Ek fcu me supply temperature sahi hai and return bhi sahi hai stainer pura clean hai valve proper open hai aur jab fcu start krte hai to return coil heat ho jaata hai fir cooling nhi krta kya problem jo skta hai plz reply
Sir how to calculate heat load such as door windows .electrical load .mechanical load . Man as worker in side office shops etc for air conditioner design.
FCU actuator is working normal, actuator cartridge is also ok, room thermostat is ok, stariner cleaning, FCU motor is working normal,chiller supply return temperature is also normal CHILLER PLANT CWS 7°C/ CWR 12°C,Chilled water line pressure is normal in building around 2.9br as per design, supply return gate valve is open, by pass valve close, stariner clean, chilled water coil cleaning done , FCU filter also clean but still my FCU not cooling no sweating in chilled water supply line, Please assist.
As per my knowledge air lock in fcu chilled water line, please remove air lock in chilld water line to draining the water and same time note the chilled water supply line temperature it should chilled automatic when proper circulation in chilled water.
Excellent explain sir
❤
Kafi acha explain kiya Apne.. thanks 😊
Ek fcu me supply temperature sahi hai and return bhi sahi hai stainer pura clean hai valve proper open hai aur jab fcu start krte hai to return coil heat ho jaata hai fir cooling nhi krta kya problem jo skta hai plz reply
manual valve band hai PIVC ka... use open kro
@@nikhilmishra1268 hn Bhai PICV valve Ka problem tha abhi Sahi hai
Bhai FCU room me cooling nahi ker raha stainer clean kiya hoon ab kya ker na hoga actuator bhi chang ketna padega kya
Nhi
Bohat accha laga
Sir how to calculate heat load such as door windows .electrical load .mechanical load . Man as worker in side office shops etc for air conditioner design.
FCU actuator is working normal, actuator cartridge is also ok, room thermostat is ok, stariner cleaning, FCU motor is working normal,chiller supply return temperature is also normal CHILLER PLANT CWS 7°C/ CWR 12°C,Chilled water line pressure is normal in building around 2.9br as per design, supply return gate valve is open, by pass valve close, stariner clean, chilled water coil cleaning done , FCU filter also clean but still my FCU not cooling no sweating in chilled water supply line, Please assist.
As per my knowledge air lock in fcu chilled water line, please remove air lock in chilld water line to draining the water and same time note the chilled water supply line temperature it should chilled automatic when proper circulation in chilled water.
Description is in English.. the video is NOT English.
Actuator to saply line par hota ha