I am starting a maintenance job and my work is related to this breaker repair category. It's great that you shared this with us, thank you very much for that. Wishing you and your family all the best
I'm a former Radio Operator and now I'm a OIC-NW license officer. I think some trouble shooting guide indicated on the block diagram. It's mean the trouble shooting will definitely in a particular place since the ship is almost new, so the solenoid (function is to amplified the required current in order to run the motor to open up.) Since the c/e and 1st/engr act a electrian onboard. But I think if the ship become old I think it's better to have an electrician who's knowledge in electronics techinical and we'll verse in such like computer, electronics, electrical and even knowledge in mechanical as well. Take care, God bless! Salute you sir. Peace
Hey jake, We had a similar situation onboard my vessel - during port state inspection the EMDG did not connect to the board(engineers swear they checked it before hand
I think there is a dedicated spring release mechanism in this kind of breaker. Also if you just close the breaker I think you just release the closing spring but the opening spring is still charged. Please correct me if I'm wrong Sir.. By the way I enjoy watching your videos they are very informative.
Nope it is the same spring for closing and opening. So if you close the breaker without the Motor connection or the Jack Cable then it will stay released unless you charge it
@@leckyjake Cone Dela Cruz, you are absolutely correct!! The closing spring / closing action charges the trip spring. That is why he was able to trip the breaker when the semaphore was showing the spring was discharged. The spring charged semaphore is just for the closing spring. To properly discharge all stored energy, on most spring close breakers, you need to disconnect spring charging motor, do a close operation to discharge closing spring, then do an open operation to discharge trip spring that was charged when the breaker was closed. Some breakers can even do two close operations on one spring charge cycle. So always close, open and try close again before sticking your fingers in the breaker mechanism.
May you please clarify a moment? If i press close on circuit breaker before rack out then it means that we take generator on bus bars. But generator not started. As a result redundant load on bus bar. Generator will act as an engine.
I like you video so usefully , if u have time please show me How to do the operated well of OWS (OIL WATER separator) on board and part of Name with funcion please..
Hi, I'm surprised, that ships VCB's doesn't have Relay switch circuit, to check the coils. I work in a hydro power plant and all our main switces have these sort of control.
And if it was mechanically sticking, it would have tripped when you had the control power removed from it. So what am I missing here? Is there a trip circuit monitor that was tripping it due to low resistance? Which normally only sends indication of an electrically open trip circuit. But I see an 85X device, which I am not familiar with. Thanks
I saw you pull the break out but no testing done. 3 tests need to be done. Contact resistance, insulation resistance, and a vacuum bottle integrity test. Grease all moving parts and if all tests look good rack it back in and test the relay.
Sir gud day... hndi ba sya delikado na mag testing nang VCB na nasa switchboard? Hndi ba pag mag Switch ON magsupply sya sa generator? Slamat..safe sailing....
I am starting a maintenance job and my work is related to this breaker repair category. It's great that you shared this with us, thank you very much for that. Wishing you and your family all the best
I'm a former Radio Operator and now I'm a OIC-NW license officer. I think some trouble shooting guide indicated on the block diagram. It's mean the trouble shooting will definitely in a particular place since the ship is almost new, so the solenoid (function is to amplified the required current in order to run the motor to open up.) Since the c/e and 1st/engr act a electrian onboard. But I think if the ship become old I think it's better to have an electrician who's knowledge in electronics techinical and we'll verse in such like computer, electronics, electrical and even knowledge in mechanical as well. Take care, God bless! Salute you sir. Peace
good day ka lecky! thank you for sharing your idea in troubleshooting in VCB. laking tulong po to sa amin ka leckky....
Thanks for sharing your knowledge, your videos are precious for us the unexperienced ETOs , what other causes can trip a reverse power alarm?
Thank you.
The most probable and obvious cause is the failure of prime mover. But as shown in this video it was a false alarm due to VCB failure.
Hey jake, We had a similar situation onboard my vessel - during port state inspection the EMDG did not connect to the board(engineers swear they checked it before hand
Thank you for the support
Excellent video great work sir ! waiting for more vidoes
Thank you
Great video. Great explanations.
Thank you so much
Experience is the best teacher
Jake you are doing great job, Pls keep it up.
Thank you
More respect from 🇸🇦 🙏 👏 🙌 💯
Thank you for sharing your knowledge and actual experience onboard. Godbless & more videos troubleshooting…
Keep SAFE 🙏 maraming salamat SA turo ninyo God bless 🙏
Can you please upload complete VCB rack out . Appreciate for all of your videos
your vedio is so informative thanks for sharing your knowledge 😊
Thank you Sir, for explanation and never stop to share to us
Good Jobs lecky,, you share everything you know
Thank you so much for Sharing your knowledge
Good job 👍 appreciate
astig sir... Thanks for sharing your knowledge... keep safe always
Very nice thank for sharing knowledge
I learned a lot from this video
Sir jake thank u more power gob bless i love eletrical...
I think there is a dedicated spring release mechanism in this kind of breaker. Also if you just close the breaker I think you just release the closing spring but the opening spring is still charged. Please correct me if I'm wrong Sir.. By the way I enjoy watching your videos they are very informative.
Nope it is the same spring for closing and opening. So if you close the breaker without the Motor connection or the Jack Cable then it will stay released unless you charge it
@@leckyjake Cone Dela Cruz, you are absolutely correct!! The closing spring / closing action charges the trip spring. That is why he was able to trip the breaker when the semaphore was showing the spring was discharged. The spring charged semaphore is just for the closing spring. To properly discharge all stored energy, on most spring close breakers, you need to disconnect spring charging motor, do a close operation to discharge closing spring, then do an open operation to discharge trip spring that was charged when the breaker was closed. Some breakers can even do two close operations on one spring charge cycle. So always close, open and try close again before sticking your fingers in the breaker mechanism.
Lecky thanks for this video, im Eto also but still learn
May you please clarify a moment?
If i press close on circuit breaker before rack out then it means that we take generator on bus bars. But generator not started. As a result redundant load on bus bar. Generator will act as an engine.
I like you video so usefully , if u have time please show me How to do the operated well of OWS (OIL WATER separator) on board and part of Name with funcion please..
Thank you for sharing this Boss Jake!!! Godbless
Hi,
I'm surprised, that ships VCB's doesn't have Relay switch circuit, to check the coils.
I work in a hydro power plant and all our main switces have these sort of control.
I love this video
Love you bro 🙏🙏
Hi..thank u for sharing...
Great video. Lots to learn in this
Can you do a video of boiler and boiler alarm???
Very informative sir jake.
thank you for the knowledge sharing.. stay safe po god bless..
Thank you very much
How do you think that the issue with the VCB it is reversed power , so why you didnt think there is something wrong with the generator?
Thank you sir for this very useful video
Very nice master
And if it was mechanically sticking, it would have tripped when you had the control power removed from it. So what am I missing here? Is there a trip circuit monitor that was tripping it due to low resistance? Which normally only sends indication of an electrically open trip circuit. But I see an 85X device, which I am not familiar with. Thanks
Where did my first comment go? I was genuinely curious.
I saw you pull the break out but no testing done. 3 tests need to be done. Contact resistance, insulation resistance, and a vacuum bottle integrity test. Grease all moving parts and if all tests look good rack it back in and test the relay.
Thanks for another knowledge, Sana wag kng magsawa na mag share ng mga idea leckyjake...
Sir gud day... hndi ba sya delikado na mag testing nang VCB na nasa switchboard? Hndi ba pag mag Switch ON magsupply sya sa generator? Slamat..safe sailing....
Galing mo nmn idol
Thank you sir
we usually just send ours out, and install a spare...so we get 'warranty"
thanks for sharing sir God bless
Refrigerator container does not cutoff set temperature please give some ideas
Set temperature display side blinks al52 code
how much is the return and supply? as well as the pressures
Thanks boos
Thank you very helpful
Very informative video, thanks for the share!!!
Good job sir take care
Salamat sa pag share lect God bless
God bless u sir🙏🙏
Thank you Master
hallo sir,how many persons electrician on your ship?
im all alone
Thank u so much boss....
That was awesome
❤❤
Cool.
Sir pwide lokal laguage lng tayo ( TAGALOG)?
sirgood video
How can you work MSB without blackout?
You isolate one generator usually you have 2 per side in case of one failure the other generator supply that line...
Bus tie breaker
O no 😂
Slmt sir leckyjake😁
Thanks sir leckyjake
Thank you for your support
In this video u had not shown the trouble shoot very clearly