Basically, it is recommended to use [Auto tuning] after setting the SV. If the problem continues even after [Auto tuning], set the P(Proportional band) value larger than before.
To perform auto-tuning, the temperature sensor and heater must be connected. After setting the SV, please set the [At] parameter of parameter group 1 to [ON]. The temperature controller calculates and stores the PID values after performing temperature control twice based on the SV reference.
How to set temperature to keep same as set value? My modul keep overshoot the sv
Basically, it is recommended to use [Auto tuning] after setting the SV.
If the problem continues even after [Auto tuning], set the P(Proportional band) value larger than before.
How to set Auto tuning settings?
To perform auto-tuning, the temperature sensor and heater must be connected.
After setting the SV, please set the [At] parameter of parameter group 1 to [ON].
The temperature controller calculates and stores the PID values after performing temperature control twice based on the SV reference.