Hi there. This is a great video. I have a military generator. An MEP 005a. I have my voltage sensing hooked up and I have my F1 and F2 hooked up correctly. I'm at 60 hertz and I have the stability selection table from a2c since it's only a 30 KW generator. I do not know if it has an auxiliary winding. It has two wires that come from the genset to excite. It's a positive and negative that I have hooked up correctly to F1 and F2. Any help you can give me would be much appreciated! Thank you!
Ok, thanks.. Btw, I am having trouble with AS440 AVR. We've got supplied with AS440 instead of SX440. When running the generator we only get 40 VAC out and cannot increase. Direct Exciting with the battery increases the voltage.
Hello. I have hard time to find someone smart enough in sweden. So i try to ask you. I have a faulty avr on my stamford generator. Its Stamford newage 350-29700. Du you think i can use as440 instead. Because i cant find 350-29700
Com a regulagem máxima do avr as 440 está 210v preciso aumentar a voltagem além da regulagem volts sem passar dos 60hz Oq eu posso fazer ? Onde eu posso regular ?
@@benzblogsVlogs Boss we reach naman yong 230V, 60hZ 3phase , 35kVa... Using as440 AVR as we observe seems extreme heating ng heatsink ng as440, may need ba ako baguhin sa settings to reduce the heating? tska pano ko malalaman kung may auxiliary windings ang generator? baka need ko i follow yong isang diagram with auxiliary windings? thankyouu
@@mikeybeltran5820 sir makikita mo agad kong anong type ng alternator meron ka if shunt or arep if arep means meron na agad yumang aux winding hut if shunt its nothing aux winding
Good tutorial lods Ang galing mo talaga pag dating Jan salute sayo lods Ikaw na talaga
Same lang tayo lods di lahat ng alam meron ako sometime we need to ask also 💓😊
@benzblogsVlogs Tama Yan lods piro lapit na pasko hehehehe
Nice one again idol.yan ang idol namin.. godbless idol
Salamat lods bless you
Hi there. This is a great video. I have a military generator. An MEP 005a. I have my voltage sensing hooked up and I have my F1 and F2 hooked up correctly. I'm at 60 hertz and I have the stability selection table from a2c since it's only a 30 KW generator. I do not know if it has an auxiliary winding. It has two wires that come from the genset to excite. It's a positive and negative that I have hooked up correctly to F1 and F2. Any help you can give me would be much appreciated! Thank you!
Ahm what alternator you have so we can identify if it has a aux winding and waht avr you using?
Thanks sir I am from Bangladesh
Buhot shukria
Thank you Lodz keep it up for bless
Bless you sir
Hi, can you discuss more about AS440 AVR sensing voltage selection? specifically La and Lb.
Double check my other vlogs about it its there there is two vlogs about it
Ok, thanks.. Btw, I am having trouble with AS440 AVR. We've got supplied with AS440 instead of SX440. When running the generator we only get 40 VAC out and cannot increase. Direct Exciting with the battery increases the voltage.
@@JosephBilly-m8h thin meaning to say that avr itself is faulty
Is it possible to change the voltage sensing connection(T7, T8) of SX440 to U1 and neutral (N) when using AS440 AVR? or will it damage the AVR?
Hello. I have hard time to find someone smart enough in sweden. So i try to ask you. I have a faulty avr on my stamford generator. Its Stamford newage 350-29700. Du you think i can use as440 instead. Because i cant find 350-29700
Can u send me some pic i hive link m.me/ch/AbaxH-Wu4NQGcD2L/
Its posible but make sure you know what are those wiring you need to connect what voltage sensing you need too
@buhaygitmotropangpinoyofw157 search benjie moquite
@buhaygitmotropangpinoyofw157 kong double delta 220 naman sensing ng as440 tama so line to line kalang komoha ng v sensing nya
@buhaygitmotropangpinoyofw157 as 440dalawa lang yan sir exited at voltage sensing
Galing pod...lods
Tanks lods
Com a regulagem máxima do avr as 440 está 210v preciso aumentar a voltagem além da regulagem volts sem passar dos 60hz Oq eu posso fazer ? Onde eu posso regular ?
Bolahi must 220-240 regular voltage
Adjust in the avr volatge to rease up the voltage
Applicable ba ito sa single phase na generator na may auxillary winding
Yes
8 n 22 terminals for what purpose
8-z2 aux winding
Sir are you Filipino,I just want to ask our generator the C and 50hz and is connected but in monitor is 60 hz and rpm is 1800
Sir anong frenquency ba at pano nyo naconfig ang module
@@benzblogsVlogs Yun AVR ng Gen set namin Stamford AS440.yun Common nakalink sa may right side 50hz ang tanong ko sir bakit sa monitor 60hz/1800 rpm
@@philipcuntapay9354 check mo lng configuration ng module mo or yung mga analog na gamit mo
From Old Generator. Diagram is not available how do I find the terminal 7&8 , can I interchange it as trial?
No problem co this is voltage sensing 220 vac
@@benzblogsVlogs thankyou
@@benzblogsVlogs Boss we reach naman yong 230V, 60hZ 3phase , 35kVa... Using as440 AVR as we observe seems extreme heating ng heatsink ng as440, may need ba ako baguhin sa settings to reduce the heating? tska pano ko malalaman kung may auxiliary windings ang generator? baka need ko i follow yong isang diagram with auxiliary windings? thankyouu
@@mikeybeltran5820 sir makikita mo agad kong anong type ng alternator meron ka if shunt or arep if arep means meron na agad yumang aux winding hut if shunt its nothing aux winding
@@mikeybeltran5820 lot of heating check the excitation current of your avr baka masyadong mataas
how to adjust voltage of as440 ?
Sir check my yt for AS440 there all stated thank you
yes sir thank you, because the voltage output of our generator is only 205 vac and it cannot drive the 15hp submersible motor , it shutt down