How to test 3 port system wiring for issues. Reference Sheet at End of vid

Поделиться
HTML-код
  • Опубликовано: 22 май 2018
  • A Reference sheet is at the end of the video. There are issues with this wiring that I don't cover because they don't affect operation.
    To support this content and get access to the PDF files to go with this training click here: / heatinggeeks
    Injector cleaning tool: rover.ebay.com/rover/1/710-534...
    To support the channel and see the tools used day to day by me check out the links below:
    1) CARHARTT Tool Roll amzn.to/2yGiexO
    2) BAHCO Screwdriver with LED amzn.to/2Op5Ug1
    2)BAHCO Screwdriver without LED amzn.to/2yEhLML
    3)WERA Kraftform Kompakt Screwdriver amzn.to/2OnOe4K
    4)WERA 0.8x4x100 Flat screwdriver amzn.to/2RNcpra
    5) KNIPEX Alligator amzn.to/2RNctqU
    5)KNIPEX Cobra amzn.to/2PA5YWY
    same size as the alligator above just the “cobra” version
    6)BAHCO Spanner amzn.to/2IW3iR8
    6)BAHCO Spanner with slimline jaw amzn.to/2yHCq2i
    7)CK Wire cutters amzn.to/2RP19dW
    7)CK Wire cutters (shorter version) amzn.to/2OnJwnB
    8)KNIPEX bent long nose pliers amzn.to/2IW9uZ3
    9)TESTO 510 Digital U gauge amzn.to/2Cfz36a
    9)TESTO Bluetooth U gauge amzn.to/2IW4t30
    10)Mirror tool amzn.to/2OpKVKl
    11)Cheap as chips pick set!!! amzn.to/2OpK10o
    12)FLUKE alert volt stick amzn.to/2PxCYPF
    13)MONUMENT Tailing Spanner amzn.to/2OrypK8
    14)Tee Bar 4mm amzn.to/2yDPRAr
    15)Tee bar 2mm amzn.to/2yzbjGA
    16)Tee bar 2.5mm amzn.to/2OqqSvd
    17)Full Tee bar set amzn.to/2yAoIyk
    18)10mm ratchet spanner (flex head) amzn.to/2IWCoZ9
    19)8mm ratchet spanner (flex head) amzn.to/2IUDZP5
    20)14mm/15mm spanner amzn.to/2Aa6wgZ
    21)BAHCO small spanner amzn.to/2RRkKKH
    22)Cheap Lock knife amzn.to/2IWatZf
    23)Sharpie amzn.to/2IVrxPk
    24)Injector cleaning pins link coming soon. Review to follow.
    25)Rothenberger 18” heavy-duty pipe wrench amzn.to/2ChkRd6
    These are the heat duty ones I use.
    26)Knipex (large) amzn.to/2OrgfIm
    27)BAHCO 12” (not wide jaw) amzn.to/2Aatuob
    28)Fluke 115 multimeter amzn.to/2OqaFpF
    Drain down hose amzn.to/2RM4ZEN
    Gas Tap Grease amzn.to/2SE0jRL
    Led lights for the ​van. amzn.to/2Bh7RTQ
    Fluke 101 multimeter amzn.to/2PoLP5g
    Extech EX330 amzn.to/2AYq872
    Silicone grease amzn.to/2Rnls4F
    Fluke Twist Guard probes
    amzn.to/2CfwCz4
    Commando drills
    amzn.to/2L5f50u
    Weed Sprayer amzn.to/2Ryx1Hh
    Large LDF amzn.to/2I0ss4d
    NTC Clamps:
    amzn.to/2GVUWL5Also the valve makes a funny noise but works fine.
    If you are unsure about electrics consult a qualified professional.

Комментарии • 140

  • @buzzardc7
    @buzzardc7 6 лет назад +4

    Thanks for making these kind of videos. Always great advice given.

    • @HeatingGeek
      @HeatingGeek  6 лет назад +2

      Im not always right and don't mind being corrected. If my knowledge helps anyone then I should share it.

  • @jonhollamby7301
    @jonhollamby7301 3 года назад +1

    Thank you for this very useful video. Enabled me to diagnose the issue with the lack of hot water. Cylinder stat failed. Thanks again.

  • @Shandybrother
    @Shandybrother 6 лет назад +1

    Hey, congrats on addition to your family! great videos!

    • @HeatingGeek
      @HeatingGeek  6 лет назад

      Thanks.
      He's easy compared to his brothers but its still a shock to the system!!!

  • @DeeaKzy
    @DeeaKzy 6 лет назад +1

    Top work bud! Always good to see how other people work!

  • @leerolfe5332
    @leerolfe5332 5 лет назад +1

    20 years an installer man! keep these vids coming bruv i need too improve my tech side.

    • @HeatingGeek
      @HeatingGeek  5 лет назад

      I will as soon as I can get my laptop to work!!!

  • @martinjosephoconnor3613
    @martinjosephoconnor3613 Год назад

    Still using your vids for a refresh on y-plan faults. Just this week client had moved programmer base and put a permanent live on the grey, sounds easy now it's fixed but that test sequence you posted at the end got it sorted. Thanks.

  • @prophetnathan1989
    @prophetnathan1989 3 года назад +1

    Nice video, currently an apprentice and this has helped with my understanding. Keep up the good works mate

    • @HeatingGeek
      @HeatingGeek  3 года назад +2

      You should go through the How to wire playlist. Don't skip through no matter how boring they may seem. :-) ruclips.net/video/awqlFlHKmZA/видео.html

    • @prophetnathan1989
      @prophetnathan1989 3 года назад

      @@HeatingGeek thanks mate I appreciate it

  • @johnnysingh418
    @johnnysingh418 6 лет назад +9

    Always enjoy watching your videos' so much knowledge to pass on, keep them coming .

  • @brendanmoran9516
    @brendanmoran9516 2 года назад +2

    thank you for your videos. they are very good and have helped me out. keep up the great work.

  • @finandpebtv6299
    @finandpebtv6299 3 года назад

    Very helpful for a recent issue I’ve been tasked with, subscribing to this channel for sure

  • @sandraallsopp1234
    @sandraallsopp1234 5 лет назад

    I like your videos, very thorough thought process. Nice to see another heating engineer work! I use you as a teaching tool for my apprentice... you need a go pro though! On a 3 port that back feed 80v will keep a Viessmann 100w boiler on they have started giving you a resistor to fit, first time I came across that it messed with my head for ages!

    • @HeatingGeek
      @HeatingGeek  5 лет назад

      Worcester Ri's Glowworm Micron and Now (thanks to you) I know about Viessmann 100w. I have a gopro now but cant really work out how the best way to implement it. Check out the Worcester Cdi diverter video and Ideal logic sump video for how I'm doing it now.
      Ideal sump ruclips.net/video/LWYlV3D-GnY/видео.html
      Worcester Cdi diverter. ruclips.net/video/bX2BqZ-TYnY/видео.html
      Have a look at the tools vid and see if you think I'm right. I think its good for new guys.
      Tools. ruclips.net/video/GCa0sEc0CtQ/видео.html

  • @Carl-re6zb
    @Carl-re6zb 4 года назад +4

    Compared to most of what i come across on a regular basis, this box was wired quite neatly. At least it was easy to trace and check the wiring.
    Nice job once again Ollie.

    • @HeatingGeek
      @HeatingGeek  4 года назад

      It was wired well. I have some shockers on my phone. One thats ALL red. Mad :-)

  • @dzmalekvali1110
    @dzmalekvali1110 6 лет назад +1

    Thanks for the reply

  • @Hilliard82
    @Hilliard82 5 лет назад +1

    You know your stuff man. Your videos are amzing. Subscribed !!!!

  • @jaxmar88
    @jaxmar88 6 лет назад +1

    Of corse, because it a Baxi BBU there is no pump overrun, very informative video, I must admit I didn't know about the feedback to Micron & Worcester's shows your never too old to learn.

    • @HeatingGeek
      @HeatingGeek  6 лет назад +1

      Its not very common but does happen. When you pull out the S live the boiler stops. Unless you had it you wouldn't know. If you had it you never forget. ;-)

  • @TheRealBillyKent
    @TheRealBillyKent 6 лет назад +1

    Brilliant video mate!! Very useful

  • @barrylumsden6331
    @barrylumsden6331 Месяц назад

    I’m proud of you. Old school. I remember the old problem with the Worcester RI. Their technical used to tell you to convert it to splan before they brought out the new board. 🫶

    • @HeatingGeek
      @HeatingGeek  Месяц назад

      Our boilers are shit so fit a different system :-)

  • @simonnitro9574
    @simonnitro9574 Год назад +2

    Love your videos. Can you do a video on sorting a back feed voltage problem if the Ri is firing with no demand. Thanks you are the best

  • @baz9487
    @baz9487 3 года назад

    Mines a bloody mess! Had a new 3PZV by a plumber, put in and for some reason, i have to switch the mains off then back on again for the pump to kick in so gonna have to check my mess of a wire box. thanks for the vid

  • @adeyzzz5328
    @adeyzzz5328 2 года назад

    Hi, good video, thanks
    Trying to diagnose an issue, does the CH to boiler and pump only get 240 from the 3 way valve once it has moved out of the HW position into mid of full CH? Thanks

  • @paullenton2076
    @paullenton2076 5 лет назад +1

    Hi mate good vids and congratulations on the new arrival, I was looking at the stat wire and the earth is not connected, I was pulled up by a spark years ago because of this. Even though the stat has no need for the earth you still need protection within the cable, ie- if the cable gets cut, broken Or even drilled/screwed through the earth is there to protect whoever does this.

    • @HeatingGeek
      @HeatingGeek  5 лет назад +1

      Yes your totally correct. I was part P and my brother is a sparks so I know how bad a lot of the stuff we see is shit. The only problem is its ALL so bad. Where do you start.

  • @ShahedAhmed-er4ih
    @ShahedAhmed-er4ih 3 года назад +1

    This video is amazing

  • @puttingtechniques
    @puttingtechniques 2 года назад

    Great video thanks this helped a lot.

  • @train4905
    @train4905 Год назад

    A fantastic video sir very helpfull indeed.thanku

    • @HeatingGeek
      @HeatingGeek  Месяц назад

      Sorry I didn’t respond to this comment. I didn’t see it in my feed. :-(

  • @seankirby2580
    @seankirby2580 4 года назад +1

    This is excellent. I changed my Ideal heat-only boiler for an Ideal Logic + condensing heat only one. It's Y-plan connected with a 3-port valve. I had trouble with the boiler over-running the circulator pump and had to rewire the snake pit of wiring. I did it 95% right but noticed the radiators getting warm after the hot water only mode has run for 20 mins, so I have it wrong. This video will help. I see Honeywell do a proper wiring centre. Are these any good? All I have currently is a 10 space choc-block in an enclosure. It's a disgrace.

    • @HeatingGeek
      @HeatingGeek  4 года назад +2

      I have done a whole series on wiring. Check the Playlist tab and you will find it.:-)

  • @mo-gc3ik
    @mo-gc3ik 5 лет назад +1

    hi, very good explanation.

  • @classicalcarpenter4297
    @classicalcarpenter4297 5 лет назад

    Hi HeatingGeek. I am an electrician and I will produce a fault finding chart and drawings so people can see what and why they are testing. Whether it is better or more useful than yours remains to be seen. One piece of advice, get a lead with croc clip (IGNPION 0.15”(4mm) 5PC Banana Plug to Crocodile Alligator Clip Test Probe from Amazon £9.00) or grips so you can get a good neutral or earth and you only have to poke around with one lead. I have glued magnets on the back of my old meter so I can stick it to metal consumer units and that works well. Keep up the good work.

    • @HeatingGeek
      @HeatingGeek  5 лет назад +1

      I do have crocodile clips for the MM but I try and pack light for the scooter. There is usually somewhere to wedge a probe tbh. Also remember that (on boilers) the neutral may have failed on the specific item your testing (ie downstream on the PCB), so if you use a generic earth point the potential difference will be there and you would miss the PCB fault. Hope that makes sense... Im tired and rambling!
      PS the magnet is a good shout. Fluke charge a lot for a magnet to attach!!

    • @HeatingGeek
      @HeatingGeek  5 лет назад

      Yes. When I know I can or if i'm going into central London. Usually I work from a van though.

    • @HeatingGeek
      @HeatingGeek  5 лет назад

      Im usually going after several engineers (when I'm Contracting) so usually the correct part has been fitted but not set up or the customer is just happy to have a correct diagnosis.
      When I'm working for myself I will go and get the part and go back if needed. I usually bring what I think is the issue with me. I do fixed price labour so customer doesn't mind!

  • @TheDickPuller
    @TheDickPuller 6 лет назад +1

    Of course the first check would be LNE & fuse size. This would confirm Polarity etc.
    This is always better checked at the ‘10 Way’ & the boiler. Always check for random links at the boiler terminals too.
    Good video mate👍

    • @HeatingGeek
      @HeatingGeek  6 лет назад +4

      I should do a basic electrical checks video. Safe isolation, polarity, resistance to Earth, short circuit etc but i don't think people would be interested. Fixing stuff YES, safe isolation?? not sure.

    • @TheDickPuller
      @TheDickPuller 6 лет назад +1

      HeatingGeek Without these basic initial check, you could’ve ‘backfeed’ issues & a dodgy N or E can give you rectification boiler problems,
      not with an old BBU, but most modern appliances.
      Keep the videos coming mate, very enjoyable.......Go on be brave, do one on the guts of a 3 Port actuator - diodes, resistors etc👍😜

    • @markrainford1219
      @markrainford1219 5 лет назад +1

      John Wards channel has already covered this in depth.

  • @jcb208
    @jcb208 5 лет назад

    Thanks for the video,After some advice my boiler fires fine with call for HW but when the heating is first turned on some times it takes several minuites before the pump starts and boiler fires, any ideas thanks

    • @HeatingGeek
      @HeatingGeek  5 лет назад

      Sounds like a syncron motor issue. Get an engineer out and he will sort it quickly.

  • @moulesanctuary
    @moulesanctuary 4 года назад

    Just brilliant mate

  • @shahidmussa7693
    @shahidmussa7693 3 года назад

    can you help answer me something please, when i put the heating on at the programmer it doesnt fire up the boiler. so does this mean i only get hot water when the heating is on?

  • @dominichalliday8929
    @dominichalliday8929 5 лет назад

    That backfeed voltage has caught me out before with ri,s. Do you know how it gets by the 3 port? It can't be the microswitches surely, can it?

    • @HeatingGeek
      @HeatingGeek  5 лет назад +2

      I think it is there to hold the valve in the set position. So its meant to be there...... I think...

  • @simsy1982
    @simsy1982 Год назад

    Thanks for your videos.
    I’m going to one today where the heating is staying on if heating only is on and then turned off at the programmer the pump and boiler stay on (3 port)
    If I put the hot water on at the programmer with the heating and turn the cylinder stat down it then turns it off. Really odd

    • @HeatingGeek
      @HeatingGeek  Год назад

      I have a video on that. It's usually a Ri, Micron or Logic. I cant remember what video it is now...

  • @mikemcdermott4870
    @mikemcdermott4870 2 года назад

    When you go in to hot water only should the arm return back over when I turn my hot water back off? Great video by the way

    • @HeatingGeek
      @HeatingGeek  2 года назад

      No, the arm will stay in HW only until a new demand Is given.

  • @normanboyes4983
    @normanboyes4983 3 года назад

    Still catching up on your back catalogue. Off the wall and broadly irrelevant question - what do you thing of the relatively newly introduced WAGO based wiring centres - and have /would you use one?

    • @HeatingGeek
      @HeatingGeek  3 года назад

      I have always been very slow to accept new technology. I use normal wiring centres because I know what to expect. I know what I can fit (wire wise) and I know how tough they are. I will use a WAGO one when I have seen it in the flesh and can have a play with it. Until then, I like Drayton wiring centres.

  • @mimo1dz38
    @mimo1dz38 5 лет назад

    nice one mate😎

  • @taddy666
    @taddy666 5 лет назад +2

    Hi. Thanks for a great video. Very informative! I'm trying to diagnose a problem with my system at the moment and have noted that when the programmer is set to HW ONLY I'm getting a 240V reading on the 3-port valve's white wire when the cylinder thermostat is calling for heat. Surely this is incorrect!? The white wire is connected only to the programmer so should be off when set to HW only. Could the 2nd switch inside the 3-port valve be stuck so that the white is getting 240v from the orange? The water is heating but the radiators are also on. Thanks in anticipation. Tom

    • @HeatingGeek
      @HeatingGeek  5 лет назад

      What boiler do you have. I hate this fault. Hopefully you don't have micron...... or a UPSII pump.

    • @taddy666
      @taddy666 5 лет назад

      It's a Baxi solo 3. Can't remember what the pump is and I'm at work at the mo. Weirdly the white wire as behaving when I retested it last night but instead the CH only function was malfunctioning. So white and grey ON was not giving the 240V output on orange going into the SL of the boiler so boiler was turning off when it should have been supplying the CH. This I think could be that second switch sticking again but this time sticking on the default position. I think I just have to replace the 3 port valve and hopefully it'll be sorted.

    • @HeatingGeek
      @HeatingGeek  5 лет назад +2

      Just the head.
      To test this fault:
      1) turn heating and hot water on together. Valve should go Mid position. Low voltage on Grey and 240v on white and orange.
      2) turn hw off. valve should go to htg only (all the way across) grey, orange and white should be 240v.
      3)turn htg off and hw on. valve should motor back to Hw only and only orange should be live.
      4) if (3) dosent happen and the valve stays in htg only (grey has 240v) then I do a test that isn't safe and tells me where the 240v is coming from.
      If you turn the power off the fault will disappear.
      Usually the actuator is the issue. Most engineers just replace that and see if its fixed.

    • @taddy666
      @taddy666 5 лет назад

      Hey thanks so much! 2 is the problem. I don't have a HTG only function on my programmer (only HW or HW+HTG), but when I put it on HW+HTG it is fine until the cylinder reaches the thermostat temp and then instead of switching to HW only the boiler just shuts down. At this point the WHT is 240V, Grey is 240V (from the cylinder thermostat) but I'm not getting the expected 240 V from the valve's orange wire hence the shut down. I'm not sure whether I can replace the motor and actuator only as it is a LANDIS and Staffer valve and I think it is not detachable - as in if I pull the actuator out it's going to flood!

    • @HeatingGeek
      @HeatingGeek  5 лет назад

      Its the microswitch or motor. Im sure you can find a video on how to do it.
      Sorry for the late reply. I had no broadband for 5 days!!

  • @6804harry
    @6804harry 6 лет назад +1

    Excellent..

  • @henrybartlett1986
    @henrybartlett1986 3 года назад

    Great, as usual.

    • @HeatingGeek
      @HeatingGeek  3 года назад

      Glad you think so! Thanks for watching and commenting. It means a lot. :-)

  • @Dususdo
    @Dususdo 5 месяцев назад

    Great video but at about 1:43 do you say the orange should be 240v with the hw on then about 9.30 say you can remove the orange? Don't get that bit

    • @HeatingGeek
      @HeatingGeek  5 месяцев назад

      The reason is the orange will only have power when "CH only" is on. The orange is wired into the demand from the cylinder stat, so when the HW is on and their is a demand from the cylinder stat the valve hasn't moved to "CH Only" the power to run the boiler comes from the demand on the cylinder stat.
      It's very hard to explain over text.
      The simple answer is the orange on a 3 port (isolated from other wires) will only ever be live the you have a CH demand and no HW demand. I hope this helps

  • @YorkshireBeaver
    @YorkshireBeaver 3 года назад

    Cool video. If i can ask a question. Any idea why when hot water is switched on it shuts boiler down whatever heating is set to. Heating works fine on its own but not with hot water

    • @HeatingGeek
      @HeatingGeek  3 года назад +1

      The wiring is wrong or the cylinder stat is faulty.

    • @YorkshireBeaver
      @YorkshireBeaver 3 года назад

      @@HeatingGeek Wow. !! Yes it was a dry joint on cylinder thermostat live input. Thanks for replying thou. 😃

    • @HeatingGeek
      @HeatingGeek  3 года назад +1

      @@YorkshireBeaver I'm glad Its sorted and knowing wiring meant I had a good guess too. :-)

  • @Taqqiyastar
    @Taqqiyastar 5 лет назад

    Thanks alot

  • @mbroderick85
    @mbroderick85 3 года назад

    I cant find my 3 port valve. My junction box looks to be two faceplates with a 3amp fuse in one of them. The heating on doesnt circulate water in the rads unless it is combined with hot water on. No idea whats going on.

    • @HeatingGeek
      @HeatingGeek  3 года назад +1

      That could be how its meant to work. Old gravity systems were designed like that. What size are the pipes coming off the boiler?

    • @mbroderick85
      @mbroderick85 3 года назад

      @@HeatingGeek there is a valve but its behind a stud wall. I managed to install a nest combining the valve wire with the boiler and pump in the shed so all works at once. Cant have them separate due to it being an old system

  • @dzmalekvali1110
    @dzmalekvali1110 6 лет назад +1

    Thanks..hiw did you learn wirring

    • @HeatingGeek
      @HeatingGeek  6 лет назад +1

      The guy who trained me had me do wiring before I could even solder. I hated it at the time but it all came together and now its a great skill.

    • @dzmalekvali1110
      @dzmalekvali1110 6 лет назад +1

      Lucky you had good mentor..unluck me lol...chop chop..and go

  • @nrg-5003
    @nrg-5003 5 лет назад

    Hi there, I may have a potential issue with my central heating side of the system, I have a y plan with a worcester 18ri with pump overrun. When the central heating only is selected, I only get about 90v (from the orange wire) on the boiler demand terminal in the wiring centre, when the cylinder stat is satisfied. The boiler appears to still work and the pump runs. I can't help thinking if the pump wasn't switched from the boiler,i it would not work as the voltage on the orange is too low only 90v? The pump is wired directly to the wiring centre in the airing cupboard as you would expect with rest of the controls. The cylinder thermostat has recently been replaced, is it possible it could have been mis wired? its just the usual honeywell type, it has a short piece 3 core flex to the wiring center (Brown Blue and Green and Yellow)
    The boiler is in the kitchen as well as the receiver, from the receiver two 3 core and earth cables go to the wiring centre in airing cupboard.
    One cable contains (in the wiring centre)
    Red=hot water on, connected brown to cylinder stat common
    Yellow= central heating on, connected to white to 3 port valve
    Blue= hot water off, connected to grey to valve and the Green and yellow which is connected to the 2 terminal on the cylinder stat
    second cable
    Red=boiler demand, connected to the orange to valve and blue which is connected to 1 on the cylinder stat
    Yellow=Used to be unused but is now the pump live
    Blue=neutral
    Earths obviously speak for themselves.
    we have a hive active system so the room thermostat cable has been disconnected from the wiring centre.
    hope this makes sense thanks
    thanks

    • @HeatingGeek
      @HeatingGeek  5 лет назад

      If you have CH only on and then remove demand by turning off the room stat I think your boiler may stay on and the pump runs continuously? Ri's will often run with very low voltage on the switch live.
      Check this and let me know.

    • @nrg-5003
      @nrg-5003 5 лет назад

      @@HeatingGeek Hi there thanks for getting back to me, the boiler doesn't seem to turn off after I have switched off the central heating not immediately anyway, the green flame symbol is still on the boiler and the pump is running, the boiler does turn off after a good 5 minutes then about 3 minutes approx after the pump turns off.

    • @HeatingGeek
      @HeatingGeek  5 лет назад +1

      @@nrg-5003 you have 2 different issues I think. Your wiring is wrong (posable neutral issue) and your boiler is firing from back feed voltage from the 3 port. These are issues an engineer will need to find the solution for.
      Good luck and I hope you get it sorted.

    • @nrg-5003
      @nrg-5003 5 лет назад

      @@HeatingGeek thanks I will get it looked at, do you recon the 3 port valve has an open/loose neutral? Did the cylinder thermostat sound like it was wired correctly? or do you think the 1 and the 2 terminals could have been mixed up?
      the cylinder stat is a honeywell L641A1039
      thanks

    • @HeatingGeek
      @HeatingGeek  5 лет назад

      @@nrg-5003 In your first post you said "When the central heating only is selected, I only get about 90v (from the orange wire) on the boiler demand terminal in the wiring centre, when the cylinder stat is satisfied." This statement means you don't quite understand how the system works.
      Regardless of the cylinder stat position, when only heating is selected, the 240v for HW OFF is supplied from the programmer or HIVE. So your last question cannot be answered. More clarity is required on exactly what voltage you have where with what demand on.
      Sorry, I know it doesn't help but I can't with the information provided.

  • @joanofarc708
    @joanofarc708 Год назад +1

    What a mess fair play to you i haven't the patience for shit like that

    • @HeatingGeek
      @HeatingGeek  Месяц назад

      Sorry I didn’t respond to this comment. I didn’t see it in my feed. :-(

  • @melvinevans9981
    @melvinevans9981 6 лет назад +2

    That re- wiring looks great hmm. And done one handed lol with phone in hand haha

    • @HeatingGeek
      @HeatingGeek  6 лет назад

      I didn't wire this. At all. Spur is in a wooden box.... Welcome to the 60s

    • @melvinevans9981
      @melvinevans9981 6 лет назад +1

      HeatingGeek hahaha this is modern 60’s do a Honeywell course and it’s perfect

    • @HeatingGeek
      @HeatingGeek  6 лет назад

      Heating engineers are really bad at wiring. Im really bad at testing with an iPhone 6 in my hand.

  • @theetheeyog9878
    @theetheeyog9878 5 лет назад +2

    Jhon ward done a good diagrams of this on his chanel hes a electrichen

  • @anthonycosta2613
    @anthonycosta2613 6 лет назад +4

    Teach me master 🙏

  • @B1cam
    @B1cam 4 года назад

    I love a OAP house.

    • @HeatingGeek
      @HeatingGeek  4 года назад

      To true. Lovely old dear. ;-)

  • @johnjackson1106
    @johnjackson1106 2 года назад

    Where should the grey wire go on a three port system pls.. I’m desperate.

    • @HeatingGeek
      @HeatingGeek  2 года назад +1

      Hot water off. So should join 2 other wires.

    • @johnjackson1106
      @johnjackson1106 2 года назад

      @@HeatingGeek Thanks, I’ve got a black from tank stat.and the grey from the valve, .. where do I put them? Pls.

    • @HeatingGeek
      @HeatingGeek  2 года назад +1

      @@johnjackson1106 I have a video showing how to wire a 3 port system. If your system is a normal 3 port system, the grey wire goes to 2 other wires.1 will be from the cylinder stat (satisfied) and the other will be from the timer/programmer. (hot water off)

    • @johnjackson1106
      @johnjackson1106 2 года назад

      @@HeatingGeek you are brilliant 👍👍. Thanks for taking the time to help me. I’ll msg you when I’ve got the hot water back on.

    • @HeatingGeek
      @HeatingGeek  2 года назад +1

      @@johnjackson1106 I hope you got it sorted

  • @alantagg57
    @alantagg57 4 года назад

    I don't know what has already been commented but I wonder what the cuddly dog has been used for near the vent?

    • @HeatingGeek
      @HeatingGeek  4 года назад

      What time?

    • @alantagg57
      @alantagg57 4 года назад

      @@HeatingGeek 17.05. So often used as a draught excluder for vents

    • @HeatingGeek
      @HeatingGeek  4 года назад

      @@alantagg57 I see what you mean. :-) that's probably exactly what it is. :-0

  • @fargogemini694
    @fargogemini694 5 месяцев назад

    Definitely a cowboy plumbers wiring

    • @HeatingGeek
      @HeatingGeek  4 месяца назад

      Welcome to UK heating system writing.

  • @SpikesMavic
    @SpikesMavic 3 года назад +1

    If someone rewired the system and that sorted the original problem, why would they ask you to check the wiring !

    • @HeatingGeek
      @HeatingGeek  3 года назад +2

      Because they weren't sure. :-)

  • @leaturk11
    @leaturk11 5 лет назад

    I would just rewire it..hate other folks wiring

    • @HeatingGeek
      @HeatingGeek  5 лет назад

      I often do. I usually give it 20min and then rewire.

  • @lazenbytim
    @lazenbytim 4 года назад

    I know it sounds like I'm having a go. But if I open a j/box and see that the first thing i do is show the customer and tell them I gotta rewire it. That's what I call a snakes wedding. Aweful just shocking. Otherwise your just chasing your tail. Again IMHO

    • @HeatingGeek
      @HeatingGeek  4 года назад +2

      You cant rewire a junction box on an insurance contract. You have to fix 8 jobs a day :-)

  • @colingreig3460
    @colingreig3460 2 года назад

    Who TF did that wiring? Was that one of the boiler monkeys again? What an absolute mess. That should be condemned. Under no circumstances was that ever carried out by a proper time served electrician. Shameful and embarrassment to the trade.

    • @HeatingGeek
      @HeatingGeek  2 года назад +1

      Welcome the the heating industry:-)