east Basements are a Savior for the main floor at least 😉

  • @shaire99
    @shaire99 6 лет назад +50

    That's what This Old House does almost every time, , , they show the easiest scenario where there's plenty of room to just daisy chain through a nice big crawlspace of basement. My grandma could do that . . . . show us how to add outlets where its NOT easy enough for a child to do!

  • @rmcc0621
    @rmcc0621 4 года назад +16

    I honestly thought he said carpet wiring and then he continued to speak and realized he meant copper.

  • @MRSTEEL15
    @MRSTEEL15 10 месяцев назад

    Makes it look easy 😅

  • @Googaliemoogalie
    @Googaliemoogalie Год назад

    When the oscillating tool was cutting the baseboards I could actually smell the sawdust burning just watching that smoke

  • @SeanBaker
    @SeanBaker 4 года назад +6

    My house was built in 1964, and I'm still often surprised at how many outlets I have in this house. Someone clearly did some work in here before I moved in.

    • @pbufh
      @pbufh 2 года назад

      Probably a math lab

  • @probegt75
    @probegt75 4 года назад +7

    Show how to get a receptacle on the second floor with a finished basement...

  • @ivorycrown8673
    @ivorycrown8673 6 лет назад

    good job

  • @briankohlenberg
    @briankohlenberg 6 лет назад +2

    Nice job, Could u send more time explaining the solution to running the wires in the house, screwing the wire to and outlet gets old after the 1st time. What about in houses WO basements, where drywall is covering up everything and you have to go into the attic.

  • @clutchgaming2289
    @clutchgaming2289 6 лет назад

    Great 👍 job

  • @foxfiresidechats5227
    @foxfiresidechats5227 4 года назад +4

    I think he just broke a new world record for the fastest, best looking pigtails lol. I’ve still got work to do

    • @vandammefan34
      @vandammefan34 3 года назад

      Right??!! Man alive, takes me forever. I doubt that he blinked lol

    • @MAGAMAN
      @MAGAMAN 2 года назад +1

      @@vandammefan34 You think this is difficult?

    • @vandammefan34
      @vandammefan34 2 года назад

      @@MAGAMAN I dont do it everyday so it takes me a bit. I wouldnt say difficult though.

  • @tcpnetworks
    @tcpnetworks 3 года назад

    Scott's philosophy - Everything is a hammer. :)

  • @mikefox2379
    @mikefox2379 6 лет назад +1

    Glad to see instruction done by someone who actually knows what he is doing. I have seen a few videos on RUclips that were code violation after code violation. One kid had open splices in the attic and he's showing other people how to create the same fire hazards.... Oh my

    • @MAGAMAN
      @MAGAMAN 2 года назад +1

      RUclips is full of safety violations and people are destroying their property and in some cases killing or severely injuring themselves because of it. RUclips should be held 100% financially and legally responsible for all its content.

  • @PatHaskell
    @PatHaskell 3 года назад

    Nice to have an assistant with small hands.

  • @nicholasd7731
    @nicholasd7731 2 года назад +1

    My grandparents ran their stereo systems wires through the carpet like that.

    • @joaquinsuarez6090
      @joaquinsuarez6090 2 года назад

      Speaker wires are not dangerous, so don't worry about your grandparents safety.

  • @billcahill4218
    @billcahill4218 5 лет назад +32

    The cord under the carpet was staged. It's brand new, you can see the kinks in it from when it was folded up for packaging. It would have been worn flat had it been under there for any real length of time.

    • @violetfrank581
      @violetfrank581 4 года назад +10

      Good spotting. You my friend should be a detective.

    • @Bootstrahps
      @Bootstrahps 4 года назад +9

      Nothing gets by Bill cahill

    • @shadowblack1987
      @shadowblack1987 4 года назад +4

      Bill Cahill, pet detective!

    • @leonardholt5311
      @leonardholt5311 4 года назад +3

      We’ve got a detective here

    • @pejpj2890
      @pejpj2890 4 года назад +2

      Bill cahill to the rescue. Heee haaaaa

  • @JayWC3333
    @JayWC3333 6 лет назад +25

    I love it when these electrical how to videos are done in locations where conduit are not required. Anyone can install an outlet that way. Do this in conduit and you add a lot of complexity.

    • @TheLastSpartan04
      @TheLastSpartan04 6 лет назад +4

      JayWC3333 exactly, and that's why there are licensed electricians

    • @jameshawkins809
      @jameshawkins809 6 лет назад +3

      JayWC3333 it's not required for homes.

    • @JayWC3333
      @JayWC3333 6 лет назад +2

      Where I live and work conduit is required for homes too.

    • @jameshawkins809
      @jameshawkins809 6 лет назад

      JayWC3333 in America?

    • @JayWC3333
      @JayWC3333 6 лет назад +3

      Yes! I live and work in Illinois. So, your comment about conduit not being required in homes is not correct.

  • @evilAshTheDog
    @evilAshTheDog 2 года назад

    95% of a job like this is balancing the act of finding a decent outlet location with finding a reasonable wire path before your first cut. It’s rare to find such an easy path as was shown here. Still a good video!

  • @linod7265
    @linod7265 6 лет назад

    Congratulations Scott. Nice and neat job. Just 3 questions, 1st.- When running HDMI cables, What distance between HDMI cables and Power cords I must leave between them to avoid noise? 2nd .- If I run each cable( not three in one insulation) do I need to join them with electrical tape or just knit them, or leave them straight each? and 3th.- How did you run the cables from each outlet in the wall and below the floor? Thank you for your video.

  • @nicholaswalker3200
    @nicholaswalker3200 2 года назад +1

    "Is that a drill bit?"
    "No, you put it in a drill and use it as a drill bit."
    thanks for the clarification

  • @WizardMower
    @WizardMower 3 года назад +2

    3:11 He should've left some more rubber sticking out, Because the rubber (insulation) will eventually wear down and the copper touching the metal box can make an electrical short.

  • @somhrsh
    @somhrsh 6 лет назад

    Only if I had a house like this

  • @Robert1965ish
    @Robert1965ish 6 лет назад

    Nice work, I need my work shop wired up and a 240 for welding ?

  • @Yz85rider338
    @Yz85rider338 3 года назад +2

    Awesome video, not to be that guy but I'm not so sure those receptacles being that low to the floor meets code in most areas! Check code in your area before installing that low!

  • @stevesid4403
    @stevesid4403 6 лет назад +3

    I don't think it's necessarily code, but I know the NEC recommends pigtails instead of attaching both sets of wires to the outlet. The method shown in the video will save you some wire nuts and wire but is pretty old school.

    • @leonardholt5311
      @leonardholt5311 4 года назад +3

      Steve Sid the NEC doesn’t make recommendations

    • @electricaf365
      @electricaf365 3 года назад

      @@leonardholt5311 🤣🤣🤣 I forgot about that “recommendations” section of the NEC

  • @michaeld.3779
    @michaeld.3779 2 года назад

    Pretty easy if you have and access area-like a basement.

  • @cattigereyes1
    @cattigereyes1 4 года назад +1

    Gauge 20 amp wire for outlet for power draw is better separate lighting on 15 gauge, these outlets are all linked same breaker meaning the draws all from one

  • @wizard3z868
    @wizard3z868 4 года назад

    Insulation rod try a coat hanger cut with a sharp point shown that 25 yrs ago

  • @macmorgan6685
    @macmorgan6685 Год назад

    Surprised a #1 square drive screw driver wasn’t used on both the receptacles and the gfi/arc breaker on the circuit breaker box. I also believe that torquing the connections should be done.

  • @joshsteele5701
    @joshsteele5701 2 года назад

    So nice of him to hide those tv cables

  • @geoffmorse4366
    @geoffmorse4366 6 лет назад +1

    In the Chicago area, you can’t use Romex, code calls for metal conduit

    • @jamesdarnell8568
      @jamesdarnell8568 4 года назад +1

      And in Chicago, they still required lead pipes for your water service until the Feds banned it in 1986. Let's not do things the "Chicago way" if we don't have to.

    • @electricaf365
      @electricaf365 3 года назад +2

      In Chicago, 10-15 murders take place over a weekend

  • @AngelLuisTrinidad
    @AngelLuisTrinidad 6 лет назад +3

    Okay, please do that on my concrete house.

  • @lopakaa3288
    @lopakaa3288 6 лет назад

    I love ur Shows I wish. U could come to Hawaii and help us with our house😍😍😍

  • @Trafficlight678
    @Trafficlight678 4 года назад

    Can I use this installation process to install telephone or cable TV wall jacks
    Because we need to add more phone and cable TV jacks

  • @ottoschless4115
    @ottoschless4115 5 лет назад +1

    Where i am from, electrical outlets must be a minimum of 75mm from floor level to the bottom of the outlet.

  • @benjaminkline4855
    @benjaminkline4855 4 года назад +3

    It's an outlet every 7 feet here, and those are standard receptacles now

  • @emanuelgrella8090
    @emanuelgrella8090 Год назад

    Awesome instructions! Should the metal boxes have been grounded for extra protection?

    • @Googaliemoogalie
      @Googaliemoogalie Год назад

      you should always do that. Its code in a lot of areas too.

  • @uptopmikep7065
    @uptopmikep7065 3 года назад

    That's great if you have a basement. How would you do it when you have a slab?

  • @ThinkTheory
    @ThinkTheory 5 дней назад

    What about when you have an old house like this but you need outlets added to the second floor and you can’t just run a wire from the second floor to the basement??

  • @brucecyganoski4200
    @brucecyganoski4200 Год назад

    I have a couple of electrical outlets that have No Power GOING to them , they use to work before, I CHECKED the circuit breakers they seem to be fine, I also checked the electrical outlet, the connections they also seem fine.Can you assist me with this problem, I am in the Rhode Island area, PLEASE Advise

  • @ttpechon2535
    @ttpechon2535 2 года назад

    1:30 That whole series of words was ridiculous.. XD

  • @bwakel310
    @bwakel310 6 лет назад +10

    Sweet! Can you come and do my house next?

    • @AnaIG4
      @AnaIG4 4 года назад

      bwakel310 yeah for 5 grand lol

  • @rachelzacherl8245
    @rachelzacherl8245 Год назад

    What if you don't have studs? I have an old house with plank framing. Nobody ever seems to have info on dealing with plank framing.

  • @gerardosalas9477
    @gerardosalas9477 4 года назад +1

    It’s easy to add outlets, and anything really to a house, if your house is a box made of triply wood.

  • @josemacon7385
    @josemacon7385 3 года назад

    Does this method work for adding outlets on a second floor of a home

  • @felixjimenez7272
    @felixjimenez7272 6 лет назад +2

    Is there a video of how to fix outlets if they don't work?

    • @MAGAMAN
      @MAGAMAN 2 года назад +1

      You don't fix them, you replace them.

  • @justinwoods240
    @justinwoods240 3 года назад +1

    I swear his multi tool makes it’s own music

  • @joejackson4202
    @joejackson4202 6 лет назад +1

    A surge protector should always be used between wall sockets and electronic equipment. There is nothing unsafe about certified surge protectors that are in good condition and are used in a safe manner.

  • @AR-cp5dz
    @AR-cp5dz 3 года назад +2

    Are there any electricians that use Phillips head screw drivers? 3:54

    • @surferdude642
      @surferdude642 3 года назад

      Handyman?

    • @MAGAMAN
      @MAGAMAN 2 года назад +1

      The screws on outlets are usually flat head, so it probably just becomes a habit. In all honesty, if you are using the correct size screwdriver, the flat heads are better than the Philips.

  • @XxGR4V3R41D3RxX
    @XxGR4V3R41D3RxX 6 лет назад

    Not sure where this is, but where im from, there is a local ordinance that requires everything to be pigtailed

  • @anthonya.torchia396
    @anthonya.torchia396 2 года назад

    Idk maybe I missed it but I didn’t see him ground the metallic box. Maybe the outlet has the self grounding clip but I prefer to ground the box the right way anyways.

  • @JonO387
    @JonO387 4 года назад

    What do I do if I don't have a basement to pull from?

  • @tcntad87
    @tcntad87 6 лет назад

    3:33 it sure goes in