Autonics Tutorial : Setting PID Control(TCN Series)

Поделиться
HTML-код
  • Опубликовано: 8 сен 2024
  • www.autonics.c...

Комментарии • 33

  • @ganiulhasan4461
    @ganiulhasan4461 Год назад

    Great

  • @muhamadsolehabdillah3124
    @muhamadsolehabdillah3124 2 года назад

    how to setting type TK4L-24SN output SSR.
    We Setting PID for Temperature Heater Stabil

    • @AutonicsCorp
      @AutonicsCorp  2 года назад

      TK4L-24SN is an SSR drive voltage output product.
      So, there is no need for separate settings related to output.
      For the PID value, set the set value(SV) and execute Auto-tuning.

    • @muhamadsolehabdillah3124
      @muhamadsolehabdillah3124 2 года назад

      @@AutonicsCorp do you have video tutorial execute auto tuning?,

    • @AutonicsCorp
      @AutonicsCorp  2 года назад

      @@muhamadsolehabdillah3124 Unfortunately, there is no video based on the TK series.
      However, it is similar to the TCN series auto-tuning method in this video. 01:52
      Just set [At] of parameter 2 group from [OFF] to [ON].

    • @muhamadsolehabdillah3124
      @muhamadsolehabdillah3124 2 года назад +1

      @@AutonicsCorp thanks you very much for information.
      I Will try

  • @joelarmy716
    @joelarmy716 8 месяцев назад

    Hola, se puede usar el modo PID con la salida Rele?

    • @AutonicsCorp
      @AutonicsCorp  8 месяцев назад

      Si, está disponible.
      Sin embargo, en el caso del control PID, la salida se activa/desactiva con frecuencia, lo que puede afectar la vida útil del relé.

  • @abi4abilo807
    @abi4abilo807 9 месяцев назад

    Please i need help it is same way for tcn4w

    • @AutonicsCorp
      @AutonicsCorp  9 месяцев назад

      The TCN4S and TCN4W parameter setting methods are the same.
      What problem might you have?

  • @LabTEL
    @LabTEL 10 месяцев назад

    How long auto tune do?

    • @AutonicsCorp
      @AutonicsCorp  10 месяцев назад

      Auto-tuning controls the temperature twice based on the SV and calculates the value.
      So, it may take more than twice as long to reach the set value.

    • @LabTEL
      @LabTEL 10 месяцев назад

      i got problem, indicator value is more higher than actually. how to solve this problem? thermometer 10-15oC lower than indicator on oven. but normal and show samevalue at room temperature@@AutonicsCorp

    • @LabTEL
      @LabTEL 10 месяцев назад

      I use tcn4s for an oven with 2 heaters using ssr. I have tried to replace the thermocouple but the measurement results when the temperature is hot are way off. I have reset and tuned pid. Is there anything wrong or missing in what I did to get it back to normal?

    • @AutonicsCorp
      @AutonicsCorp  10 месяцев назад

      The difference between the PV displayed value and the actual temperature is a problem on the temperature sensor side.
      Do the temperature sensor type used and the temperature controller settings[In-t] match?
      The PID value is not relevant to this issue.

    • @LabTEL
      @LabTEL 10 месяцев назад

      @@AutonicsCorp I have tried replacing the type K thermocouple, and the result remains the same.

  • @ramadeddyirawan12
    @ramadeddyirawan12 2 года назад

    Bagaimana kalau muncul error tpi AL 1 dan AL2 nyala semua. Bagaimana cara mengatasinya

    • @AutonicsCorp
      @AutonicsCorp  2 года назад

      If the alarm operation mode of parameter 2 group is set to [AM0], the alarm output can not be used.

  • @alex-w8p2e
    @alex-w8p2e 2 года назад

    Do you kniw where I can buy this product? Are the ones on aliexpress original or fake?

    • @AutonicsCorp
      @AutonicsCorp  2 года назад

      Visit our website www.autonics.com/company/global. Please check the nearest corporation and contact us. Thank you.

  • @Symboos1990-nl5yx
    @Symboos1990-nl5yx Год назад

    Hello. For recovery password, could you provide me the steps to reset it? I have error 6329.thank you

    • @AutonicsCorp
      @AutonicsCorp  Год назад

      Could you please check your model name?

    • @Symboos1990-nl5yx
      @Symboos1990-nl5yx Год назад

      T4KM-T4CN

    • @AutonicsCorp
      @AutonicsCorp  Год назад

      Please try [0516]. If this does not work, please contact us again.

    • @Symboos1990-nl5yx
      @Symboos1990-nl5yx Год назад

      Thank you very much for your support. It is ok now

    • @Symboos1990-nl5yx
      @Symboos1990-nl5yx Год назад

      I write you again because after i did factory reset now is asking again ne to put pass, and i have error 9300