ETAP Transient Stability Study

Поделиться
HTML-код
  • Опубликовано: 16 дек 2024

Комментарии • 12

  • @beckenbauer1974
    @beckenbauer1974 2 месяца назад

    Is there any way to simulate Transient voltage recovery after Generator fault clearance?

  • @wongsabarchannel1335
    @wongsabarchannel1335 Год назад

    What is the meaning of Bus Voltage Angle under positive Axis in ETAP during Transient (Short Circuit event) ploting manager results?

  • @wongsabarchannel1335
    @wongsabarchannel1335 Год назад +1

    Can you Plot also Gen 2 Power Angle. in my simulation Swing Gen Could not plot the Gen Angle for Swing gen, Only Voltage Control or Mvar control Generator can be plotted the Power Angle? how is that?

    • @SmartEducare
      @SmartEducare  Год назад

      Swing generator can also be plotted..
      Go to Transient stability study case editor>Plot (check against the generator to be plotted - x sign will be shown there).
      You are done 👍

    • @mkhoirun918
      @mkhoirun918 Год назад

      @@SmartEducare already can be ploted, but it not shown any oscillation, just flat. Can you check it?

  • @user-cb3oq2cy5s
    @user-cb3oq2cy5s Год назад +1

    What about transient caused by motor / transformer switching?

    • @SmartEducare
      @SmartEducare  Год назад +1

      Will be posted as separate video named Transient Stability,, keep in touch...

  • @mkhoirun918
    @mkhoirun918 Год назад

    How is about setting of Excitation?

    • @SmartEducare
      @SmartEducare  Год назад

      Response of the excitation system to the changes in generator speed / electrical output caused by system disturbances is negligible.
      Most important thing is generator reactances which are responsible for system stability..

    • @mkhoirun918
      @mkhoirun918 Год назад

      @@SmartEducare what is common value fot H of Prime mover, coupling and Generator?

  • @mohamedali-wo8zd
    @mohamedali-wo8zd 9 месяцев назад

    Thank you brother ❤