Boiler not working. Heating System Diagnosis

Поделиться
HTML-код
  • Опубликовано: 1 дек 2024

Комментарии • 71

  • @SalimKhan-gk1fh
    @SalimKhan-gk1fh 6 лет назад +3

    Another excellent video hope you produce loads more! that is most probably a faulty relay on circuit board inside the time switch! ( The contacts on the relay itself usually burn/arc out Due to the load current on them) I’ve come across this quite a few times. to any heating guys out there I have saved a fortune replacing these relay switches on boiler PCBs . and they are only around £2 pound for a new relay unit!!

    • @HeatingGeek
      @HeatingGeek  6 лет назад

      I think your right. Its a relay or transformer issue. a: bad relays b: voltage too low when both relays need to be switched.

    • @millomweb
      @millomweb 5 лет назад +1

      Relay is fine - as clearly each works ok when only 1 at a time. It's most likely a dried out capacitor issue.

  • @ArifPolicewala
    @ArifPolicewala 7 месяцев назад

    That was very interesting Ollie. You really are a master in this. ❤

    • @HeatingGeek
      @HeatingGeek  7 месяцев назад

      I try. I cant remember anything about this video so I might rewatch it :-)

  • @Martindyna
    @Martindyna 5 дней назад

    Interesting video. Those Honeywell motorised valves are reliable units but eventually the rubber ball plug starts to disintegrate I guess. My 3 way example is 34 years old and only on its 2nd actuator head (i.e. it's been replaced once). I have noticed that my fairly new Grundfoss pump has suddenly started to vibrate more than usual, I'm guessing that a chunk of rubber from the Honeywell valve's plug has become lodged in one of the impeller vanes. Can't complain though after that time.
    I haven't got a magnetic filter on my system (they claim to incorporate a filter for non metallic debris) but I looked at a Worcester branded magnetic filter on my late parents system and it didn't appear to direct the water flow through to the non magnetic debris end traps positively.

  • @mrsayef1059
    @mrsayef1059 6 лет назад +2

    Just needed this videos for tommorrow, your video uploads are somehow synced with my problems always there when i need it 🙌😎

  • @Ed-fp9rx
    @Ed-fp9rx 3 года назад

    great video heating geek, not many videos actually show fault finding, good job

  • @DenisSmart-p1f
    @DenisSmart-p1f Год назад

    Very informative
    Keep spreading the love ❤️

  • @andrewmillwardwatford9410
    @andrewmillwardwatford9410 5 лет назад

    I love your logic progression and your component knowledge is excellent.

    • @HeatingGeek
      @HeatingGeek  5 лет назад

      Thanks. Most repairs are logical and sometimes you just need to take a second to think clearly. :-)

  • @woodbine66
    @woodbine66 6 лет назад +3

    Bit naughty installing that Vaillant without the pump being wired directly into it's electrics. Hex won't get a proper cool down on pump overrun. Thanks for another great vid. Please keep them coming!!!

    • @HeatingGeek
      @HeatingGeek  6 лет назад

      Its weird not putting that stuff right but I have been TOLD! We don't put right installation defects.

    • @woodbine66
      @woodbine66 6 лет назад

      Dead right. You haven't got time to go worry about the non-safety related defects in systems we see every day. Blame lies with the boiler installer.

    • @millomweb
      @millomweb 5 лет назад

      @@HeatingGeek Change your contract. Refuse to do work on systems you can't put right. If someone else comes along afterwards and find it's incorrect, you could get the blame for it !
      Or leave a sticker on it saying there are other faults with the system outside the contracted work.

    • @HeatingGeek
      @HeatingGeek  5 лет назад

      @@millomweb I can't be blamed for non safety installation defects. EVER. I can even be blamed for safety defects. Unless I miss them because of negligence. This whole game is a farce. :-)

    • @millomweb
      @millomweb 5 лет назад

      @@HeatingGeek I didn't say legally blamed !

  • @train4905
    @train4905 Год назад

    Fantastic job sir

    • @HeatingGeek
      @HeatingGeek  8 месяцев назад

      Sorry I didn’t respond to this comment. I didn’t see it in my feed. :-(

  • @jonkasch1244
    @jonkasch1244 5 лет назад

    when i want to chill out i put this on and relax as he takes you on the logic process , it's relaxing

    • @HeatingGeek
      @HeatingGeek  5 лет назад +1

      Oh dear. :-) Put you to sleep...

    • @jonkasch1244
      @jonkasch1244 5 лет назад

      @@HeatingGeek not to sleep , the info still goes in , i watch builds from cars to watches .

    • @HeatingGeek
      @HeatingGeek  5 лет назад

      @@jonkasch1244 I watch electronics, videos. :-)

  • @baitrunner1000
    @baitrunner1000 6 лет назад

    Great video and a common fault. We change loads of them Honeywell programmers for this ‘no click’ fault

    • @millomweb
      @millomweb 5 лет назад

      Are they always in airing cupboards ?

  • @melvinevans9981
    @melvinevans9981 6 лет назад +1

    Great video dude 👏🏻

  • @chohanchohan8208
    @chohanchohan8208 4 года назад

    Yes brv...Tricks of the trade...this will help alot of people who scared fault finding electrics....Wicked Video

  • @charliesinden8711
    @charliesinden8711 6 лет назад +3

    Mate, you're clued up

    • @HeatingGeek
      @HeatingGeek  6 лет назад

      Thanks :-) Sorry for the late reply. Been really busy with the baby etc

  • @peterryan7827
    @peterryan7827 5 лет назад

    i wonder if you can help with my baxi solo 18 HE ,it seems to be having what i think might be overheating stat probs,it reaches temperature then wants to cut out ,then keep trying to relight,if i press the reset button we can get it to go for quite a while then it sort of pops and starts the same prob over again ,Maybe you can suggest how old this model is,should we replace or is this a common small fault.

    • @HeatingGeek
      @HeatingGeek  5 лет назад +1

      Im not sure of the issue. If its consistent then you should call and engineer out who can investigate the issue.

  • @millomweb
    @millomweb 5 лет назад

    The "fault" is probably an electrolytic capacitor in the programmer drying out from heat from the DHW cylinder. I've gone through 2 Drayton timeswitches with the same problem (mounted in airing cupboard) yet the old (previous system install) Honeywell programmer's still working fine - so am still using that !
    With 1 of the Drayton(/iflo) - you can hear the relay buzzing - trying to operate - and a tap with a screwdriver's enough to get it to actually come on !
    I think the wiring on the one in the vid is worse than mine here at home - unbelievable !
    Makes you wonder why they don't put the indicator lights on the actual output thru the relay !

    • @kims-uw4hd
      @kims-uw4hd 10 месяцев назад

      Hi Se top of the comments from me

  • @haccogas2498
    @haccogas2498 6 лет назад +1

    Great video thanks

  • @vladimirstafasani4630
    @vladimirstafasani4630 5 лет назад

    Very nice video I like it👍
    Can you please do a video on how to wire central heating and hot water. Thanks

  • @extremephotography3911
    @extremephotography3911 4 года назад

    great videos mate what contract are you doing

    • @HeatingGeek
      @HeatingGeek  4 года назад

      I do a few different contracts. Mostly for manufacturers

  • @kims-uw4hd
    @kims-uw4hd 10 месяцев назад

    The problem with the programmer is the AC Capacitor dropper there will be a large X2 capacitor probably .47 uF that has dropped in value therefore there is only enough current to power one really at a a time. Your multimeter should be able to measure it. They are probable a £1 out of mouser, RS Rapid electronics

    • @HeatingGeek
      @HeatingGeek  10 месяцев назад

      I have a video in a couple of weeks you will like. :-)

  • @leaturk11
    @leaturk11 5 лет назад

    I hate other folks wiring, for some reason they always wire it like a birds nest..as usual a great vid..

    • @HeatingGeek
      @HeatingGeek  5 лет назад

      Sometimes it's ok. But not very often. :-)

  • @millomweb
    @millomweb 5 лет назад

    The sound on your videos is generally quite quiet in any case!

    • @HeatingGeek
      @HeatingGeek  5 лет назад

      Noted.

    • @millomweb
      @millomweb 5 лет назад

      @@HeatingGeek Still working through a pile of your vids - selected ones only.

  • @edcooper2396
    @edcooper2396 5 лет назад

    I'm an EE, I suspect Honeywell went for the cheapest of mains power supplies and elected to use a "capacitor dropper" these have a finite lifetime and is a crud decision for a heating controller. Inside will be a large yellow capacitor, replace it and it'll work again.

    • @HeatingGeek
      @HeatingGeek  5 лет назад +1

      Someone has done a video about this. I cant find it at the moment but its out there somewhere!!! Thanks for watching. :-)

    • @millomweb
      @millomweb 5 лет назад

      It's funny, I've same issue with 2 Drayton/iflo programmers - so have reverted to the old Honeywell from the previous installation ! Programmers all in airing cupboard. All the other same make/model programmers have worked flawlessly - but they're not in the airing cupboard!

  • @daveylad2
    @daveylad2 5 лет назад

    Enjoying you videos HG. Would the fact the boiler earth was out effect the flame rectification signal or would it work because it is going to ground through the copper pipes?

    • @HeatingGeek
      @HeatingGeek  5 лет назад +1

      It can effect it. On this one it didn't but it can and does.

  • @650GSF
    @650GSF 6 лет назад +1

    wiring always looks a pain in the arse to figure out ha ha, bet that would have had a few engineers scratching there heads.

    • @HeatingGeek
      @HeatingGeek  6 лет назад

      Thats why I use the 2 port or 3 port as a guide to what should be what. Usually works out.

    • @millomweb
      @millomweb 5 лет назад

      It won't fool engineers. Installers, maybe.

  • @mimo1dz38
    @mimo1dz38 6 лет назад

    An other nice vid 🖒👏

  • @pasgas12safe58
    @pasgas12safe58 6 лет назад +1

    Thanks for the video mate, very well described. Liked, saved & subscribed!👍😉
    Ps. Hope missus and baby doing well.💪

    • @HeatingGeek
      @HeatingGeek  6 лет назад +1

      Thanks. All doing well here. House is a dump..... 3 kids.... whats new!!!!

    • @pasgas12safe58
      @pasgas12safe58 6 лет назад

      @@HeatingGeekGlad to hear they're doing good!! Our Henry is 18 months old, only child after much heartache over 12 years!! We never gave up hope & Love him more than words can describe, even though the house looks like a laundrette, so I can imagine yours, but I know you love 'em dearly!!😀

    • @HeatingGeek
      @HeatingGeek  6 лет назад

      Wow. 12 years is really tough. We have been really lucky and I never thought about the possibility of it not happening. I don't know how tough that would be.
      I have three boys and every day is amazing. The older 2 are into fortnight and iPads and the baby cant even hold his head up!!! its great.
      Good luck to you, your lady and little Henry. Bikes, walking (Maybe he's started) all to come. Have fun!!!!

    • @pasgas12safe58
      @pasgas12safe58 6 лет назад

      @@HeatingGeek Thanks for your kind words mate😃 Yes he's walking alright & into everything, as you well know, with your eldest 2!! ipads & tech, we've got all that to come & I'll have to get more jobs in, lol. Glad yours are doing fine pal & thanks again.🙏😉

  • @kims-uw4hd
    @kims-uw4hd 10 месяцев назад

    Relay